In short. Protection decides what happens in the first fraction of a second after a fault: whether only the faulty circuit trips, or the whole site goes dark. In a generator-backed system this is harder, because generators supply far less fault current than the grid, and settings that work on mains may not trip on generator. Good protection starts from fault levels, coordinates every device, and is tested and maintained.
Who this section is for: For consultants, electrical engineers and facility managers specifying, setting or maintaining switchgear and protection on generator-backed systems.
Key facts
- Breaker ratings must exceed the highest fault level.
- Settings must still trip at the lowest fault level, often on generator.
- The nearest device to a fault should trip first.
- Generators need their own protection: reverse power, unbalance, earth fault.
- Earthing and neutral arrangements change with the source.
- Untested protection is unproven protection.
How this section is organised
| Group | Questions it answers | Start with |
|---|---|---|
| Switchgear and devices | Which breakers and boards? | Device selection |
| Fault levels and coordination | Will the right device trip? | Coordination and selectivity |
| Earth faults | Will earth faults be detected? | Earth-fault protection |
| Generator protection | What protects the set itself? | Generator protection relays |
| Changeover and paralleling | How are sources switched safely? | Changeover switchgear |
| Earthing and surges | Is the site safe during faults and lightning? | Earthing and bonding |
| Testing and life | Does it still work? | Testing and commissioning |
Worked example: a feeder that would not trip on generator (illustrative)
| Item | On mains | On generator |
|---|---|---|
| Fault current at a 250 A feeder | About 18 kA | About 2.5 kA |
| Instantaneous setting | 10 × 250 A = 2.5 kA | Same |
| Result | Trips instantly | At or below the setting once trip tolerance and generator current decay are allowed for; may clear only slowly on the thermal element |
| Fix | Electronic trip unit with a lower short-time pickup, checked against selectivity | |
See fault-level engineering and setting philosophy.
Do not assume protection that works on mains also works on generator. Check every main feeder at the generator’s fault level.
Where to start
| If your question is… | Start with |
|---|---|
| Which protection for which fault? | Fault to protection |
| Neutral switching and earthing | Neutral and earth |
| Old switchgear | Switchgear modernisation |
| Arc-flash risk | Arc-flash mitigation |
Protection check sheet
| Item | Status |
|---|---|
| Fault levels known on mains and generator | |
| Settings coordinated | |
| Generator protection set | |
| Last injection test |
A protection study in the order the guides follow
| Step | What it settles | Guide |
|---|---|---|
| 1. Single-line diagram and sources | Every source, transformer, generator, board and large motor | Protection and switchgear systems |
| 2. Maximum and minimum fault levels | Breaking capacities, and whether settings will operate on generator supply | Fault-level engineering |
| 3. Device selection | Ratings, breaking capacity and trip units | Device selection |
| 4. Coordination on every source | Which device trips first, on grid and on generator | Coordination and selectivity |
| 5. Earth faults and earthing | Detection on each source and the neutral arrangement | Earth-fault protection |
| 6. Generator protection | Reverse power, unbalance, excitation, voltage and frequency | Generator relay architecture |
| 7. Arc flash | Clearing times where people work | Arc-flash mitigation |
| 8. Testing and records | Proof that the settings in the relays are the settings in the study | Injection testing |
What changes when the generator takes over
| Protection | On grid supply | On generator supply |
|---|---|---|
| Short-circuit elements | Tens of kiloamperes; instantaneous elements operate | A 250 kVA set sustains about 1044 A; many elements never pick up |
| Selectivity | Graded on high currents | Devices sit on flat parts of their curves; margins and backup can disappear |
| Earth fault | Set by the transformer earthing | Set by the generator neutral earthing, often lower |
| Arc flash | High current, fast clearing | Low current, possibly slow clearing and higher energy |
| Motor starting | Small voltage dip | Large dip; longer starts and undervoltage trips |
| Machine protection | Not applicable | Reverse power, unbalance, loss of excitation, over and under frequency |
Five checks for any site with a standby set
- Every main feeder’s short-circuit element picks up below the generator’s sustained fault current, or a generator setting group covers it.
- Something upstream still backs up each feeder on generator supply.
- Earth-fault detection works with the generator neutral arrangement, and neutral switching matches the earthing design.
- Undervoltage and stall settings ride through the largest motor start on the generator.
- The settings in the relays match the study, proved by injection and recorded.
A site that passes all five has protection that works on the source it depends on when the grid fails. Most sites that fail one fail it silently, because grid supply never exercises the generator case.
What to send us
Send your single-line diagram and breaker settings. WhatsApp 98852 01608 or use the application engineering enquiry.
All 42 guides in this section
- Electrical Protection and Switchgear Systems Guide — How protection and switchgear work together to detect faults, isolate them and keep healthy circuits running: devices, zones, coordination and testing.
- LV Switchboards, PCC, MCC and Distribution Architecture Guide — How low-voltage switchboards, power control centres and motor control centres are arranged, with form of separation, busbar ratings, incomer and feeder design, and what to specify.
- ACB, MCCB, MCB and Protection Device Selection Guide — How to choose between air, moulded-case and miniature breakers and fuses: ratings, breaking capacity, trip units, selectivity and what suits generator duty.
- Short-Circuit and Fault-Level Engineering Guide — How fault levels are estimated for utility and generator systems: source contributions, transformer impedance, motor input, generator decay, and how results set ratings and settings.
- Protection Coordination and Selectivity Guide — How to make the protective device nearest a fault trip first, using time, current and zone methods, with margins, generator considerations and the checks that prove a coordination study.
- Overcurrent and Short-Circuit Protection Guide — How overload and short-circuit protection work: inverse-time and instantaneous elements, pickup and delay settings, and voltage-restrained protection for generators.
- Earth-Fault and Ground-Fault Protection Guide — How earth-fault protection detects current to ground with residual, core-balance and neutral CT schemes, how earthing type changes fault current, and how to set and test it.
- Restricted Earth-Fault Protection Guide — How restricted earth-fault protection detects winding earth faults in generators and transformers: high and low impedance schemes, CT needs, stability and setting checks.
- Differential Protection Guide for Generators, Transformers and Buses — How differential protection compares current entering and leaving a zone: percentage bias, CT matching, inrush restraint, saturation and use on generators and transformers.
- Reverse Power and Generator Protection Guide — What reverse power, loss of excitation, overload and other generator protections do, why a motoring generator can damage its engine, and how to set and test these functions in parallel systems.
- Negative-Sequence and Phase-Unbalance Protection Guide — Why unbalanced currents overheat rotors and motors, how negative-sequence and unbalance protection detect them, and how thermal withstand limits shape the settings.
- Generator Protection Relay Architecture Guide — How to organise generator protection relays: functions by generator size, relay versus controller, redundancy, CT and VT arrangement and trip paths.
- Transformer Protection Guide for Distribution and Generator Step-Up — How transformers are protected: fuses and overcurrent, differential, REF, Buchholz and temperature devices, inrush and overexcitation, with typical schemes by transformer size and application.
- Busbar Protection Guide for Switchboards and Generator Buses — How busbar faults are detected and cleared: high-impedance and low-impedance differential, zone-selective interlocking, arc detection, CT needs and when each method suits LV and MV boards.
- Motor and Feeder Protection Guide — How motors and feeders are protected: overload, locked rotor, short circuit, earth fault, unbalance and undervoltage, with starter types, relay settings and generator-supply considerations.
- ATS and Changeover Switchgear Engineering Guide — How automatic transfer switches and changeover systems work: open, delayed and closed transition, pole count, ratings, sensing, timers, bypass and the checks for safe operation with generators.
- Synchronising and Paralleling Switchgear Guide — How paralleling switchgear lets generators share load: bus design, breakers, sync-check, controllers, load sharing, protection and the points to specify for multi-generator systems.
- DG Synchronising Panels Guide — What a DG synchronising panel contains and how it works: synchroniser, sync-check, breaker control, metering, load sharing, protection and the commissioning tests that prove a safe paralleling.
- Multi-DG Load Sharing and Power Management Guide — How parallel generators share kW and kVAr: droop, isochronous and communication-based sharing, power management for start-stop and load shedding, and commissioning checks.
- Breaker Interlocking and Transfer Logic Guide — How mechanical, electrical and key interlocks and transfer logic prevent unsafe paralleling and dead-bus closing, with typical schemes for multi-source boards and their tests.
- Protection CTs and VTs Guide — How current and voltage transformers feed protection: accuracy classes, burden, knee-point, saturation, ratio selection, polarity, grounding and common wiring faults that disable protection.
- Protection Relay Setting Philosophy Guide — How to define a setting philosophy before calculating settings: objectives, dependability versus security, margins, setting groups, documentation, change control and review for generator systems.
- Cable Protection and Coordination Guide — How protective devices are matched to cables: overload and short-circuit withstand, the adiabatic check, earth-loop impedance, voltage drop and selectivity, with generator-supply considerations.
- Neutral Protection and Neutral-Earth Architecture Guide — How neutral and earth connections are arranged on generator systems: solid, resistance and unearthed neutrals, single earthing point, three- versus four-pole switching and neutral protection.
- Earthing, Bonding and Equipotential Architecture Guide — How earthing and bonding make an installation safe and quiet: protective earth, equipotential bonding, functional earth, generator frame and neutral earthing, and the tests that verify them.
- Earth-Electrode and Soil-Resistivity Engineering Guide — How soil resistivity is measured and how electrode type, depth, spacing and treatment determine earth resistance, with seasonal variation, corrosion, testing methods and design steps.
- Lightning Protection and SPD Coordination Guide — How lightning and surge protection fit together: air terminals, down conductors, earthing, surge protective devices by zone, coordination, generator and control circuit protection and inspection.
- Breaker Failure and Backup Protection Guide — What happens when a breaker does not open on a trip command, how breaker-failure schemes clear the fault through other breakers, and how backup protection is timed, tested and coordinated.
- DC Control Power, Trip Circuits and Battery Systems Guide — Why protection depends on DC supply: battery and charger sizing, trip circuit supervision, redundancy, earth-fault monitoring, autonomy and maintenance for switchgear controls.
- Protection Alarms, Events and Disturbance Records Guide — How to use relay alarms, sequence-of-events logs and disturbance records to find the cause of trips, with time synchronisation, alarm design, retrieval practice and a post-trip analysis method.
- SCADA, BMS and Remote Electrical Monitoring Guide — How switchgear and generators are monitored remotely: points list, protocols, gateways, alarm philosophy, cybersecurity, data quality and what to monitor for early warning and fast response.
- Switchgear Testing and Commissioning Guide — The tests that prove switchgear before energising: visual, mechanical, insulation, contact resistance, CT and VT checks, protection and interlock tests, functional tests and handover records.
- Primary and Secondary Injection Testing Guide — How injection testing proves protection: secondary versus primary injection, what each covers, test plans for pickup, timing and logic, safety, record keeping and typical findings.
- Protection Maintenance and Lifecycle Testing Guide — How to keep protection and switchgear dependable over time: maintenance intervals, condition-based checks, breaker servicing, relay testing, battery tests, thermography and end-of-life planning.
- Legacy Switchgear Modernisation and Retrofit Guide — Options for ageing switchgear: condition assessment, retrofit breakers, relay replacement, partial and full replacement, outage planning, safety and the decision factors for each route.
- Critical-Power Protection Architecture Guide — How to design protection for critical-power systems: selectivity, redundancy, fast bus clearing, generator and UPS protection, DC independence, testing without outage and failure-mode thinking.
- Protection Failure-Mode and Resilience Engineering Guide — How protection fails (relay, CT, DC, trip circuit, settings, human error), how to analyse these failure modes, and design measures that keep it dependable.
- Electrical Fault to Protection Technology Selection Guide — Map each electrical fault or abnormal condition, such as short circuit, earth fault, overload, reverse power or arc, to the protection technology that detects it and the guide to read next.
- Under/Overvoltage and Frequency Protection Guide — How voltage and frequency relays protect generators, motors and loads, with typical elements, settings logic, time delays, loss-of-mains use and coordination with the generator’s own controls.
- Utility Plus DG Synchronisation Guide — How a generator is paralleled with the utility: permissions, sync-check, protection, anti-islanding, export control, grid-code needs and the tests required before operating in parallel.
- Arc-Flash Risk and Mitigation Engineering Guide — What arc flash is, what sets incident energy, how a study is structured, and mitigation options: faster clearing, maintenance mode, arc detection, remote operation and labelling.
- Switchboard Thermal and Busbar Engineering Guide — How heat limits switchboard capacity: busbar rating, temperature rise, ventilation, derating by ambient and altitude, joints, short-circuit forces and thermography.
Questions engineers ask
What should a protection study include for a site with a generator?
Maximum and minimum fault levels on every source, device ratings checked against the maximum, and every short-circuit and earth-fault setting checked against the minimum, which is usually the generator figure. Coordination is then plotted for grid, generator and any parallel mode, followed by the generator machine protection, an arc-flash assessment and injection testing of the final settings.
Why can a board lose its backup protection on generator supply?
Because the incomer long-time setting is sized for the transformer, and a generator may never reach it. A 250 kVA set sustains about 1044 A, below the 1440 A long-time setting of a 1600 A incomer, so if a feeder fails to clear, nothing upstream operates. The generator relay, with voltage-restrained overcurrent, has to provide that backup.
Why do breakers that work on mains sometimes fail to trip on generator?
A generator delivers much lower fault current than the grid, so breakers set for mains fault levels may not trip fast enough. Protection must be checked for the generator source as well. A coordination study covering both sources shows the settings that clear faults quickly on generator supply while staying selective on mains, and the settings are recorded and tested at commissioning.
What is reverse power protection?
It trips a generator that starts drawing power instead of supplying it, which happens in paralleled systems when an engine loses fuel or fails, preventing the set being motored. Motoring can damage the engine and overloads the other sets, so the relay is set to the maker guidance, usually a small percentage of rating with a short time delay, and tested at commissioning.
Engineering content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026. For advice on your own site, send us your requirement or call 98852 01608.