Electrical Protection and Switchgear

Protecting generator-backed systems: breakers, relays, coordination, generator and earth-fault protection, switchgear, earthing and testing.

In short. Protection decides what happens in the first fraction of a second after a fault: whether only the faulty circuit trips, or the whole site goes dark. In a generator-backed system this is harder, because generators supply far less fault current than the grid, and settings that work on mains may not trip on generator. Good protection starts from fault levels, coordinates every device, and is tested and maintained.

Who this section is for: For consultants, electrical engineers and facility managers specifying, setting or maintaining switchgear and protection on generator-backed systems.

Key facts

  • Breaker ratings must exceed the highest fault level.
  • Settings must still trip at the lowest fault level, often on generator.
  • The nearest device to a fault should trip first.
  • Generators need their own protection: reverse power, unbalance, earth fault.
  • Earthing and neutral arrangements change with the source.
  • Untested protection is unproven protection.

How this section is organised

GroupQuestions it answersStart with
Switchgear and devicesWhich breakers and boards?Device selection
Fault levels and coordinationWill the right device trip?Coordination and selectivity
Earth faultsWill earth faults be detected?Earth-fault protection
Generator protectionWhat protects the set itself?Generator protection relays
Changeover and parallelingHow are sources switched safely?Changeover switchgear
Earthing and surgesIs the site safe during faults and lightning?Earthing and bonding
Testing and lifeDoes it still work?Testing and commissioning

Worked example: a feeder that would not trip on generator (illustrative)

ItemOn mainsOn generator
Fault current at a 250 A feederAbout 18 kAAbout 2.5 kA
Instantaneous setting10 × 250 A = 2.5 kASame
ResultTrips instantlyAt or below the setting once trip tolerance and generator current decay are allowed for; may clear only slowly on the thermal element
FixElectronic trip unit with a lower short-time pickup, checked against selectivity

See fault-level engineering and setting philosophy.

Do not assume protection that works on mains also works on generator. Check every main feeder at the generator’s fault level.

Where to start

If your question is…Start with
Which protection for which fault?Fault to protection
Neutral switching and earthingNeutral and earth
Old switchgearSwitchgear modernisation
Arc-flash riskArc-flash mitigation

Protection check sheet

ItemStatus
Fault levels known on mains and generator 
Settings coordinated 
Generator protection set 
Last injection test 

A protection study in the order the guides follow

StepWhat it settlesGuide
1. Single-line diagram and sourcesEvery source, transformer, generator, board and large motorProtection and switchgear systems
2. Maximum and minimum fault levelsBreaking capacities, and whether settings will operate on generator supplyFault-level engineering
3. Device selectionRatings, breaking capacity and trip unitsDevice selection
4. Coordination on every sourceWhich device trips first, on grid and on generatorCoordination and selectivity
5. Earth faults and earthingDetection on each source and the neutral arrangementEarth-fault protection
6. Generator protectionReverse power, unbalance, excitation, voltage and frequencyGenerator relay architecture
7. Arc flashClearing times where people workArc-flash mitigation
8. Testing and recordsProof that the settings in the relays are the settings in the studyInjection testing

What changes when the generator takes over

ProtectionOn grid supplyOn generator supply
Short-circuit elementsTens of kiloamperes; instantaneous elements operateA 250 kVA set sustains about 1044 A; many elements never pick up
SelectivityGraded on high currentsDevices sit on flat parts of their curves; margins and backup can disappear
Earth faultSet by the transformer earthingSet by the generator neutral earthing, often lower
Arc flashHigh current, fast clearingLow current, possibly slow clearing and higher energy
Motor startingSmall voltage dipLarge dip; longer starts and undervoltage trips
Machine protectionNot applicableReverse power, unbalance, loss of excitation, over and under frequency

Five checks for any site with a standby set

  • Every main feeder’s short-circuit element picks up below the generator’s sustained fault current, or a generator setting group covers it.
  • Something upstream still backs up each feeder on generator supply.
  • Earth-fault detection works with the generator neutral arrangement, and neutral switching matches the earthing design.
  • Undervoltage and stall settings ride through the largest motor start on the generator.
  • The settings in the relays match the study, proved by injection and recorded.

A site that passes all five has protection that works on the source it depends on when the grid fails. Most sites that fail one fail it silently, because grid supply never exercises the generator case.

What to send us

Send your single-line diagram and breaker settings. WhatsApp 98852 01608 or use the application engineering enquiry.

All 42 guides in this section

Questions engineers ask

What should a protection study include for a site with a generator?

Maximum and minimum fault levels on every source, device ratings checked against the maximum, and every short-circuit and earth-fault setting checked against the minimum, which is usually the generator figure. Coordination is then plotted for grid, generator and any parallel mode, followed by the generator machine protection, an arc-flash assessment and injection testing of the final settings.

Why can a board lose its backup protection on generator supply?

Because the incomer long-time setting is sized for the transformer, and a generator may never reach it. A 250 kVA set sustains about 1044 A, below the 1440 A long-time setting of a 1600 A incomer, so if a feeder fails to clear, nothing upstream operates. The generator relay, with voltage-restrained overcurrent, has to provide that backup.

Why do breakers that work on mains sometimes fail to trip on generator?

A generator delivers much lower fault current than the grid, so breakers set for mains fault levels may not trip fast enough. Protection must be checked for the generator source as well. A coordination study covering both sources shows the settings that clear faults quickly on generator supply while staying selective on mains, and the settings are recorded and tested at commissioning.

What is reverse power protection?

It trips a generator that starts drawing power instead of supplying it, which happens in paralleled systems when an engine loses fuel or fails, preventing the set being motored. Motoring can damage the engine and overloads the other sets, so the relay is set to the maker guidance, usually a small percentage of rating with a short time delay, and tested at commissioning.

Engineering content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026. For advice on your own site, send us your requirement or call 98852 01608.