Protection CTs and VTs Guide

How current and voltage transformers feed protection: accuracy classes, burden, knee-point, saturation, ratio selection, polarity, grounding and common wiring faults that disable protection.

In short. Relays see the power system only through current transformers (CTs) and voltage transformers (VTs). If a CT saturates, is wired with the wrong polarity, has the wrong ratio or is open-circuited, protection can fail to operate or trip wrongly. Choosing the right class, ratio and burden, and proving polarity and ratio at commissioning, matters as much as setting the relay.

Who this page is for: For protection engineers, panel builders and commissioning teams specifying and testing protection CTs and VTs.

Key facts

  • Protection CTs must stay accurate at fault current; metering CTs are designed to saturate early.
  • The burden (relay plus leads) must be within the CT’s rating.
  • Long leads to a 5 A secondary add a lot of burden; 1 A secondaries reduce it.
  • Never open-circuit a CT secondary with primary current flowing.
  • VTs need fusing and correct earthing of the secondary.
  • Prove ratio and polarity by primary injection or on load.

CT and VT basics

ItemMeaning
RatioPrimary to secondary current, commonly 5 A or 1 A secondary
Protection classAccuracy at a multiple of rated current, with a stated burden
BurdenLoad on the secondary: relay plus leads
Knee pointVoltage above which the CT starts to saturate
VT ratio and fusingSecondary voltage for relays; fuses protect wiring

Worked example: lead burden on a 5 A CT (illustrative)

Item5 A secondary1 A secondary
Lead length (go and return)2 × 60 m of 2.5 mm² copper, about 0.9 Ω
Lead burden = I² × R5² × 0.9 ≈ 22.5 VA1² × 0.9 ≈ 0.9 VA
Relay burdenabout 0.5 VAabout 0.5 VA
CT rated burden15 VA15 VA
ResultOverburdened: CT saturates early on faultsWell within rating

The long run to a remote relay room made the 5 A CTs unsuitable. Switching to 1 A secondaries solved it without changing the cables. See differential protection, where CT performance matters most.

Never open-circuit a CT secondary while primary current is flowing. The secondary voltage can rise to dangerous levels and damage the CT. Short the secondary first.

Testing

  • Ratio and polarity by primary injection. See injection testing.
  • Insulation and secondary wiring checks.
  • Magnetisation curve where knee point matters.
  • On-load check of currents and phase angles.

See overcurrent, earth fault and REF.

CT check sheet

The reference site’s main board, not the feeder in the example above. Burden is the figure that gets assumed rather than calculated, so it is worked here: lead burden is I²R, and with a 5 A secondary that I² is 25, which is why the leads dominate. Copper at 2.5 mm² is about 0.0074 Ω per metre of conductor, so a 60 m loop is 0.44 Ω and at 5 A that is 11.1 VA before the relay is connected at all.

CTRatio and classBurden (relay + leads)Polarity checked
Incomer phase CTs, neutral end1600/5 A, 5P20, 15 VA11.4 VA — 0.3 VA relay plus 11.1 VA in a 60 m loop of 2.5 mm²Yes, primary injection 14 March
Feeder 4 CTs250/5 A, 5P10, 10 VA4.0 VA — 0.3 VA relay plus 3.7 VA in a 20 m loopYes, primary injection 14 March
Generator differential CTs, both ends1600/5 A, 5P20, 30 VA12.1 VA, matched pair from one batchYes, and relative polarity between the two sets confirmed
Restricted earth fault, core balance400/5 A, 5P10, 10 VA2.1 VAYes, primary injection through the neutral earthing conductor
Metering CTs, incomer1600/5 A, class 0.54.0 VANot used for protection — designed to saturate at fault current
    
    
    

Row one is at 11.4 VA against a 15 VA rating, which passes — but with only 3.6 VA of margin for a longer run, a second relay on the same cores or a future addition. Had the panel been 100 m away instead of 30, the loop would have been 200 m and the leads alone 37 VA — more than twice the CT’s 15 VA rating, so it would have saturated during a fault, at which point the relay sees a current far below the real one and the protection under-reads exactly when it matters.

The same installation with 1 A secondaries would put 0.44 VA in those leads instead of 11.1, because the burden falls with the square of the current. That single choice is what makes long cable runs between a switchboard and a relay panel workable, and it is decided at the order stage, not on site.

The last row is the error that looks like a saving. Metering CTs are built to saturate early so that the instruments behind them survive a fault; a protection relay fed from one will under-read a fault current by a wide margin and may not pick up at all. Protection and metering take separate cores, always.

Protection CT classes and what each one promises

ClassWhat the maker guaranteesTypical use
5P (for example 5P20)Composite error within 5% up to the accuracy limit factor, here 20 times rated current, at rated burdenOvercurrent and earth fault where accurate operating times matter
10P (for example 10P10)Composite error within 10% up to the accuracy limit factorSimple overcurrent where some timing error is acceptable
PX (class X)No error figure; instead a stated knee-point voltage, secondary resistance and magnetising currentHigh-impedance differential and restricted earth fault, where the scheme is calculated from those three values
TP classesDefined performance through the DC offset of a faultFast schemes on large machines and high-voltage systems
Metering 0.2, 0.5, 1Ratio and phase error within limits from about 5 to 120% of rated current; saturate early by designEnergy metering and instruments, never protection

Worked example: the accuracy limit factor you actually get (illustrative)

The figure 20 in 5P20 holds only at rated burden. A CT with less burden connected stays accurate to a higher multiple, and one with more burden saturates sooner. The usual estimate is: effective factor = rated factor × (internal burden + rated burden) ÷ (internal burden + actual burden).

Take the incomer CT from the check sheet: 1600/5 A, 5P20, 15 VA, with an internal winding resistance of 0.08 Ω, which at 5 A is an internal burden of 25 × 0.08 = 2 VA. With the 11.4 VA actually connected, the effective factor is 20 × (2 + 15) ÷ (2 + 11.4) = 20 × 17 ÷ 13.4 ≈ 25, so the CT stays accurate up to about 25 × 1600 = 40 kA. Move the relay panel to the 100 m position described above and the connected burden becomes about 37.3 VA: the effective factor falls to 20 × 17 ÷ 39.3 ≈ 8.7, and the CT is accurate only up to about 8.65 × 1600 ≈ 13.8 kA. On a board with a 25 kA fault level, the relay would under-read every serious fault.

Worked example: knee-point voltage for a differential CT (illustrative)

High-impedance differential and restricted earth fault schemes are calculated, not chosen from a class. The CT must drive the worst through-fault current into the resistance of the other CT and its leads without the scheme operating, and it must not saturate before the relay does. The common rule is that the knee-point voltage should be at least twice the stabilising voltage.

StepWorkingResult
CT ratio and through-fault1600/1 A, 25 kA maximum through-fault25,000 ÷ 1600 = 15.6 A secondary
Loop resistanceCT winding 4 Ω; leads 2 × 60 m of 2.5 mm² at 0.0074 Ω per metre = 0.89 Ω4.89 Ω
Stabilising voltage15.6 × 4.89about 76 V
Minimum knee point2 × 76about 153 V; specify 200 V for margin

Note that the 1 A secondary is what keeps these numbers modest. The same scheme with 5 A secondaries would put five times the current through the same lead resistance, and the knee point needed would rise steeply. Both ends of a differential zone should be ordered together, from one batch, with the magnetising curve supplied.

Why fault current saturates CTs that pass a steady test

A fault rarely starts at the ideal point on the voltage wave, so its current carries a decaying DC offset. The flux the CT core must carry to reproduce that offset can be many times the flux for the steady fault current, roughly one plus the system X/R ratio in the worst case.

Close to generators and large transformers X/R is high, often 10 to 20, so a CT that is comfortably sized for the steady current can still saturate for the first few cycles. Instantaneous and differential elements act in exactly those cycles. That is why differential schemes are stabilised against through-faults and why their knee points carry the margin worked out above.

Choosing the voltage transformer

  • Ratio: at low voltage the relay usually connects directly to the busbar through fuses; at 11 kV a VT of 11,000/√3 to 110/√3 is common.
  • Class: 3P or 6P for protection, which holds accuracy from 5% of rated voltage upwards so the relay still measures during a fault; 0.5 or 1 for metering.
  • Burden: add up every relay, meter and transducer on the winding, then choose a rated burden above that total.
  • Residual winding: an open-delta winding gives the residual voltage that directional earth-fault and neutral voltage elements need.

One earth on every CT circuit

Each CT secondary circuit, like a VT secondary, is earthed at one point only. For most circuits that is the first terminal block near the CT; for a differential scheme it is often the relay star point, so that the whole scheme shares one reference. Two earths let currents in the station earth flow through the CT wiring and appear as false differential or residual current. During commissioning, lift the earth link briefly and measure insulation resistance to prove there is no second earth hidden in the wiring.

Common mistakes

  • Metering CTs used for protection.
  • Lead burden ignored on long runs.
  • Polarity assumed from drawings.
  • Open CT secondaries during work.

What to send us

Send CT and VT data, lead lengths and relay types. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Resistances and burdens are illustrative; makers’ data govern.

The voltage transformer side: fusing and one earth

Current transformers get the attention because the consequence of getting one wrong is dramatic. Voltage transformers fail more quietly, and two details account for most of it.

Fusing. A VT secondary is a voltage source behind a small transformer, and a short on its wiring will burn the winding out. Secondary fuses protect the VT, not the relay. The awkward part is what happens when one blows: the relay now sees a missing or depressed phase voltage, and any element that uses voltage will misbehave — a voltage-restrained overcurrent element becomes far more sensitive than intended, a loss-of-excitation element may see what looks like a collapse, and a directional element can reverse.

That is why fuse failure monitoring exists and why it should block the elements that depend on voltage rather than merely raise an alarm. A set tripped off a healthy bus by a blown secondary fuse is a common callout, and the fuse is the cheapest item in the panel.

One earth, chosen deliberately. The secondary needs exactly one earth point, at one end, decided in the design rather than by whoever wired it. Earth it in two places and circulating current flows in the earthing conductor between them, which appears to the relay as a residual voltage that is not there. Earth it nowhere and the secondary floats, so capacitive coupling from the primary puts the whole winding at an unpredictable potential and nothing reads correctly.

Both of these have the same signature in service: a protection scheme that behaves correctly during testing, when the VT wiring is quiet and the relay is fed from a test set, and behaves oddly on load. If a voltage-dependent element has ever tripped without an obvious cause, check the fuses, then count the earths, before changing any settings.

Questions engineers ask

What knee-point voltage does a differential CT need?

At least twice the stabilising voltage, which is the maximum through-fault secondary current times the CT winding and lead resistance. With 1600/1 A CTs, a 25 kA through-fault gives 15.6 A secondary; with 4 ohms of winding and 0.89 ohm of leads the stabilising voltage is about 76 V, so the knee point must be at least about 153 V. Specifying 200 V leaves margin.

What is the effective accuracy limit factor of a CT?

The multiple of rated current to which the CT stays accurate with the burden actually connected. It is roughly the rated factor times the internal plus rated burden, divided by the internal plus actual burden. A 5P20 15 VA CT with 2 VA internal burden reaches about 25 with 11.4 VA connected, but only about 8.7 with 37.3 VA, which is well below a 25 kA fault level on a 1600 A CT.

Why must a CT secondary never be open?

A CT forces its ratio of the primary current into the secondary circuit whatever the burden. If the circuit is opened with primary current flowing, the core saturates and the secondary voltage rises to peaks that can reach thousands of volts, endangering people and damaging insulation. Always short the secondary at a test block before disconnecting a relay or meter.

What is CT knee-point?

The secondary voltage above which the CT core begins to saturate, defined as the point where a 10% rise in voltage needs a 50% rise in magnetising current. Differential and restricted earth fault schemes are calculated from it: the knee point must usually be at least twice the stabilising voltage the scheme needs.

Can one CT serve protection and metering?

Not reliably. Metering cores are designed to saturate early so instruments survive faults, which makes them under-read fault current; protection cores stay accurate at many times rated current but are less accurate at normal load. Use separate cores, or separate CTs, for protection and metering.

What if a VT fuse blows?

The relay sees a missing or low phase voltage, and voltage-dependent elements can operate wrongly: voltage-restrained overcurrent becomes oversensitive, directional elements can reverse and undervoltage can trip a healthy set. Relays therefore include VT supervision, which detects the loss and blocks those elements rather than only raising an alarm.

This guide gives general principles. CT specification needs relay and fault data.