In short. Choose an ACB, MCCB or MCB by four things: its current rating, its breaking capacity at the point where it is installed, its trip characteristics, and how it coordinates with the devices above and below it. Breaking capacity must exceed the maximum fault level at that point, including what the generators and motors contribute. Trip settings must still operate at the minimum fault level, which on generator supply can be much lower.
Who this page is for: For electrical engineers, panel builders and contractors selecting circuit breakers for LV boards.
Key facts
- ACBs: large currents and high short-time withstand; incomers, couplers, generator breakers.
- MCCBs: medium currents; feeders, motors, sub-distribution.
- MCBs: small final circuits.
- Breaking capacity must exceed maximum prospective fault current at the point.
- A short-circuit trip element (instantaneous or short-time) must operate at minimum fault current, including generator-only supply.
- Check selectivity between upstream and downstream devices.
Device families
| Family | Typical range | Typical use |
|---|---|---|
| ACB | Larger currents, high short-time withstand | Incomers, couplers, generator breakers |
| MCCB | Medium currents | Feeders, motors, sub-distribution |
| MCB | Small currents | Final circuits |
Worked example: a feeder MCCB on grid and generator (illustrative)
| Check | Value | Result |
|---|---|---|
| Feeder load | 200 A | 250 A frame, set 220 A |
| Maximum fault at the board (grid plus motors) | about 32 kA | Breaking capacity 36 kA or more |
| Minimum fault at feeder end on generator only | about 1.5 kA | Instantaneous at 10 × 220 A = 2.2 kA (or 2.5 kA if set on the 250 A frame) would not operate |
| Fix | Electronic trip with short-time pickup about 1.1 kA, so the feeder clears on generator supply within its short-time delay, checked above motor starting current and within the cable withstand | |
Choosing the breaker for the grid fault level alone would have left the feeder unprotected on generator supply. See fault levels and fault current.
Do not pick a breaker by its current rating alone. Check its breaking capacity against the maximum fault, and its trip settings against the minimum fault on every source.
Coordination
The downstream device should clear first. Check time-current curves and the makers’ selectivity data for each pair. See differential protection for zones needing fast, selective clearing, and changeover switchgear.
Breaker selection sheet
The reference site used across this section — a 1000 kVA transformer with a 250 kVA standby set, separate from the feeder in the example above — filled in as a selection schedule. Two columns do the work: the maximum fault decides the breaking capacity, and the minimum fault on generator supply decides whether the short-circuit element will ever operate.
| Circuit | Load | Max fault | Min fault (generator) | Device and settings |
|---|---|---|---|---|
| Incomer, 1000 kVA transformer | 1391 A | 25 kA | — | 1600 A ACB, Icu 50 kA, Ir 1440 A, short-time 5760 A at 0.3 s |
| Generator incomer, 250 kVA | 348 A | 1.6 kA | 1.0 kA | 400 A ACB, Icu 25 kA, Ir 360 A, short-time 900 A at 0.2 s |
| Motor feeder, 45 kW | 78 A | 22 kA | 1.0 kA | 125 A MCCB, Icu 36 kA, Ir 88 A, magnetic 700 A |
| Sub-board, lighting and small power | 60 A | 18 kA | 1.0 kA | 100 A MCCB, Icu 25 kA, Ir 65 A |
| Final circuit, socket outlets | 20 A | 6 kA | 1.0 kA | 32 A MCB, C curve, Icn 10 kA |
Notice the generator incomer. Its breaking capacity need only cover 1.6 kA, so a 25 kA device is ample, and its short-time setting is pulled down to 900 A precisely because the set cannot produce more than about 1044 A for any length of time. A 400 A breaker left at a factory default of eight times would sit there and never trip.
Icu, Ics, Icw and Icm: the four short-circuit ratings
| Rating | What it means | Where it decides the choice |
|---|---|---|
| Icu, ultimate breaking capacity | The largest fault the breaker can interrupt; it may not be fit for further service afterwards | Must exceed the maximum prospective fault at that point |
| Ics, service breaking capacity | The fault it can interrupt and then carry on in service, stated as 25, 50, 75 or 100% of Icu | Incomers and critical feeders, where a breaker must stay in service after a fault |
| Icw, short-time withstand | The current it can carry closed for a stated time, usually 1 s, while a downstream device clears | Any breaker with a short-time delay for selectivity, mainly air circuit breakers |
| Icm, making capacity | The peak current it can close onto; at least 2.1 times Icu for ratings from 20 to 50 kA at low voltage | Breakers that may close onto a fault, such as generator and changeover breakers |
Worked example: why the service breaking capacity matters (illustrative)
A feeder breaker has an Icu of 36 kA and an Ics of 50%, that is 18 kA. The prospective fault at its terminals is 22 kA. It will interrupt a 22 kA fault, because that is within Icu, but it has not been tested to carry on in service afterwards: after such a fault it should be inspected and may need replacing.
On the same board, an incomer with Ics at 100% of a 50 kA Icu can clear the worst fault and stay in service. Where a breaker must keep working after clearing a heavy fault, choose Ics at or above the prospective fault, not just Icu. The making capacity follows the same logic: a breaker with an Icu of 50 kA must be able to close onto a peak of at least 2.1 × 50 = 105 kA.
The trip unit settings, one by one
| Setting | Protects against | On a site with a generator |
|---|---|---|
| L: long time, Ir and tr | Overload of the cable and the load | Set to the cable and load, the same on both sources |
| S: short time, Isd and tsd | Faults, with a delay for selectivity | Isd must sit below the generator’s sustained fault current, or a setting group is needed |
| I: instantaneous, Ii | Heavy faults close to the breaker | Often switched off on incomers so the short-time delay can grade |
| G: earth fault, Ig and tg | Earth faults too small for the phase elements | The most reliable fault element on generator supply, where phase fault current is low |
Electronic trip units also offer a thermal memory, which remembers recent overloads after a reset, and a neutral protection setting for four-pole breakers. Record every setting on the selection sheet; a trip unit left at factory defaults is a setting decision nobody made.
Cascading: when a smaller breaker is allowed below a larger one
A current-limiting breaker upstream can reduce the fault current that reaches a downstream breaker so much that the downstream one, rated below the prospective fault, is protected in combination. The makers publish tested combinations: for example a 25 kA feeder breaker below a particular 50 kA current-limiting breaker may be rated for 36 kA in that pairing.
Two cautions apply. The combination is valid only for the exact devices tested, so a substitution on site breaks it. And cascading usually means the upstream breaker trips too, so selectivity is given up for the faults above the downstream breaker’s own rating. It is a cost tool for final distribution, not for critical feeders.
Derating for heat and altitude
Breaker ratings are stated at a reference ambient, often 40 degrees Celsius around the breaker. Inside a closed panel in a hot switchroom the temperature can be well above that, and electronic trip units and thermal elements both respond. Use the maker’s derating tables for the actual panel temperature, and allow for altitude above about 2000 m where both current and voltage ratings fall. A 1600 A breaker may carry noticeably less in a sealed panel than on the test bench.
Common mistakes
- Breaking capacity below the fault level.
- Trip settings that never operate on generator supply.
- No selectivity check.
- Motor and generator contribution ignored.
What to send us
Send the single-line diagram, loads and fault levels. WhatsApp 98852 01608 or use the application engineering enquiry. See switchboard architecture.
Evidence note. Values are illustrative; studies and makers’ data govern.
Working out which family a circuit needs
The three families overlap in current rating, so the choice is rarely made on amps alone. Four questions settle it:
- What is the prospective fault current here? This sets the breaking capacity, and it is the one parameter that cannot be adjusted afterwards. An MCB rated 10 kA on a board that can deliver 18 kA is not a setting error, it is the wrong device.
- Does anything downstream have to stay on while this clears? If yes, the device needs an adjustable short-time element and a time delay, which in practice means an MCCB with an electronic trip unit or an ACB. Fixed-curve MCBs cannot be graded against each other with any confidence.
- What is the smallest fault current this device must still clear? On a site with a standby set this is the generator figure, not the grid figure, and it is often less than a tenth of it. It sets the ceiling on the instantaneous and short-time settings.
- How much energy will pass before it clears? Current-limiting devices let through far less than their rating suggests, which is what protects the cable and the busbar downstream rather than just disconnecting them eventually.
Answer those four and the family chooses itself: ACBs where the current is large and something downstream must be allowed to clear first, MCCBs where a feeder needs adjustable settings, MCBs on final circuits where nothing downstream needs grading. The mistake that costs most is not picking the wrong family; it is accepting the factory default settings on the right one.
Checking the device protects the cable, not just the circuit
A breaker that is correctly rated for the load and the fault level can still allow the cable behind it to be damaged. The load current sets the thermal setting and the fault level sets the breaking capacity, but what protects the conductor is how much energy passes before the contacts part — and that is a third number, published separately.
The check is a comparison. The cable has a withstand that depends on its cross-section, its insulation and how long the fault lasts. The device has a let-through figure for the prospective fault current at that point. The let-through must be the smaller of the two, at the fault level that actually exists there.
Two places this goes wrong on real installations:
- A long final run on a small cable. Downstream of a 125 A device, a reduced-section run to a single machine can have a withstand below what the device lets through, even though the device is correctly sized for the load. The fix is a smaller device, a larger cable or a current-limiting device — not a bigger breaker.
- A device chosen for the generator and left on the grid. The 900 A short-time setting in the sheet above is right for the set and lets through far more energy on grid supply, where 25 kA is available, than the same setting suggests. Where one breaker serves both sources, the energy check has to be done at the higher fault level.
Current-limiting devices are what make tight installations work: they clear so quickly that the let-through is a fraction of the prospective energy, which protects the cable rather than merely disconnecting it eventually. See cable protection and coordination for the cable side of the same comparison.
Questions engineers ask
What is the difference between Icu and Ics?
Icu is the largest fault a breaker can interrupt, after which it may not be fit for service. Ics is the fault it can interrupt and then stay in service, stated as 25, 50, 75 or 100% of Icu. A breaker with a 36 kA Icu and 50% Ics clears a 22 kA fault but should then be inspected; incomers and critical feeders need Ics above the prospective fault.
What do the L, S, I and G settings on a trip unit do?
L is long time, protecting the cable and load against overload. S is short time, clearing faults after a delay so downstream devices can trip first. I is instantaneous, for heavy faults near the breaker, and is often switched off on incomers. G is earth fault, catching faults too small for the phase elements, which makes it the most dependable fault element on generator supply.
When do I need an ACB rather than an MCCB?
For large currents, typically above about 1600 A, and wherever the breaker must carry a fault for a short time while a downstream device clears it, which needs a high short-time withstand. That makes air circuit breakers the usual choice for transformer and generator incomers, bus couplers and large changeover schemes.
What is breaking capacity?
The largest fault current a breaker can safely interrupt at its rated voltage, stated as Icu. It must exceed the maximum prospective fault at the point where the breaker is installed, including contributions from generators and running motors. The service breaking capacity, Ics, says how much of that the breaker can interrupt and remain in service.
Why four-pole breakers?
To switch the neutral together with the phases when a load moves between a transformer and a generator that are each earthed at their own star point. Without it, neutral current divides between the two earthing points and earth-fault protection measures wrongly, causing nuisance trips or missed faults. The earthing design decides where four-pole switching is needed.
Do fuses still have a role?
Yes. Fuses limit current very quickly and cheaply, which protects cables and busbars downstream, and they are common on motor circuits with a contactor and overload relay. They are also selective with each other at a rating ratio of about 1.6. Their limits are single use, no adjustment and the risk of single-phasing when one fuse blows.
This guide gives general principles. Check manufacturer data for ratings.