In short. A cable must be protected against overload by a device rated at or below its current capacity. It must also be protected against short circuit by a device that clears the fault before the conductor overheats. On generator supply, lower fault current can slow the protective device a lot, so check the cable on both sources, at both ends of the run.
Who this page is for: For electrical engineers and contractors sizing cables and choosing their protection on sites with generators.
Key facts
- Overload: load current ≤ device setting ≤ cable capacity after derating.
- Short circuit: the energy let through must stay below what the cable can withstand.
- Cable withstand is k² × S²; the device must clear in less than t = (k × S ÷ I)².
- Minimum fault current, at the far end and on generator supply, is the hard case.
- Voltage drop and starting dips are separate checks.
- Derating for grouping, temperature and installation changes capacity.
Overload protection
The device rating or setting must be at least the load current and not more than the cable’s derated capacity. See cable sizing.
Worked example: 95 mm² copper feeder on grid and generator (illustrative)
| Check | Working | Result |
|---|---|---|
| Cable withstand constant (copper, PVC) | k ≈ 115 | |
| Maximum clearing time at 10 kA (grid, near end) | (115 × 95 ÷ 10,000)² ≈ 1.19 s | Breaker clears in about 0.02 s; let-through energy below k²S²: OK |
| Fault at far end on generator only | about 1.2 kA | |
| Maximum clearing time at 1.2 kA | (115 × 95 ÷ 1200)² ≈ 83 s (the formula is adiabatic and strictly valid up to about 5 s; beyond that it is conservative) | |
| Breaker at 1.2 kA | Below instantaneous; thermal element about 20 s | Within 83 s: cable protected, but slow |
The cable survives, but a 20 s fault on generator supply would also stress the generator and cause long voltage dips. The site added a short-time element set below 1.2 kA. See short-circuit protection.
Do not check cable short-circuit protection at the grid fault level only. On generator supply, the far-end fault current may be a small fraction, and a breaker that clears in milliseconds on the grid may take many seconds.
Other checks
- Voltage drop at full load and during motor starts. See voltage drop.
- Earth-fault loop impedance for disconnection.
- Coordination with upstream and downstream devices. See coordination.
See earth fault.
Cable protection check
Four circuits from the same board, checked against the limit the page states: the device must clear inside t = (k × S ÷ I)², with k = 143 for copper conductors in cross-linked polyethylene. For 95 mm² that gives k × S = 13585, so at a 25 kA grid fault the cable can stand 0.295 s and at the 1044 A the generator sustains it can stand 169 s. The hard column is the fourth one.
| Cable | Derated capacity | Device setting | Min fault (generator) | Clearing time vs limit |
|---|---|---|---|---|
| 95 mm² copper, tray, grouped | 224 A | 400 A MCCB, Ir 200 A | 1044 A | Limit 0.295 s at 25 kA, device clears in 0.02 s. Limit 169 s at 1044 A, thermal element about 8 s. Pass both |
| 35 mm² copper sub-main | 110 A | 125 A MCCB, Ir 100 A | 1044 A | Limit 0.040 s at 25 kA, device clears in 0.02 s. Pass |
| 16 mm² copper, long run to one machine | 68 A | 125 A MCCB, Ir 100 A, magnetic 700 A | 420 A at the far end | Fail. Limit 29.7 s at 420 A, but 420 A is below the 700 A magnetic setting so the thermal element takes about a minute. Reduce the magnetic setting to 350 A, or take the cable to 25 mm² |
| 240 mm² copper, two runs per phase, generator cable | 580 A | 400 A ACB, Ir 360 A | 1044 A | Limit 460 s at 1.6 kA, device clears in under a second. Pass with a wide margin |
Row three is the failure this check exists to find, and notice what is wrong with it. The cable is correctly sized for its load, 68 A against a 100 A setting. The device is correctly rated for the fault level. Every individual selection is defensible.
What fails is the combination at the one current that matters: a fault at the far end of a long run, with the generator supplying, produces 420 A — too little to operate a magnetic element set at 700 A, and enough to damage a 16 mm² conductor before the thermal element gets round to it. Nothing on the board indicates this, and it will pass every test anyone performs on grid supply.
The overload rule in numbers
Overload protection has two conditions. The device rating must sit between the design current and the cable’s derated capacity, and the current that reliably trips the device within its conventional time must not exceed 1.45 times that capacity. Moulded-case breakers to IEC 60947-2 trip reliably at 1.3 times their setting, so a breaker set at or below the cable capacity meets the second condition on its own. General-purpose fuses need about 1.6 times their rating, so a fuse must be no larger than about 1.45 ÷ 1.6 ≈ 0.9 of the cable capacity.
| Step (illustrative) | Working | Result |
|---|---|---|
| Base capacity, 95 mm² copper XLPE on tray | Tabulated for 30 degrees Celsius air, single circuit | 330 A |
| Ambient correction at 45 degrees Celsius | × 0.87 | 287 A |
| Grouping, four circuits touching on tray | × 0.78 | 224 A, the figure in the check sheet |
| Largest breaker setting | Ir ≤ 224 A | Ir of 200 A chosen |
| Largest fuse | 0.9 × 224 | about 202 A, so a 200 A fuse |
The ambient correction is not a formality in a Hyderabad switchroom or cable trench. Summer air around a busy tray can sit well above 40 degrees Celsius, and a cable chosen at the 30 degree rating loses an eighth of its capacity before grouping is applied.
Worked example: how long a final circuit can be on generator supply (illustrative)
For automatic disconnection, the earth fault loop impedance must be low enough that a fault draws the current that operates the device within the required time: Zs × Ia ≤ U0. Take a sub-circuit with a moulded-case breaker whose magnetic element operates at 700 A, and a 230 V phase-to-earth voltage. The largest loop impedance that still operates the magnetic element is 230 ÷ 700 ≈ 0.329 Ω.
A 16 mm² copper cable with a 16 mm² protective conductor has about 1.15 mΩ per metre per conductor at 20 degrees Celsius. Out and back, and corrected by 1.2 for the conductor at operating temperature, that is about 2.76 mΩ per metre of route.
| Supply | Source part of the loop | Left for the cable | Longest run |
|---|---|---|---|
| Grid transformer | about 0.05 Ω | 0.329 − 0.05 = 0.279 Ω | 0.279 ÷ 0.00276 ≈ 100 m |
| 250 kVA generator, sustaining about 1044 A | about 230 ÷ 1044 ≈ 0.22 Ω | 0.329 − 0.22 = 0.109 Ω | 0.109 ÷ 0.00276 ≈ 39 m |
A circuit that clears instantly on the grid at 90 m is, on the generator, a circuit that relies on the slow thermal element. That is acceptable only where the conductor can stand it, and only where the disconnection time allowed for that circuit is met. Lowering the magnetic setting, adding residual current protection or an earth-fault element, or enlarging the protective conductor are the usual remedies.
Cables in parallel
Large generator and incomer circuits often use two or more cables per phase. They share current properly only if they are the same size, length, type and route, laid so that each phase group is balanced; otherwise one run carries more than its share and runs hot while the device sees an acceptable total. A fault on one of the parallel cables is also fed from both ends, through the healthy runs, so the faulted cable may carry more current than the device setting suggests. Check each run’s capacity against its actual share, and check the short-circuit withstand of a single run against the full let-through of the device.
The neutral on loads with harmonics
Third-harmonic currents from single-phase electronic loads add in the neutral rather than cancelling. Where the third harmonic is about 15 to 33% of phase current, cable ratings are usually reduced to allow for the neutral heating; above about 33% the neutral current exceeds the phase current and the cable is sized on the neutral. A four-pole device or neutral overcurrent protection is then worth considering, because a three-pole device sees only the phase currents and cannot detect an overloaded neutral. See power quality.
Keep the cable schedule with the settings
Every check on this page depends on the cable’s size, length, installation method and grouping. Record them in the same schedule as the protection settings, and re-check the circuit whenever a device setting, a cable route or the source changes. A new generator, a changed transformer or a tray that has filled up with later circuits can each invalidate an earlier calculation without anyone touching the cable.
Common mistakes
- Grid fault levels only.
- No derating for grouping and heat.
- Far-end fault never calculated.
- Device rating above cable capacity.
What to send us
Send cable sizes, lengths, installation method and protection data. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. Constants and fault levels are illustrative; studies and makers’ data govern.
Why the far end on generator supply is the hard case
Protection is usually checked at the point of highest fault current, because that is where breaking capacity is proved. Cable protection has to be checked at the lowest fault current the circuit can see, and that is a different place entirely: the far end of the longest run, with the generator supplying instead of the grid.
Two effects stack up there, and they work in the same direction:
- The source gets weaker. A 250 kVA alternator sustains roughly three times its rated current, about 1044 A, against the tens of kiloamperes a distribution transformer delivers. That alone takes a factor of twenty out of the available fault current.
- The cable adds impedance. A fault at the far end of a long run sees the whole loop impedance, out and back. On a small conductor over a long route this can halve the current again, which is how the 1044 A at the board becomes 420 A at the machine.
The consequences are not symmetrical. Too little current to operate the instantaneous or magnetic element does not mean no protection; it means the thermal element takes over, and thermal elements work in tens of seconds. Whether that is acceptable depends on the conductor: a generous cross-section will sit through it, and a small one will not. That comparison is the whole content of the fifth column in the sheet above.
The practical rule, and it is cheap to apply: calculate the earth fault loop impedance and the phase-to-phase fault at the far end of every long or small-section run, on generator supply, before the settings are finalised. Where a circuit fails, the fixes in order of cost are a lower magnetic setting, then a larger conductor, then a current-limiting device. Which one applies is decided by what else has to grade against it — see protection coordination and selectivity, where the same site is worked down the chain.
Questions engineers ask
What does the 1.45 times cable capacity rule mean?
The current that reliably trips the device within its conventional time must not exceed 1.45 times the cable capacity. Moulded-case breakers trip reliably at 1.3 times their setting, so a setting at or below the cable capacity complies. General-purpose fuses need about 1.6 times their rating, so the fuse must be no more than about 0.9 times the capacity: about 200 A on a cable derated to 224 A.
How long can a circuit be before generator supply stops the magnetic trip?
Work it out from the loop impedance. For a 700 A magnetic element at 230 V the loop must be under about 0.329 ohm. A grid source takes about 0.05 ohm, leaving room for about 100 m of 16 mm² cable with a 16 mm² protective conductor. A 250 kVA generator sustaining about 1044 A takes about 0.22 ohm, leaving room for only about 39 m.
What is the adiabatic check?
A check that the cable can absorb the fault energy before the protective device clears it, assuming no heat escapes during the short fault. The cable withstands k squared times S squared, so the clearing time must be less than (k times S divided by I) squared. For 95 mm² copper with k of 143 at 25 kA, that is about 0.3 s.
Why are generator checks stricter?
Because a generator delivers far less fault current, and at the far end of a long cable even less. Magnetic and short-time elements may not pick up, so the fault is cleared by the slow thermal element, and earth fault loop impedance limits become much harder to meet. A circuit fine on grid supply can fail both checks on generator supply.
Can a larger cable fix a trip problem?
Sometimes. A larger conductor, or a larger protective conductor, lowers the loop impedance so more fault current flows and the device operates faster, and it also raises the cable withstand. But it is often cheaper to lower the magnetic or short-time setting, or add earth-fault or residual current protection, so compare the options.
What is a residual-current device?
A device that compares the current going out on the phase conductors with the current returning in the neutral, and trips when the difference, the leakage to earth, exceeds its rating. Devices of 30 mA protect people; 100 mA and 300 mA devices protect against fire. They detect leakage far too small for overcurrent protection to see.
This guide gives general principles. Calculations should follow applicable standards.