Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

Electrical Protection and Switchgear Systems Guide

How protection and switchgear work together to detect faults, isolate them and keep healthy circuits running: devices, zones, coordination and testing.

In short. Switchgear carries, switches and isolates power; protection detects abnormal conditions and tells the switchgear to act. A good system trips the smallest part of the network that clears the fault, quickly enough to limit damage, and leaves everything else running. It must work on every source, including generator-only supply, and keep working through a blackout on its own DC power.

Who this page is for: For owners, facility managers and engineers starting a review or design of switchgear and protection.

Key facts

  • Protection detects; switchgear interrupts.
  • Selectivity means the nearest device clears the fault.
  • Speed limits damage and arc flash energy.
  • Generator fault levels are lower than grid levels; settings must work on both.
  • DC control power and trip circuits are part of the protection.
  • Untested protection is unproven protection.

What the system does

FunctionSee
Detects overcurrent and short circuitsovercurrent
Detects earth faultsearth fault
Protects generatorsgenerator protection
Sets the earthing and neutralneutral-earth
Coordinates devicescoordination
Backs up a failed breakerbreaker failure

Worked example: a protection review in five questions (illustrative)

QuestionFinding at one siteAction
Does every fault and abnormal condition have a protection that sees it?No reverse power on paralleled setsAdded
Does it work on generator supply?Two feeders would not trip for faults on generator supplyShort-time elements added
Is it selective?Incomer tripped before feeder on one fault levelSettings regraded
Will it work in a blackout?DC battery failed load testReplaced; load test added to maintenance
Has it been tested?Last injection test six years agoFull secondary injection and trip tests

Five plain questions found five real gaps. See protection coordination.

Do not assume protection works because nothing has tripped. Silence can mean healthy, or it can mean a relay, trip path or battery that will fail on the first real fault. Test it.

Where to start

  1. Get an up-to-date single-line diagram.
  2. List fault levels on grid and generator supply.
  3. List each protection and its settings.
  4. Check coverage, selectivity and generator operation.
  5. Test and record.

Protection review checklist

QuestionAnswerAction
Every fault covered?  
Works on generator supply?  
Selective?  
DC system healthy?  
Recently tested?  

Protection functions by equipment

Every item of equipment on a generator installation has its own set of failure modes, and each failure mode needs a protection function that can see it. The table is a starting checklist; the size and importance of each item decide how far down the list it goes.

EquipmentTypical functions (ANSI number)Main guide
GeneratorOvercurrent, voltage-restrained (51V); earth fault (51N); reverse power (32); loss of excitation (40); negative sequence (46); voltage and frequency (27, 59, 81); differential (87G) on larger setsGenerator protection relays
TransformerHV fuse or overcurrent (50/51); restricted earth fault (64REF); standby earth fault; differential (87T) on larger units; gas, pressure and temperature devicesTransformer protection
BusbarIncomer overcurrent and earth fault; busbar differential (87B) on critical boards; arc detectionBusbar protection
Cable feederOvercurrent and earth fault, set within the cable’s withstandCable protection
MotorThermal overload (49); short circuit (50); earth fault; locked rotor; phase loss and unbalanceMotor and feeder protection
Changeover and parallelingInterlocks; check synchronising (25); loss of mains where paralleled with the gridParalleling switchgear
Control powerTrip-circuit supervision; DC earth-fault monitoring; battery and charger alarmsDC control power

Start from an accurate single-line diagram

Every protection decision refers back to the single-line diagram: which sources can feed which boards, where every breaker, fuse and CT sits, how the neutral is earthed and switched, and which loads hang off each feeder. On many sites the diagram on file no longer matches the switchboard, because feeders, generators and UPS units have been added over the years. Walk the site, trace every source and every changeover, and correct the diagram before any study or settings work begins. A protection study built on an out-of-date diagram produces settings that are precise and wrong at the same time. See single-line diagram engineering.

The value of this table is in the gaps it reveals. Go through it with the single-line diagram, tick each function that is actually fitted and set, and the unticked items become the start of the review’s findings. On most sites the first pass shows at least one generator without reverse power protection, one transformer whose temperature devices only alarm, and one board with no record of its settings.

Selectivity in numbers

Selectivity means that, for any fault, the device nearest to it trips first and the devices upstream wait long enough to let it. On time-graded protection that wait is a grading margin, typically about 0.2 to 0.3 s between numerical relays and more where older electromechanical relays or slow breakers are involved.

A three-level board might therefore clear a feeder fault in about 0.1 s at the feeder breaker, wait about 0.4 s at the sub-board incomer and about 0.7 s at the main incomer. Each extra level adds a margin to the slowest clearing time on the site, which is why boards with many levels in series end up with long clearing times at the top and why busbar differential or zone-selective interlocking is used to restore speed there. See protection coordination and selectivity.

The generator-supply check that finds most problems

Most protection on a site is set for the utility, where fault currents are large. The single most useful check in any review is whether each device still operates on generator supply alone. Take a 500 kVA, 415 V set with a full-load current of about 696 A and a subtransient reactance of 0.15 per unit. Its initial fault current is about 696 ÷ 0.15 ≈ 4.6 kA, falling within a second or so to a sustained value of perhaps three times rated, about 2.1 kA, with excitation support.

A 400 A feeder breaker with its instantaneous trip at ten times rating needs 4 kA: it may just trip in the first cycles if the fault is close to the generator, but on a fault further out, or once the current has decayed, it falls back on its slower elements. A board that clears in 0.1 s on the utility may take a second or more on the generator, with more damage and a real risk of the generator’s own protection tripping first. See short-circuit and fault-level engineering.

Earth faults on generator supply

Earth-fault protection deserves its own check on generator supply, separate from phase faults. The earth-fault current depends on how the generator’s neutral is earthed: solidly earthed sets can produce more earth-fault current than three-phase fault current, while resistance-earthed sets deliberately limit it to a few hundred amperes. Either way the value differs from the utility case, and earth-fault elements set for the utility may be too slow or may not operate at all. Check every earth-fault element against the earth-fault current on each source, and check the neutral switching at the changeover, because it decides which earth-fault relays see the current. See earth-fault and ground-fault protection.

Speed and arc flash

The energy released by an arcing fault is roughly proportional to the arcing current multiplied by the time it lasts, so the clearing time decided by the protection settings is also the main lever on arc-flash risk. A maintenance switch that temporarily lowers the instantaneous setting of an upstream breaker while people work on the board, or an arc-detection relay that trips on light and current within a few milliseconds, can reduce the incident energy many times over. Treat clearing time as a safety setting, not only as a coordination setting. See arc-flash risk and mitigation.

Gaps most often found, by type of site

SiteCommon gapUsual remedy
Office or apartment block with one standby setFeeder breakers that do not trip on generator supplyShort-time elements or a generator settings group
Factory with large motorsNuisance trips on motor starting; motor contribution ignored in breaker ratingsTwo-stage voltage settings; fault study including motors
Hospital or data centreSelectivity lost in UPS battery and bypass modesMode-by-mode selectivity study; fuse or breaker changes on branches
Plant with several paralleled setsNo reverse power or loss of excitation on sets added laterNumerical generator protection on every set
Older site of any kindUntested relays, failed batteries, no recordsFull injection, trip and battery tests; a settings record

What a protection review should deliver

  • A current single-line diagram with every protective device and CT shown.
  • Fault levels at each board for every operating mode, maximum and minimum.
  • A settings table with the reason for each setting and the mode it was checked against.
  • Time-current charts showing selectivity between each pair of devices in series.
  • A list of gaps, ranked by risk, with the remedy for each.
  • A test plan and the records of the tests carried out.

Who is responsible for what

RoleResponsible for
OwnerKeeping a current single-line diagram, settings record and test history; approving changes
Design engineerThe protection philosophy, fault study and settings, for every operating mode
Panel builderBuilding and wiring to the schematic; factory tests
Commissioning engineerInjection tests, stability tests, trip tests and the signed record
Maintenance teamPeriodic tests, battery checks, alarm response and keeping the records current

When one of these roles is missing, protection usually drifts: settings change without records, new feeders are added without a study, and the test history stops. Naming the person for each role is the cheapest protection improvement there is.

Protection over the life of the installation

Protection is designed once and then lives for decades through changes the designer never saw: a larger generator, a second transformer, a UPS, new motors. Each change alters fault levels and therefore settings. A sound practice is to review the fault study and the settings whenever a source or a large load is added, to repeat secondary injection and trip tests at intervals set by the importance of the equipment, and to repeat the full review in this guide every five years or so even when nothing seems to have changed. See protection maintenance and lifecycle testing.

Standards that apply

Protection relays are covered by IEC 60255, low-voltage switchgear and controlgear by IEC 60947 and its Indian equivalents, low-voltage switchgear assemblies by IEC 61439, high-voltage switchgear by IEC 62271, and short-circuit calculation by IEC 60909. Installation rules come from the national wiring code and the electricity regulations. The standards set the performance the equipment must meet; the site’s protection philosophy and study decide how it is applied.

Common mistakes

  • Out-of-date drawings.
  • Settings for grid supply only.
  • DC system forgotten.
  • No testing records.

What to send us

Send the single-line diagram, relay list and last test records. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. The findings are illustrative.

Questions engineers ask

Which protection does a diesel generator need?

At minimum overcurrent, preferably voltage-restrained because generator fault current decays, earth fault, over- and undervoltage, over- and underfrequency, and the engine and alternator protections in the controller. Paralleled sets also need reverse power and loss of excitation, larger sets negative sequence and often differential protection. Every setting must work on generator supply alone, where fault current is far lower than on the grid.

What grading margin is used between relays?

Typically about 0.2 to 0.3 seconds between numerical relays in series, more where electromechanical relays or slow breakers are involved. A three-level board might clear a feeder fault in about 0.1 s, the sub-board incomer at about 0.4 s and the main incomer at about 0.7 s. Each level in series adds a margin, which is why busbar differential or zone-selective interlocking is used to speed up clearing at the top.

What is the difference between switchgear and protection?

Switchgear is the equipment that carries current, switches and interrupts it: breakers, switches, fuses and busbars. Protection is the sensing and decision-making, CTs, VTs, relays and trip units, that detects an abnormal condition and tells the switchgear to open. A strong breaker with wrong settings, or good settings on an undersized breaker, both fail.

Why do generators need different protection?

Because their fault current is far lower than a grid supply and decays within seconds, so settings chosen for the grid may never operate. Generators also have failure modes of their own: motoring when they lose fuel in parallel, loss of excitation, unbalanced loading that heats the rotor, and speed or voltage running outside limits. Each needs its own function.

How often should protection be tested?

At commissioning, after any change to settings, CTs or wiring, and at intervals set by the maker and site policy, commonly every one to four years for relays depending on how critical the circuit is and whether the relay supervises itself. Breakers should also be tripped from their protection regularly, so the whole chain is proved.

Can protection be too sensitive?

Yes. Settings too close to normal load, starting or inrush current cause nuisance trips that stop production and teach operators to reset without looking. The aim is to trip for every real fault in the zone, at the lowest fault current on every source, while riding through every normal event. Both limits are calculated, not guessed.

This guide gives general principles. Settings must come from a study of your system.