Motor and Feeder Protection Guide

How motors and feeders are protected: overload, locked rotor, short circuit, earth fault, unbalance and undervoltage, with starter types, relay settings and generator-supply considerations.

In short. A motor circuit needs protection against short circuit, overload and stalling, and larger or critical motors also against phase loss, unbalance, earth fault and undervoltage. Feeders need overcurrent and earth-fault protection coordinated with the board above them. Every setting must let the motor start and still trip on a real fault. On generator supply, starts take longer and fault currents are lower, so settings that work on the grid can nuisance-trip, or fail to trip, on the generator.

Who this page is for: For maintenance engineers, panel builders and consultants setting motor and feeder protection, especially on sites that run on generators.

Key facts

  • Direct-on-line starting draws about 5 to 8 times full-load current for several seconds.
  • The overload trip class (10, 20 or 30) is the longest trip time, in seconds, at 7.2 times the setting.
  • Short-circuit elements must sit above the starting peak, including its first-cycle asymmetry.
  • Stall protection must trip below the motor’s safe stall time.
  • Undervoltage protection needs a short delay on generator supply, or every start will trip it.
  • Stagger restarts after a changeover so that motors do not all start together.

Motor protection functions

HazardProtectionTypically fitted on
Short circuitFuse, MCCB or motor-protection circuit breaker magnetic elementAll motors
OverloadThermal or electronic overload relay with a trip classAll motors
Locked rotor or stallStall timer or start-time supervisionMedium and large motors, heavy-start loads
Phase loss or unbalancePhase-failure relay or negative-sequence element. See unbalance protectionPumps, motors, critical motors
Earth faultEarth-fault relay, often with a core-balance CT. See earth-fault protectionMedium and large motors, wet locations
UndervoltageUndervoltage release with time delay and restart logicMotors that must not restart unexpectedly
Winding and bearing temperaturePTC thermistors or RTDsLarge and VFD-fed motors
Too many startsStart counter and cooling-time limitLarge motors with frequent cycling

Overload trip class and starting time

The trip class tells you how long the overload relay tolerates a high current. At 7.2 times its setting, a class 10 relay trips within 10 seconds, class 20 within 20 seconds and class 30 within 30 seconds. Choose a class whose time comfortably exceeds the motor’s starting time, and whose curve stays below the motor’s thermal limit.

Worked example: a 90 kW pump on grid and on generator (illustrative)

A 90 kW pump motor at 415 V has a full-load current of about 155 A. It starts direct-on-line at about six times, around 930 A, and takes about 4 seconds to reach speed on the grid. Its safe stall time is 15 seconds hot.

SettingGrid onlyGrid and generator
Overload setting155 A155 A
Trip classClass 10 allows the 4 s startOn the generator the dip stretches the start to about 9 s, which a class 10 relay may not allow, so class 20 is chosen. Class 20 can take longer than the 15 s safe stall time at locked-rotor current, so the stall timer below provides the locked-rotor protection
Stall timerAbout 7 sAbout 12 s, still below the 15 s stall limit
Short-circuit elementAbout 12 × full-load current, above the asymmetric starting peakCheck that the generator’s fault current reaches it; if not, rely on a short-time element
UndervoltageInstantaneous allowedAdd a delay of about 2 to 3 s so starts do not trip it

The same motor needs different settings once a generator is involved. Better still, a soft starter shortens the dip and the start on both sources. See motor starting and voltage-dip studies.

Never raise an overload setting above the motor’s rated full-load current (times the service factor, where the nameplate gives one), or bypass the stall timer, to stop trips on generator supply. Find out why the start is slow, then fix the starting method or the trip class.

Feeder protection

A feeder to a motor control centre or distribution board needs overload and short-circuit protection that protects its cable, earth-fault protection, and coordination with both the devices below it and the incomer above it. On generator supply, check that the short-time element still picks up on the generator’s decaying fault current. See overcurrent and short-circuit protection and TCC coordination.

Restart after a changeover

When supply returns after a transfer, every motor whose contactor holds in will try to restart at once, and the combined inrush can collapse a generator’s voltage. Use undervoltage releases with restart timers, a PLC sequence, or staggered contactor control, so that the largest motors start first and the rest follow in steps.

Setting steps

  1. Collect nameplate data: full-load current, starting current, starting time on each source, safe stall time and service factor.
  2. Set the overload to the full-load current and choose the trip class for the longest starting time.
  3. Set the short-circuit element above the starting peak, then check it against the minimum fault current on generator supply.
  4. Set the stall timer longer than the longest start and shorter than the safe stall time.
  5. Add phase-loss, earth-fault and undervoltage functions as the motor’s size and duty require.
  6. Check coordination with upstream devices and test by injection.

Motor protection setting sheet

Four motors from the same board, set for both sources. Start times on generator are longer than on grid because the voltage dips during the start and torque falls with the square of voltage, so the motor takes longer to reach speed — and every time setting has to accommodate the longer figure.

MotorFLC (A)Start time grid / generator (s)Trip classStall timer (s)Short-circuit setting (A)
90 kW pump, direct on line1534.5 / 7.22091989 during the start, then 900 once running
45 kW pump, direct on line783.0 / 4.81061014 during the start, then 700 once running
30 kW fan, star-delta536.0 / 8.52012424 throughout — a star-delta start peaks near 2.2 times full load
7.5 kW booster, direct on line141.5 / 2.0104182 during the start, then 140 once running
      
      
      

The last column holds a conflict that cannot be settled with one number, and it is the most useful thing on this sheet. A direct-on-line start draws six or seven times full-load current, so the 90 kW pump’s short-circuit element has to sit above about 1000 A to survive its own start — 1989 A allows for the first-cycle asymmetry on top. But the generator sustains only 1044 A, so an element parked at 1989 A can never operate on generator supply. Both requirements are correct and they contradict each other.

The resolution is in the wording of the column: the relay holds the high setting only while the start is in progress and drops to 900 A once the motor is running. A fault during the two seconds of a start is covered by the upstream device; a fault at any other time — which is almost all of the time — is cleared by an element that works on either source. A relay without that function has to choose, and most sites choose the high setting and never discover what they gave up.

The three time settings have to be read together as well. Trip class 20 permits up to 20 s at 7.2 times the setting, which comfortably passes the 7.2 s generator start on the 90 kW pump; the stall timer at 9 s sits above that start and below the motor’s safe stall time, so a rotor that fails to turn is caught in 9 s rather than 20. Set the stall timer below the generator start time and the motor trips every time the building changes over — which is the single commonest protection complaint we are called out to after a new set is installed.

One setting is deliberately absent from the table because it belongs to the board and not to the motor: undervoltage. On generator supply every start pulls the bus down, so an undervoltage element with no intentional delay will trip the motors it is meant to protect. It needs a delay long enough to ride through the dip from the largest start on the bus, and the restart sequence after a changeover needs staggering so that the starts do not arrive together.

Worked example: how many starts a motor can take (illustrative)

Each direct-on-line start puts a burst of heat into the rotor and stator. A simple way to estimate how much is to compare the start time with the safe stall time at the same current: the start uses roughly that fraction of the motor’s thermal capacity.

Case, 90 kW pump, safe hot stall time 15 sWorkingThermal capacity used per start
Start on grid, 4.5 s4.5 ÷ 1530%
Start on generator, 7.2 s7.2 ÷ 1548%

From hot, two generator starts in quick succession use almost all of the motor’s margin, where three grid starts would still leave some. That is why a pump that cycles freely on the grid can trip, or be damaged, when a generator is supplying. A relay with a thermal model and a start counter blocks a further start until the motor has cooled, and the maker’s permitted starts per hour, often stated separately for cold and hot, set the limit.

Voltage unbalance heats motors out of proportion

A small voltage unbalance drives a much larger current unbalance, typically six to ten times larger, because the motor’s impedance to the negative-sequence voltage is close to its low starting impedance. A commonly used estimate is that the extra winding temperature rise, in percent, is about twice the square of the voltage unbalance in percent: 2% unbalance gives about 2 × 2² = 8% more heating. Motor standards call for derating to about 95% of rating at 2% unbalance and about 88% at 3%. On generator supply, large single-phase loads on one phase are the usual cause. See negative-sequence and unbalance protection.

Earth-fault detection with a core-balance CT

Summing the three phase CTs to detect earth fault works on feeders but is unreliable on motors: during a start the CTs can saturate unequally, producing a false residual current. A core-balance CT around all three phase conductors measures the true earth leakage and allows a sensitive setting, typically a few amperes with a short delay, without nuisance trips on starting. Route any cable armour or screen earth back through the CT so that its current cancels.

Motors fed from variable-speed drives

A drive limits starting current and provides its own overload and short-circuit protection for the motor, so the feeder breaker sees no starting inrush and can be set closer to the running load. The drive cannot see winding temperature at low speed, where the shaft-mounted fan cools poorly, so fit thermistors to the motor and connect them to the drive. Check that the feeder protection still protects the cable between the board and the drive, and that the drive’s harmonic currents are allowed for in the generator rating.

Common mistakes

  • A trip class that trips on every generator start.
  • Undervoltage relays with no delay on generator supply.
  • No phase-loss protection on pumps and motors.
  • Short-circuit settings that never pick up on generator fault current.
  • All motors restarting together after a changeover.

What to send us

Send the motor schedule with nameplates, the starter types and present settings, and whether the motors run on generator supply. WhatsApp 98852 01608 or use the enquiry form.

Evidence note. Settings in the example are illustrative; final settings follow the motor and device makers’ data and a protection study.

Questions engineers ask

How many starts per hour can a motor take?

As many as the maker permits, usually stated separately for cold and hot starts. A useful estimate is that each start uses the start time divided by the safe stall time of thermal capacity: a 4.5 s start against a 15 s hot stall time uses about 30%, but a 7.2 s start on generator supply uses about 48%, so two hot starts nearly exhaust the margin.

How much does voltage unbalance heat a motor?

Far more than the unbalance suggests. Current unbalance is typically six to ten times the voltage unbalance, and the extra temperature rise in percent is roughly twice the square of the voltage unbalance: 2% gives about 8% more heating. Motors are derated to about 95% at 2% unbalance and about 88% at 3%.

What is a trip class?

The longest time an overload relay allows at 7.2 times its setting: class 10 trips within 10 s, class 20 within 20 s and class 30 within 30 s. Choose a class whose time comfortably exceeds the longest start, including the slower start on generator supply, and use a stall timer for locked-rotor protection where the class is longer than the safe stall time.

Why does a motor trip on generator but not on grid?

Because the generator voltage dips during the start, motor torque falls with the square of voltage and the start takes longer, so a trip class or stall timer set for the grid start can operate. Undervoltage elements with no delay trip on the dip itself. Short-circuit settings chosen for the grid may also never pick up on the lower generator fault current.

Is a fuse or a breaker better for motors?

Both work. Fuses limit fault current very quickly and are often used with a contactor and overload relay for coordination. Motor-protection breakers and MCCBs can be reset, have adjustable settings and avoid single-phasing when one fuse blows. Choose by the fault level, the coordination needed with the contactor and how quickly the motor must be returned to service.

Do small motors need all these functions?

No. Every motor needs short-circuit and overload protection; phase loss, earth fault, stall, undervoltage and temperature sensing are added according to size, cost of failure and duty. A small fan may need only a motor-protection breaker, while a large critical pump justifies a numerical motor relay with a thermal model and start counter.

This guide gives general principles. Check motor data for settings.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.

CallWhatsAppEnquire