Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

Switchboard Thermal and Busbar Engineering Guide

How heat limits switchboard capacity: busbar rating, temperature rise, ventilation, derating by ambient and altitude, joints, short-circuit forces and thermography.

In short. A switchboard’s current rating is a thermal limit, not just a conductor size. Heat from busbars, breakers and joints has to escape through the enclosure. Ambient temperature, ventilation, grouping, harmonics and altitude all reduce what the board can carry. Short-circuit forces set a separate, mechanical limit. Many failures start at a joint whose resistance has risen.

Who this page is for: For electrical engineers, panel builders and maintenance teams rating, upgrading or troubleshooting LV switchboards.

Key facts

  • Busbar losses rise with the square of current.
  • Each breaker, contactor and fuse adds its own losses at rated current.
  • A poor joint can produce many times the heat of a sound one.
  • Hot rooms, poor ventilation and harmonics reduce the usable rating.
  • Short-circuit withstand depends on busbar supports and bracing, not only conductor size.
  • Thermography under load and joint torque checks find problems early.

Sources of heat

  • Busbar resistive losses, proportional to current squared.
  • Switching devices, each with a loss at rated current.
  • Joints and terminations, where poor contact multiplies heating.
  • Harmonic currents, which add heating. See harmonics.

Worked example: why one joint ran hot (illustrative)

ItemSound jointPoor joint
Joint resistanceabout 10 µΩabout 60 µΩ
Current1600 A
Heat = I² × R1600² × 0.00001 ≈ 26 W1600² × 0.00006 ≈ 154 W
Thermographyabout 45 °Cabout 95 °C

The poor joint had a loosened bolt from vibration. Six times the resistance gave six times the heat at the same current, enough to discolour the bar. It was cleaned, re-made and torqued, and the reading fell to match the others. Rising current makes this worse fast: at 2000 A the poor joint would produce about 240 W.

Do not raise a switchboard’s load because the busbar “looks big enough”. Check its tested rating, the room temperature, ventilation, harmonics and the condition of every joint first.

Factors that reduce rating

FactorEffect
High ambientLess margin for temperature rise. See ambient derating
Poor ventilationHeat trapped in the enclosure
Grouping of loaded devicesNeighbours heat each other
HarmonicsExtra heating for the same RMS current
AltitudeThinner air cools less

Short-circuit forces

Fault current produces large forces between bars. The board’s short-circuit withstand rating depends on supports and bracing. A new or larger generator, or a second source in parallel, can exceed it. See coordination and short-circuit protection.

Joint and thermal survey

A thermography survey of one main board under load. The column that matters is the fourth: an absolute temperature means little on its own, because a busbar joint carrying 980 A is expected to be warm. What identifies a defect is the difference between a joint and its identical neighbours at the same current.

LocationCurrent at surveyTemperatureDifference from similar jointsAction
Incomer breaker top terminal, phase B980 A59 °CReferenceNone
Incomer breaker top terminal, phases A and C980 A62 and 61 °C+3 and +2 KNone — normal spread
Busbar riser joint, phase B, section 2980 A94 °C+35 KShut down at the first opportunity. Dismantle, clean both faces, check for bolt relaxation and re-torque to the maker’s figure
Outgoing feeder 4, phase C terminal220 A58 °C+14 K on phases A and B at the same currentRe-torque at the next shutdown and re-survey within a month
Neutral bar connection, section 3310 A, against a 220 A phase average71 °C+12 KInvestigate harmonics — the neutral is carrying more than the phases
     
     
     

The working thresholds behind the action column: a few kelvin of difference is normal spread and needs nothing; roughly 5 to 20 K says a joint is degrading and should be dealt with at the next planned shutdown; above about 20 K the joint is failing now and the heat will accelerate its own deterioration, because a loose joint’s resistance rises as it heats and it heats further as a result. The 94 °C joint in row three is on that curve.

The last row is a different failure wearing the same clothes. The joint is not loose; it is carrying 310 A of neutral current on a board whose phases average 220 A, which only happens when third-harmonic currents from switched-mode supplies and drives add in the neutral instead of cancelling. Re-torquing that connection will achieve nothing. The fix is upstream of it.

Survey under real load. A board surveyed on a Sunday at 10% of its load shows nothing at all, and the joint in row three would have read a comfortable 31 °C.

Worked example: how much heat a busbar makes

Busbar heat comes from the current flowing through the copper’s resistance, and it rises with the square of the current. A 100 × 10 mm copper bar has a cross-section of 1000 mm². Copper’s resistivity is about 1.72 × 10−8 Ωm at 20 °C, rising by about a quarter at a typical operating temperature of 85 °C, to about 2.15 × 10−8 Ωm.

The bar’s resistance is then about 2.15 × 10−5 Ω per metre. At 2000 A it dissipates 2000² × 2.15 × 10−5 ≈ 86 W per metre in each phase, about 258 W per metre for three phases. A few metres of busbar inside an enclosure therefore produces a kilowatt or more before any joint, breaker or cable termination is counted, and that heat has to leave through the enclosure walls or its ventilation.

Harmonics add heat the ammeter may not show

Harmonic currents add to the RMS current and therefore to the heat. With 30% third harmonic, the RMS current is about √(1 + 0.3²) ≈ 1.044 times the fundamental, and the losses, which follow the square, rise by about 9%, more at higher frequencies because of skin and proximity effects in thick bars. An average-reading ammeter may not show the true RMS value at all. Where boards serve drives, UPS units and electronic loads, measure true RMS currents and harmonic content, and allow for the extra heating in the busbar and neutral rating. See harmonics and THD.

Enclosure protection against heat dissipation

A higher degree of protection against dust and water usually means fewer ventilation openings and therefore less cooling. A board specified to a high IP rating for a dusty or wet location will run hotter than the same board ventilated, and its maker’s rated current may assume the ventilated version. Where a sealed enclosure is needed, ask for the rated current in that enclosure, consider filtered fans or heat exchangers, or locate the board in a clean room so that a ventilated enclosure can be used.

Reading a thermal survey

Temperature difference between similar components (commonly used bands)InterpretationAction
1 to 3 °CPossible deficiencyNote and check at the next survey
4 to 15 °CProbable deficiencyRepair at the next planned shutdown
Above 15 °CMajor discrepancyRepair as soon as possible

The bands only mean something when the components compared carry similar current. Record the load on each circuit at the time of the survey, and remember that a joint that is 10 °C warm at half load will be far hotter at full load, because heat rises with the square of the current.

Making joints that stay cool

  • Clean contact surfaces and use the jointing compound the maker specifies.
  • Use the specified bolt grade, washers and torque, and mark each bolt once torqued so a missed one is visible.
  • Use bimetallic connectors where copper meets aluminium, because a direct joint corrodes and loosens.
  • Re-torque or re-inspect new joints after the first period of loading where the maker recommends it.
  • Do not over-torque: a crushed conductor or stretched bolt loses its clamping force over time.

The switchroom is part of the thermal design

Every rating on a board assumes an ambient temperature, usually 35 °C averaged over 24 hours outside the enclosure. A switchroom in Telangana or Andhra Pradesh that reaches 45 °C in summer erodes that rating, and so do transformer, UPS and drive losses in the same room. Calculate the room’s heat load from all equipment, size ventilation or cooling for the hottest season, and monitor the room temperature as part of the board’s monitoring. See LV switchboards, PCC and MCC.

Continuous temperature monitoring

An annual thermal survey catches a joint that has deteriorated over months, but not one that loosens and fails between surveys. Wireless or fibre-optic temperature sensors fixed to the main busbar joints, incomer terminals and large cable lugs report continuously to the monitoring system, and an alarm on a rising trend gives weeks of warning instead of a single annual snapshot. On boards that cannot easily be shut down, continuous monitoring is often cheaper than the outage a failed joint causes.

Common mistakes

  • Rating judged by busbar size alone.
  • No thermography under real load.
  • Joints never re-torqued after commissioning.
  • Fault level not checked when sources are added.

What to send us

Send the board rating, load currents, room conditions and any thermography. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Resistances and temperatures are illustrative.

What the nameplate rating assumes, and what your room does to it

A busbar system rated 2000 A was tested in a defined way: a specified ambient, a specified enclosure, a specified mounting and a sinusoidal current. Change any of those and the usable rating falls, and nothing on the board says so.

Short-circuit withstand works differently and is worth stating separately, because it is the one most often assumed from conductor size. The force between parallel bars during a fault goes with the square of the current and inversely with their spacing, and it is carried by the supports rather than by the copper. A board whose bars are adequately sized and whose insulators are spaced for a lower fault level will fail mechanically at the correct current. When an incoming supply is uprated, or a second generator is added so the fault level rises, the bracing is part of what has to be rechecked — not only the breaker ratings.

Questions engineers ask

How much heat does a busbar produce?

It follows the square of the current. A 100 by 10 mm copper bar at about 85 degrees Celsius has a resistance of about 0.0000215 ohm per metre, so at 2000 A it dissipates about 86 W per metre per phase, roughly 258 W per metre for three phases. Harmonics add more: 30% third harmonic raises the losses by about 9%.

What temperature difference in a thermal survey needs action?

Commonly used bands, comparing similar components carrying similar current, treat 1 to 3 degrees Celsius as a possible deficiency to watch, 4 to 15 degrees as a probable deficiency to repair at the next shutdown, and more than 15 degrees as a major discrepancy to repair as soon as possible. Record the load, because heat rises with the square of the current.

Why does a board overheat below its rated current?

Because the rating assumes a reference ambient, ventilation and a sinusoidal current. A hot switchroom, blocked ventilation, harmonics that add heating, loose or poorly made joints, and more fully loaded feeders than the design diversity allowed can all push temperatures up while the current stays below the nameplate.

What is thermography?

Infrared imaging of energised equipment under load to find hot spots, such as loose connections, overloaded conductors and failing contacts, before they fail. Surveys are compared between similar components carrying similar current, and the load at the time is recorded, because heat rises with the square of the current.

Does altitude matter?

Yes. Above about 2000 m the thinner air cools less effectively and insulates less well, so current ratings and dielectric ratings of switchgear fall. The maker gives derating factors for altitude, which should be applied together with any derating for ambient temperature and enclosure type, and confirmed with the switchboard maker.

How often should joints be checked?

At commissioning, then by thermographic survey under load at least once a year, and by torque checks and contact resistance tests during planned shutdowns at intervals the maker recommends. Any joint found warm in a survey should be checked at the next opportunity rather than waiting for the next scheduled visit.

This guide gives general principles. Ratings come from the assembly manufacturer.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.

CallWhatsAppEnquire