In short. The neutral-earth design decides fault current, the protection needed, people’s safety and whether sources interfere with each other. On a multi-source system, the rule of thumb is one neutral-earth bond in each energised part of the system. Switch or arrange the neutral so that earth-fault protection sees the correct current on every source, and test it.
Who this page is for: For electrical engineers and consultants designing earthing for sites with grid, generators and changeovers.
Key facts
- Solid earthing gives high fault current and easy detection, but more damage.
- Resistance earthing limits fault current and needs sensitive relays.
- Two neutral-earth bonds in one energised system cause circulating current and false readings.
- The changeover’s neutral switching (3-pole or 4-pole) follows from the earthing design.
- Earth-fault CTs must see the true fault path.
- Harmonics can make neutral current large even when phases are balanced.
Earthing methods
| Method | Fault current | Points |
|---|---|---|
| Solid earth | High | Easy detection; high damage and arc energy |
| Resistance earth | Limited | Less damage; needs sensitive relays |
| Reactance earth | Limited | Less common at LV |
| Unearthed | Very low | Needs insulation monitoring; special cases |
Worked example: the earth-fault relay that tripped on healthy load (illustrative)
A site with a transformer and a generator, both with star points bonded to earth locally, used a 3-pole changeover. The generator earth-fault relay tripped at random on generator supply.
| Finding | Effect |
|---|---|
| Neutral not switched; both star points bonded | Neutral current split between two return paths, through the earth |
| Earth-fault CT on the generator neutral-earth link | Saw part of the normal unbalanced neutral current as “earth fault” |
| Third-harmonic current from electronic loads | Made the false reading worse |
| Fix | 4-pole changeover so only one source’s neutral is connected at a time, with each source bonded at its own star point; relay retested |
See changeover switchgear and earthing and neutral grounding.
Do not choose 3-pole or 4-pole changeovers by habit. The earthing arrangement decides it, and the wrong choice leaves earth-fault protection seeing either too much or too little.
Rules for multi-source systems
- One neutral-earth bond in each energised part.
- Switch the neutral, or design a single common bond, deliberately.
- Where the neutral is switched, it should make before and break after the phases, so the load neutral is never left floating.
- Place earth-fault CTs where they see the real fault return.
- Size the neutral for unbalance and harmonics. See harmonics.
- Test earth-fault protection on each source.
See earth fault, REF and coordination.
Neutral-earth review sheet
| Source | Bond location | Changeover poles | Earth-fault CT position | Tested |
|---|---|---|---|---|
| Utility / transformer | ||||
| Generator |
Where the earth-fault measurement is taken
An earth-fault relay is only as good as the current it measures, and the same fault can look very different depending on where the CT sits. The table compares the common positions on a site with a transformer, a generator and a changeover.
| Measurement | What it sees | Trap |
|---|---|---|
| Residual of three phase CTs | Earth current leaving the protected circuit | CT mismatch on heavy load or starting can produce false residual current |
| Phase CTs plus a neutral CT (four-wire residual) | Earth current, with normal neutral current cancelled | The neutral CT must be on the correct side of the neutral-earth bond |
| CT on the neutral-to-earth bond (standby earth fault) | All earth-fault current returning to that source | Sees normal neutral current too if there is a second bond elsewhere |
| Core-balance CT around all live conductors | Small earth leakage currents | Cable earth screens must be passed back through it, or it reads wrongly |
Write on the drawing where each earth-fault CT sits relative to each neutral-earth bond, for every source. Most false earth-fault trips on multi-source sites come from a CT that was correct for one source and wrong for the other.
Worked example: neutral current from harmonics
Single-phase electronic loads draw current rich in the third harmonic, and third harmonics in the three phases do not cancel in the neutral; they add. If each phase carries a third-harmonic current of 30% of its fundamental, the neutral carries three times that, 0.9 of the phase fundamental, even when the fundamental currents are perfectly balanced.
The phase current’s own RMS value rises only to about 1.04 times its fundamental, so the neutral current is about 0.86 of the phase RMS current. At 50% third harmonic, the neutral carries 1.5 times the phase fundamental, about 1.34 times the phase RMS current: more than any phase conductor. Size the neutral from a measurement or a harmonic estimate on such boards, not from the assumption that a balanced load leaves it idle. See harmonics and THD.
Circulating current between paralleled generators
When generators with directly earthed neutrals run in parallel, a third-harmonic voltage difference between them drives a circulating current through the joined neutrals, even with no load connected. Alternators with a two-thirds winding pitch produce very little third-harmonic voltage and parallel without trouble; machines of different pitch, or a generator in parallel with a transformer, may not. The symptom is neutral current, and sometimes heating, on a lightly loaded plant. The remedies are matched winding pitch, a single earthed neutral with the others left unbonded, a neutral reactor, or earthing each set through its own impedance, chosen with the protection scheme in mind.
Touch voltage on generator supply
On the utility, an earth fault on a final circuit draws enough current to trip the circuit breaker or fuse quickly, because the transformer’s impedance is low. On a generator, the earth-fault current is smaller and the disconnection slower, and while the fault persists, exposed metalwork can rise to a dangerous voltage. Check the earth fault loop impedance on generator supply, not only on the utility, for the circuits that matter most: outdoor sockets, pumps, lifts and anything people touch. Where the breakers cannot disconnect fast enough on generator supply, residual current devices on those circuits provide the protection the overcurrent devices cannot.
Neutral current and the generator’s own rating
A generator’s neutral connection and its alternator windings are rated for a certain level of unbalance and harmonic current. A site whose neutral carries close to phase current from third harmonics loads the alternator unevenly and heats its windings beyond what the kW reading suggests. Measure the neutral current and the harmonic content before choosing a set for a board dominated by single-phase electronic loads, and ask the maker for the alternator’s unbalance and harmonic limits.
Sizing a neutral earthing resistor on an 11 kV system
Medium-voltage systems are often resistance-earthed to limit the damage an earth fault can do. The resistor is sized from the phase voltage and the chosen fault current. On an 11 kV system, the phase voltage is 11,000 ÷ 1.732, about 6351 V; limiting the earth fault to 300 A needs about 6351 ÷ 300 ≈ 21.2 Ω. The resistor must also absorb the energy of the fault until it is cleared: about 6351 V × 300 A, roughly 1.9 MW, for its rated time, often 10 seconds. The protection must then be set sensitively enough to see 300 A and a fraction of it, since a fault part-way down a winding draws less. See earth-fault and ground-fault protection.
One bond per energised part: a site example
| Source | Neutral-earth bond | Changeover | Earth-fault measurement |
|---|---|---|---|
| Utility transformer | At the transformer star point | Four-pole, neutral switched | Standby earth fault on the transformer bond |
| Generator | At the generator star point | Four-pole, neutral switched | Standby earth fault on the generator bond |
| Downstream boards | None; separate neutral and protective conductors | — | Residual or four-wire residual at each feeder |
With this arrangement each source has exactly one bond in service, the neutral and protective conductors stay separate everywhere downstream, and each earth-fault relay sees only fault current. Any extra neutral-earth link added later in a sub-board, often by an electrician curing an imagined fault, quietly breaks the scheme; an annual check of neutral-to-earth current on each board finds it.
Neutral switching in a four-pole changeover
A four-pole changeover breaks the neutral as well as the phases. If the neutral opened before the phases, or closed after them, the load would briefly see the phases connected with no neutral, and single-phase loads on lightly loaded phases could be exposed to voltages well above their rating. Good four-pole switches therefore make the neutral before the phases and break it after them, an overlapping neutral, or switch it at the same instant with a mechanism designed for that. Ask the maker which method the switch uses, and check it on any changeover built from two four-pole breakers, where the neutral poles open together with the phases.
Unearthed systems and insulation monitoring
Some critical installations run with no neutral-earth bond at all, so a first earth fault causes no trip and the supply continues. That only works if the first fault is detected and repaired before a second one appears on another phase, which would then be a phase-to-phase fault through the earth. An insulation monitoring device measures the insulation resistance continuously and alarms when it falls below a set value. Unearthed systems are specialised and need trained staff, clear alarm handling and fault-location equipment; they are not a general alternative to correct earthing on a commercial or industrial site.
Neutral and earthing faults commonly found on audits
| Finding | Symptom | Correction |
|---|---|---|
| Extra neutral-earth link in a sub-board | Current in the protective conductor; earth-fault relays reading on healthy load | Remove the link; keep neutral and protective conductors separate downstream |
| Generator neutral left unbonded | No earth-fault trip on generator supply; touch voltages on a fault | Bond the generator star point as the design requires |
| Undersized neutral on an IT or LED board | Hot neutral terminals and cable | Measure; upsize the neutral or reduce triplen harmonics |
| Neutral and protective conductor swapped at a board | Residual current devices tripping; equipment frames at neutral voltage | Correct the connection and test |
Testing the neutral-earth scheme
- With the site on the utility, measure the current in the generator’s neutral-earth bond: it should be zero.
- With the site on the generator, measure the current in the transformer’s neutral-earth bond: it should be zero.
- On each source, measure the current in the main protective conductor with a clamp meter: a few amperes at most.
- Inject a simulated earth fault on each source and confirm the correct relay operates and no other.
- Record the readings on the review sheet and repeat after any change to the boards or the changeover.
Common mistakes
- Two bonds in one energised system.
- Changeover poles chosen by habit.
- Earth-fault CT not on the real return path.
- Neutral undersized for electronic loads.
What to send us
Send the single-line diagram with earthing details and the changeover type. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. The example is illustrative; an earthing study governs each site.
Questions engineers ask
How large can neutral current get with harmonic loads?
Larger than the phase current. Third-harmonic currents add in the neutral instead of cancelling, so with 30% third harmonic in each phase the neutral carries about 0.9 times the phase fundamental, even on a balanced load. At 50% third harmonic it carries about 1.5 times the phase fundamental, about 1.34 times the phase RMS current. Size neutrals on such boards from measurement.
Where should the earth-fault CT be on a two-source site?
Where it sees only fault current on every source. With a four-pole changeover and a neutral-earth bond at each source star point, a standby earth-fault CT on each bond sees only that source fault current. A CT that is correct for one source can be wrong for the other, so mark every CT position against every bond on the drawing and test earth-fault protection on each source.
Do I always need four-pole switching?
Not always. It is needed when the transformer and the generator are each earthed at their own neutral and the load moves between them, so that the neutral is switched with the phases and neutral current cannot return through two earthing points. Where the generator neutral is not separately earthed and one common neutral-earth link serves both sources, three-pole switching can be correct.
What causes neutral overheating?
Unbalanced single-phase loads, which leave the difference current in the neutral, and triplen harmonics from electronic loads, which add in the neutral instead of cancelling. With heavy third-harmonic content the neutral current can exceed the phase current, so neutrals on such circuits are sized on the measured neutral current, not on the phase rating.
Why use resistance earthing?
To limit earth-fault current to a value the equipment can tolerate, which reduces damage, arc energy and touch voltages, while still leaving enough current for protection to detect the fault. It is common on larger generators, where a solid earth fault on the winding could otherwise cause severe damage before protection clears it.
Is an unearthed system safer?
It keeps supply on after the first earth fault, because little current flows, which suits continuous processes. But it needs insulation monitoring and a fast way to locate the first fault, because a second fault on another phase becomes a phase-to-phase fault. It can also suffer high transient overvoltages, so it is used only where those risks are managed.
This guide gives general principles. Earthing design must follow local regulations.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.