In short. Different faults need different protection. Start from the fault or abnormal condition you need to cover: short circuit, overload, earth fault, winding fault, busbar fault, loss of excitation, reverse power, or abnormal voltage and frequency. Find the protection technology that detects it, then check that it is set, coordinated and tested. Most protection failures come from a fault type nobody listed, not from a bad relay.
Who this page is for: For electrical engineers, consultants and maintenance teams choosing or reviewing protection for generators, transformers, switchboards and feeders.
Key facts
- List the faults first, then choose the protection for each.
- Overcurrent covers short circuits and overload; differential covers faults inside a zone.
- Earth faults need dedicated earth-fault elements; phase overcurrent may not see them.
- Generators need reverse power, loss of excitation and voltage and frequency protection.
- Busbar faults need fast, dedicated protection or arc detection.
- Every element must be coordinated with upstream and downstream devices.
Fault to protection selector
| Fault or condition | Protection technology | See |
|---|---|---|
| Short circuit between phases | Instantaneous and short-time overcurrent; differential | overcurrent |
| Overload | Thermal or inverse-time overcurrent | overcurrent |
| Earth fault | Earth-fault relay, core-balance CT, restricted earth fault | earth fault |
| Winding fault in generator or transformer | Differential, restricted earth fault, gas and pressure devices | differential |
| Busbar fault | Bus differential, zone interlocking, arc detection | busbar protection |
| Motor stall, single phasing | Motor protection relay | motor and feeder |
| Generator motoring, loss of excitation | Reverse power, loss of field | generator protection |
| Abnormal voltage or frequency | Under and over voltage and frequency | voltage and frequency |
Worked example: a gap in a generator’s protection (illustrative)
A 1000 kVA generator feeding an LV board through its own breaker had only overcurrent and earth-fault protection. A review against the fault list found:
| Fault | Covered? | Added |
|---|---|---|
| Generator motoring in parallel | No | Reverse power |
| Loss of excitation | No | Loss of field |
| Internal winding earth fault (low current at first) | Only when large | Restricted earth fault on the star point |
| Over and under voltage and frequency | Controller alarms only | Protection trips with set delays |
Before the review, a set with failed excitation in parallel would have drawn reactive power from the other set until something else tripped. See restricted earth fault.
Do not assume an overcurrent relay covers every fault. Earth faults in resistance-earthed systems, internal winding faults and loss of excitation can all stay below its pickup.
Steps
- List every fault and abnormal condition for each piece of equipment.
- Choose the protection element for each.
- Coordinate settings across the system.
- Test with secondary injection and trip tests.
Protection coverage sheet
The reference site used across this section, as a coverage matrix over the whole installation rather than the single generator gap in the example above: faults down the left, the element that answers each one, and the setting it actually holds. Built this way round, a gap shows up as a fault with no row rather than as an element nobody questioned.
| Equipment | Fault | Element | Setting | Tested |
|---|---|---|---|---|
| 1010 kVA generator | Winding short circuit | Generator differential | 10% of rated, 1600/5 CTs at both ends of the winding | Primary injection, 14 March |
| 1010 kVA generator | Stator earth fault | Restricted earth fault | 10% of rated, 400/5 core balance on the neutral earthing conductor | Primary injection, 14 March |
| 1010 kVA generator | Overload and external short circuit | Voltage-restrained overcurrent | 1546 A, restrained to half at 40% voltage | Secondary injection, 14 March |
| 1010 kVA generator | Loss of prime mover | Reverse power | 32 kW, 5 s | Fuel reduced on load, 14 March |
| 1010 kVA generator | Field failure | Loss of excitation | The relay’s impedance characteristic, with a 1 s delay | Secondary injection, 14 March |
| Main busbar | Bus fault | Zone selective interlocking, with arc detection | 0.062 s total with arc detection; 0.08 s on interlocking alone | Light injection and functional check, 14 March |
| Feeder 4 | Cable short circuit | Instantaneous overcurrent | 900 A — below the 1044 A the set sustains, above the 768 A element downstream | Secondary injection, 14 March |
| Feeder 4 | Cable earth fault | Earth fault element | 320 A, time multiplier 0.2 | Secondary injection, 14 March |
Read the second column on its own and the gaps become obvious. Every generator fault has a row. The busbar has one. Feeder 4 has two. Sub-board 3 has none at all — no bus protection, and an incomer whose long-time element sits at 1440 A against the 1044 A the generator can deliver, so on generator supply a fault on that board appears in no row of this sheet because no element will clear it.
That is the value of building the matrix from faults rather than from equipment. An equipment-first list produces a reassuring page of relays and settings, every one correctly configured, and says nothing about the board that has no protection when the set is running. A fault-first list leaves a visible hole.
Worked example: why an arcing fault can escape overcurrent protection
An arcing fault in low-voltage switchgear draws less current than a bolted fault, because the arc itself has resistance. At 415 V the arcing current is often taken as roughly half the bolted value, though it varies with the gap and the enclosure.
On a board with a bolted fault level of 30 kA, the arc might draw about 15 kA. If the incomer’s instantaneous element is set at 20 kA to keep it selective with the feeders, the arc falls instead on its short-time element, perhaps 0.3 s, and burns for that time, releasing far more energy than an instantaneous trip would have allowed. Arc-flash detection relays, which trip on light and current together within a few milliseconds, close that gap where it matters. See arc-flash risk and mitigation.
Low-level earth leakage: the faults overcurrent never sees
Some of the most dangerous faults draw almost no current: a frayed flexible cable touching a metal frame, insulation tracking inside a damp junction box, or a person in contact with a live part. Overcurrent and ordinary earth-fault protection cannot see them. Residual current devices measure the imbalance between the live conductors and trip on tens or hundreds of milliamperes. A common scheme uses 30 mA devices for personal protection on socket outlets and portable equipment, and 100 or 300 mA devices for fire protection on larger circuits, graded with time delays so that a leakage fault on a final circuit does not trip the board above it.
Fault location to protection technology
| Where the fault is | Main technology | Backup or supplement |
|---|---|---|
| Generator stator winding | Differential or restricted earth fault | Voltage-restrained overcurrent, earth fault |
| Transformer winding | Differential, restricted earth fault, gas relay | HV overcurrent or fuses |
| Main busbar | Busbar differential or arc detection | Incomer overcurrent and earth fault |
| Cable feeder | Feeder overcurrent and earth fault | Upstream time-graded protection |
| Motor | Motor protection relay or starter overload and short-circuit device | Feeder protection |
| Final circuit with people nearby | Residual current device | Circuit breaker or fuse |
Conditions that are not electrical faults
Some threats to the installation show up first as temperature, insulation or discharge rather than as current. Continuous temperature monitoring of busbar joints and cable terminations finds deteriorating connections. Insulation monitoring on unearthed systems finds the first earth fault before a second one causes an outage. Partial-discharge monitoring on medium-voltage switchgear and cables finds insulation breakdown months before it becomes a fault. These technologies do not replace protection; they add warning time, which is what turns an unplanned outage into a planned repair.
Deciding which gap to close first
Most reviews find more gaps than the budget can close in one go. Rank them by what an uncleared or slowly cleared fault would cost, in safety first and then in outage and damage, against what the remedy costs. Gaps that endanger people, such as missing residual current protection on outdoor sockets or arc exposure on boards worked live, come first. Next come gaps that would stop a critical load or destroy major equipment, such as a generator without reverse power protection in a paralleled plant. Gaps that only make clearing less selective come after. Write the ranking down so that the remaining items are scheduled rather than forgotten.
Proving coverage, not just listing it
A coverage table that ticks every fault type is only as good as the settings and tests behind it. For each tick, confirm three things: the function is enabled and mapped to a trip output, its setting will operate for the smallest fault it is meant to cover on every source, and it has been tested end to end. A function that exists in the relay but has never been wired to the breaker is a gap with a tick beside it. See protection relay setting philosophy.
Repeat the exercise whenever the installation changes: a new generator, a UPS, a large motor or a change of earthing each alters which faults can occur and how much current they draw, and a coverage table that was complete last year may not be this year.
Common mistakes
- Protection chosen by habit, not by fault list.
- No generator-specific elements.
- Earth faults left to phase overcurrent.
- Elements fitted but never tested.
What to send us
Send the single-line diagram and relay list with settings. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. The example is illustrative.
The four gaps this exercise usually finds
Doing this on a real site tends to produce the same short list, in roughly this order of frequency:
- An element set beyond what the source can deliver. Correctly configured, properly tested, and incapable of operating on generator supply because its pickup sits above the fault current available. It passes every test performed on grid. This is the commonest gap on any site with a standby set, and it appears twice in the sheet above.
- Earth faults covered only by phase elements. A phase overcurrent element will see a solid phase-to-earth fault near the source and will not see a resistive one further out, where the current can be a fraction of full load. Earth faults need their own element, set from the earthing arrangement rather than from the load.
- A zone with no fast protection and a slow backup. Usually a sub-board or a busbar, where the design relied on grading from upstream and nobody calculated what that means in clearing time — or in arc energy, which rises with it.
- Protection that exists on paper and was never proved end to end. An element whose settings are right and whose trip path was never injected is an assumption, and it is the one gap that no amount of reviewing settings will reveal.
The order of work that avoids all four: list the plant, list the faults each item can suffer, choose an element for each fault, then set it from the minimum fault current the element must still see — which on a site with a generator is the generator figure, not the grid figure. Then grade it, then test the whole path, then write down the rule beside the number so the next engineer inherits the reasoning rather than just the setting.
Questions engineers ask
Why can an arcing fault escape overcurrent protection?
Because the arc has resistance, so it draws less current than a bolted fault, often around half at 415 V. On a 30 kA board an arc might draw about 15 kA; if the incomer instantaneous element is set at 20 kA for selectivity, the arc falls on a slower short-time element and burns for longer. Arc-flash detection relays, tripping on light and current within milliseconds, close that gap.
What residual current rating protects people?
Devices of 30 mA are the usual choice for personal protection on socket outlets and portable equipment, while 100 mA or 300 mA devices are used for fire protection on larger circuits. Grade them with time delays so a leakage fault on a final circuit trips only that circuit. Overcurrent protection cannot see these small leakage currents at all.
Do all faults need dedicated protection?
No. Every circuit needs protection against overload and short circuit, and every system against dangerous earth faults, but further functions are added by risk and cost of failure. A small standby set may need only its controller protection, while a large paralleled plant justifies differential, reverse power, loss of excitation and arc detection.
Which protection is most often missing?
On sites with generators the common gaps are earth-fault protection that does not work on generator supply, reverse power on sets added to run in parallel, loss-of-mains protection on grid-parallel systems, trip circuit supervision, and short-circuit settings that never pick up on the generator fault current. None of them shows during normal grid operation.
Can one relay do all of these?
A modern multifunction relay includes most functions, such as overcurrent, earth fault, voltage, frequency, reverse power and unbalance, in one device. That reduces cost and wiring, but a single relay or its CT or supply then becomes a single point of failure, so critical plant often uses a second relay or independent backup for the key functions.
Where do I begin?
With an accurate single-line diagram and a short-circuit study giving maximum and minimum fault levels on every source. From those, check device ratings, then whether each protection setting operates at the minimum fault, then coordination. Add generator and earth-fault functions next, and finish with testing the settings actually entered.
This guide gives general principles. Selection requires project data.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.