In short. A generator running in parallel can end up being driven by the system instead of driving it. If its engine loses fuel or its governor fails with the breaker closed, the alternator takes real power from the bus and spins the engine as a motor. Reverse power protection detects this “motoring” and trips before the engine is damaged or the other sets are overloaded. It sits alongside loss of excitation, unbalance and voltage and frequency protection.
Who this page is for: For protection engineers and commissioning teams on paralleled generator sets and grid-parallel systems.
Key facts
- Motoring happens when a paralleled set loses its prime mover power.
- A diesel engine draws only a small share of rating when motored, so settings must be sensitive.
- A time delay rides through brief power swings during synchronising and load steps.
- Loss of excitation makes the set draw reactive power from the bus.
- Negative-sequence protection guards against rotor heating from unbalance.
- Test reverse power by reducing fuel on a paralleled set, not just by injection.
Worked example: setting reverse power on a 500 kW set (illustrative)
| Item | Value |
|---|---|
| Set rating | 500 kW |
| Measured motoring power with fuel cut on test | about 50 kW (10%) |
| Setting chosen | About half of motoring power: 25 kW (5%) |
| Time delay | 5 s, to ride through power swings at synchronising |
| Test result | Fuel reduced with the set in parallel: tripped at about 26 kW reverse after 5 s |
An earlier setting at 15% would never have operated, because the motoring power was only 10%. The set would have stayed connected, driven by the others. See generator relay architecture.
Do not set reverse power higher than the set’s actual motoring power. Measure it on test; a setting above it means the protection will never operate.
Related generator protections
| Protection | Detects |
|---|---|
| Loss of excitation | Set drawing reactive power, losing synchronism |
| Negative sequence | Unbalanced loading heating the rotor. See negative sequence |
| Voltage and frequency | Abnormal operation. See voltage and frequency |
| Overcurrent, voltage-restrained | Faults where generator current decays |
See switchboard architecture and device selection.
Reverse power setting record
Three sets on one bus, each motoring figure measured the way the page recommends — by closing the breaker and winding the fuel back, not by injection. The setting is then placed at about half the measured figure, which is sensitive enough to catch a real loss of prime mover and far enough above measurement noise to stay quiet.
| Set | Measured motoring power | Setting | Delay | Test result |
|---|---|---|---|---|
| Set A, 500 kW | 42 kW, 8.4% of rated | 20 kW, 4% of rated | 5 s | Tripped at 5.2 s with 41 kW flowing in |
| Set B, 500 kW | 46 kW, 9.2% | 20 kW, 4% | 5 s | Tripped at 5.1 s with 45 kW flowing in |
| Set C, 808 kW | 68 kW, 8.4% | 32 kW, 4% | 5 s | Tripped at 5.2 s with 66 kW flowing in |
Note how small the numbers are. A diesel being driven by the bus absorbs well under a tenth of what it produces, so a reverse power element set at the 10 or 20% that feels natural on a protection form would never operate at all. The measured figure is the only sound basis for the setting, and it differs between sets on the same bus because their engines differ.
Worked example: the same setting in three different percentages (illustrative)
Reverse power settings are written as a percentage, but percentages of what? The set rating, the relay’s own nominal power and the secondary watts all give different numbers for the same setting, and a mix-up between them is a common reason for an element that never operates.
| Quantity | Working | Result |
|---|---|---|
| Set | 625 kVA at 415 V, 500 kW at 0.8 power factor | Rated current 625,000 ÷ (√3 × 415) ≈ 870 A |
| Setting chosen | Half of a measured 40 kW motoring power | 20 kW reverse |
| As a percentage of the set’s kW | 20 ÷ 500 | 4% |
| Relay nominal power, 1000/1 A CTs, 415 V direct | √3 × 415 × 1000 | about 719 kW |
| As a percentage of relay nominal | 20 ÷ 719 | about 2.8% |
| Secondary three-phase power | 20,000 ÷ 1000 | 20 W at 415 V |
Entering 4% into a relay that works on its own nominal power would set it at about 29 kW instead of 20 kW. With a measured motoring power of 40 kW that still operates, but on a set that motors at 25 kW it would never trip. Write the setting in primary kilowatts on the record, and state which base the relay uses.
Why the measurement is hard at low power factor
A motoring set usually still has its excitation, so it carries a large reactive current and only a small reverse real power: the power factor is close to zero. A small phase error in the CT then becomes a large error in measured real power, roughly the apparent power times the sine of the phase error.
Take a set motoring at 40 kW while carrying 300 kVAr, about 303 kVA. A protection CT with a phase error of 1 degree, about 60 minutes, misreads real power by 303 × sin 1° ≈ 5.3 kW, more than a quarter of a 20 kW setting. A class 0.5 measuring core, held to about 30 minutes at rated current, cuts that to about 2.6 kW. Many generator relays allow a phase angle correction to be entered; use it from the CT test results, and prove the setting by reducing fuel with the set in parallel, as the record above does.
Three different reverse power functions
| Function | Where it measures | What it protects | Typical action |
|---|---|---|---|
| Generator reverse power | At each set’s breaker | The set and the other sets on the bus | Opens that set’s breaker |
| Export limiting | At the grid incomer | The supply agreement, where export is not allowed | Reduces generator output, then trips the incomer if export persists |
| Grid-side directional power | At the grid incomer or the utility’s side | The utility network from back-feed | Opens the incomer or the generator breakers |
On a grid-parallel site all three may be present. They are set and tested separately, and none of them replaces the others. See utility plus DG synchronisation.
Unloading before opening the breaker
For a planned stop, the controller ramps the set’s load down to a few percent before opening its breaker, so the set is not dropped at load and the others do not take a step. The ramp is also where reverse power is most likely to appear briefly, as the governor settles near zero. That is why the delay of a few seconds matters, and why the unloading level should sit above the reverse power setting rather than below it.
Two stages and what each one is for
- Stage one: a slightly lower setting with a longer delay that raises an alarm, giving the operator warning of a governor or fuel problem before a trip.
- Stage two: the trip setting worked out above, with its delay of a few seconds.
- Fast stage: some schemes shorten the delay when the engine shutdown or fuel shut-off signal is already present, because then reverse power is certain and there is nothing to ride through.
Common mistakes
- Setting above the actual motoring power.
- No time delay, so trips during synchronising.
- No loss of excitation protection.
- Tested by injection only.
What to send us
Send set ratings, relay settings and any trip records. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. Motoring power and settings are illustrative; engine data and tests govern.
What motoring actually does, and why the delay is not optional
A motored diesel is being turned by the alternator acting as a motor. The engine is not producing power, so nothing is burning, and the consequences build quietly:
- Unburnt fuel and cold running. The engine turns at speed with little or no combustion, so cylinder walls cool, fuel washes past the rings and the exhaust fills with unburnt diesel. On a turbocharged set this is also how a turbine gets soaked in fuel.
- Loss of lubrication margin. Driven from the wrong end, the loading on the bearings is not what the engine was designed for, and oil pressure is produced by an engine that is doing no work.
- It hides the real fault. Motoring is a symptom. The cause is a fuel rack that has closed, a governor that has failed, a fuel supply problem or an engine that has stopped while its breaker stayed shut. Tripping promptly is what makes the cause findable.
The delay exists because the same reverse flow appears harmlessly during synchronising and during a large load step, for a second or two, while the governors sort themselves out. A reverse power element with no delay will trip a set during a textbook synchronisation. Five seconds is long enough to ride through that and short enough that a genuinely motoring engine has done no harm.
One consequence for the trip scheme, which is in the protection sheet on the generator protection relay architecture page: reverse power opens the breaker and deliberately leaves the engine running. The engine is not at fault, it is being driven, and disconnecting it is the whole remedy. Wiring reverse power into the engine lockout instead means a fault that should have been a breaker operation becomes a set that will not restart until somebody finds the latched relay.
Reverse power, loss of excitation and unbalance are three different faults
All three appear on a paralleled set, all three are often wired to the same lockout, and they have nothing in common except the machine. Telling them apart from the relay record is what makes the cause findable:
| Fault | What flows | Cause to look for | What should trip |
|---|---|---|---|
| Reverse power | Real power into the set, a few percent of rating | Fuel rack closed, governor failed, fuel starvation, engine stopped with the breaker shut | Breaker only — the engine is being driven, not failing |
| Loss of excitation | Reactive power into the set, while real power may still flow out | Automatic voltage regulator failure, open field, lost sensing, failed exciter diode | Breaker and lockout — the machine cannot support its own voltage |
| Negative sequence | Unbalanced current, drawn by the system rather than the set | A single-phase load concentrated on one phase, an open phase, a blown fuse on one leg | Alarm first, then trip — the fault is usually outside the machine |
The distinction that matters most on site is the first two. Reverse power is a real-power flow and it means the prime mover has gone; loss of excitation is a reactive-power flow and it means the field has gone. An engine that has quietly stopped looks nothing like an alternator whose regulator has failed, and treating both with one lockout relay guarantees that whoever arrives at the panel cannot tell which happened.
Negative sequence belongs in a different category again. Rotor heating from unbalanced current builds over minutes rather than seconds, and the unbalance almost always originates in the load rather than in the set, so an alarm that gives someone a chance to rebalance the phases is more useful than an immediate trip.
Questions engineers ask
Why can a reverse power relay misread at low power factor?
A motoring set still carries reactive current, so its power factor is near zero and a small CT phase error becomes a large real power error, roughly the apparent power times the sine of the error. At 303 kVA, a 1 degree phase error misreads by about 5.3 kW, more than a quarter of a 20 kW setting. A class 0.5 measuring core or the relay angle correction reduces this.
Is a reverse power setting a percentage of the set or the relay?
It depends on the relay, which is why the setting should be recorded in primary kilowatts. On a 625 kVA set rated 500 kW, a 20 kW setting is 4% of the set, but only about 2.8% of a relay whose nominal power is based on 1000/1 A CTs at 415 V, about 719 kW. Entering 4% there would set it at about 29 kW.
Is reverse power needed for a single standby set?
No. A single set running alone has nothing to drive it, so it cannot motor. Reverse power protection is needed as soon as a set runs in parallel with other sets or with the grid, including momentary paralleling for no-break transfer, because then a set that loses fuel or governor control is driven by the others and draws power from the bus.
What happens without it?
The motoring set stays connected and is driven by the other sources. The engine turns with little combustion, so cylinders run cold, unburnt fuel collects in the exhaust and turbocharger, and lubrication works outside its design conditions. The other sets carry the extra load and may overload, and the real cause, such as a closed fuel rack or failed governor, stays hidden.
How is it tested?
In two stages. Secondary injection proves the relay pickup, direction and delay against the setting. Then, with the set in parallel, the fuel is reduced in a controlled way until power flows into the set, which proves the CT and VT connections and the direction on the real plant. Record the measured motoring power, the trip value and the trip time.
Does it replace loss-of-excitation protection?
No. Reverse power detects real power flowing into the set because the engine has lost its drive. Loss of excitation detects reactive power flowing into the set because the field has failed, which can happen while the set still exports real power. Each needs its own element, setting and test, and they call for different trip actions.
This guide gives general principles. Settings need engine and relay data.