Short-Circuit and Fault-Level Engineering Guide

How fault levels are estimated for utility and generator systems: source contributions, transformer impedance, motor input, generator decay, and how results set ratings and settings.

In short. Fault level is the current that flows in a short circuit. It sets the minimum breaking capacity of devices and busbar withstand (maximum case) and also checks that protection will pick up (minimum case). Generators give a lower, decaying fault current, so both cases matter.

What contributes to the fault current

Simple estimates

For a transformer, the approximate fault current on the secondary is its full-load current divided by its per-unit impedance. For a generator, the initial symmetrical value is approximately its full-load current divided by the subtransient reactance in per unit.

If ≈ IFL ÷ Zpu

These are screening values. A full study includes source impedance, cables and motor contribution.

Maximum and minimum cases

CaseUse
MaximumBreaker breaking capacity, busbar and cable withstand, equipment ratings
MinimumCheck that protection picks up and trips in time, important on generator supply

Generator behaviour

A generator’s short-circuit current falls over a short time as flux decays. An alternator without a way to sustain excitation can fall below the overcurrent pickup, and the fault is not cleared. Excitation systems that provide short-circuit support, such as a PMG, help. See alternator reactance and short circuit.

Using the result

  1. Compare maximum fault level with breaker ratings. See device selection.
  2. Check busbar short-time withstand.
  3. Use minimum fault level to confirm pickup and speed.
  4. Feed results to coordination and arc-flash studies.

Illustrative example

A 1250 kVA transformer at 5% impedance gives a secondary fault current of roughly twenty times full load. The same board on a 1000 kVA generator with 15% subtransient reactance might see only about seven times its full-load current, decaying toward about three times. A relay set for the utility case may not trip on the generator alone, so a separate setting is needed.

A worked fault-level calculation (illustrative)

Consider a 1000 kVA, 11 kV/415 V transformer with 5% impedance, supplied from a strong utility so that source impedance is small.

Rated current = 1000 ÷ (√3 × 0.415) ≈ 1391 A

Fault current ≈ Rated current ÷ impedance = 1391 ÷ 0.05 ≈ 27.8 kA

So switchgear on the secondary must be rated above roughly 28 kA, with margin. Adding a weaker source impedance lowers this slightly, but design practice uses the higher figure.

Generator fault current

A generator’s short-circuit current is driven by its reactances. Initially (subtransient) it may be several times rated current, then decays toward the lower steady-state value, which depends on excitation. For a set with 15% subtransient reactance, the initial fault is about 6.7 times rated current. After a short time it may fall to around three times rated with a field-forcing exciter, or lower without. Protection must work with these shapes. See excitation where relevant.

Why both maximum and minimum matter

CaseUsed for
Maximum fault levelEquipment withstand and breaking capacity
Minimum fault levelConfirming protection will trip on the smallest fault, for example on generator only

Contribution from motors

Running motors feed current into a fault for a few cycles. In plants with large motor load, add this to the fault level for breaker making and breaking duty.

Report content

  1. Assumptions and source data.
  2. Fault levels at each bus, maximum and minimum.
  3. Equipment ratings compared with results.
  4. Recommendations.

Related study: utility fault level and source impedance.

How the generator’s fault current changes with time

A generator’s contribution to a fault is not one number. It starts at its subtransient value, falls within a few cycles to its transient value, and settles at a sustained value that depends almost entirely on the excitation system. For a 1000 kVA, 415 V set with a full-load current of about 1391 A, typical reactances give the figures below.

StageGoverning quantity (illustrative)Multiple of rated currentCurrent for a 1000 kVA set
Subtransient, first few cyclesX″d = 0.15 per unitAbout 6.7About 9.3 kA
Transient, first second or soX′d = 0.25 per unitAbout 4About 5.6 kA
Sustained, with PMG or other excitation supportField forcingAbout 3About 4.2 kA
Sustained, self-excited without supportExcitation collapses with voltageCan fall below 1Below rated current

The breaker’s breaking duty is set by the early values. The protection’s ability to clear the fault is set by the sustained value: a time-delayed overcurrent element that needs a second or more to operate sees the sustained current, not the subtransient one. See alternator reactance and short circuit.

Earth faults follow different rules. On a solidly earthed set, a single-phase earth fault at the terminals can exceed the three-phase value, because the zero-sequence reactance of most alternators is small. On a resistance-earthed set, the earthing resistor limits it to a chosen value, often a few hundred amperes, which protects the winding but means that earth-fault protection must be set far more sensitively than phase protection. Both the earthing method and the resulting earth-fault current belong in the fault-level study, alongside the three-phase figures, because they decide the settings of every earth-fault element on the board.

Peak current and the breaker’s making capacity

The symmetrical fault current is not the highest current the equipment sees. In the first half-cycle, an offset in the waveform can raise the peak well above √2 times the symmetrical value, depending on the X/R ratio of the circuit.

The method in IEC 60909 expresses this with a factor κ = 1.02 + 0.98 × e−3R/X. For the 27.8 kA transformer fault worked through above, with an X/R ratio of 10, κ is about 1.75 and the peak is about 1.75 × 1.414 × 27.8, roughly 68.6 kA. The breaker’s rated making capacity, and the busbar’s peak withstand, must exceed that peak as well as the symmetrical current exceeding the breaking capacity. See IEC short-circuit calculation.

How far a cable reduces the fault level

Fault level falls along every cable, and sub-boards are often sized for the main board’s fault level when they need not be, or, worse, protected by devices whose minimum fault current has not been checked. Take the same 27.8 kA main board, whose source impedance per phase is about 239.6 V ÷ 27.8 kA, or 0.0086 Ω, mostly reactive.

Add 100 m of 240 mm² copper cable at about 0.075 Ω per kilometre resistance and 0.08 Ω per kilometre reactance. The total impedance rises to about 0.0186 Ω, and the fault current at the sub-board falls to about 239.6 ÷ 0.0186, roughly 12.9 kA: less than half the main-board value. The same calculation on generator supply, starting from a much higher source impedance, gives a far smaller figure, which is the case the sub-board’s protection must still clear.

The trap when a generator is paralleled with the grid

Fault contributions add. A board rated for the utility’s 27.8 kA becomes inadequate the moment a generator is paralleled with it, because the generator adds its own subtransient contribution of about 9.3 kA for a 1000 kVA set. The total of about 37.1 kA exceeds the breaking capacity of switchgear rated at 36 kA, which was perfectly adequate on either source alone.

The same trap appears with closed-transition changeovers, where the two sources are paralleled for a fraction of a second, and with motor contribution on large motor boards. Recalculate the maximum fault level for every combination of sources the plant can run, including momentary paralleling, before a generator is connected in parallel with an existing supply. See utility and DG synchronisation.

A quick estimate of motor contribution

Running induction motors feed a fault for a few cycles with a current close to their starting current. A board carrying 300 kW of running motors at an efficiency of 0.90 and a power factor of 0.85 has about 392 kVA of motor load, a running current of about 546 A at 415 V. At about five times that, the motors add roughly 2.7 kA to the initial fault current at the board.

That is small beside a 27.8 kA utility fault, but it is a third or more of the contribution of a modest generator, and it adds to the peak the breakers must make. See motor contribution to fault current.

Worked example: will the breaker trip on generator supply?

The minimum case is the one most often missed. On generator supply alone, the 1000 kVA set’s sustained current with excitation support is about 4.2 kA, which corresponds to a source impedance of about 239.6 V ÷ 4.2 kA, or 0.057 Ω. Adding the same 100 m of 240 mm² cable brings the total to about 0.065 Ω, and the sustained fault current at the sub-board to about 3.7 kA. A 400 A breaker feeding that sub-board, with its instantaneous trip set at ten times its rating, needs 4 kA to trip instantaneously, so on generator supply it will not.

It must clear the fault on its short-time or thermal element instead, which takes longer, lets through more energy and may no longer be selective with the generator’s own protection. Lower the instantaneous setting, add a short-time element, or use a separate settings group for generator operation, and check the result against the cable’s withstand. On a set without excitation support, the sustained current may be smaller still. See device selection.

Can the cable survive until the fault clears?

Every cable must carry the fault current until the protection clears it without its insulation being damaged. For faults lasting up to about five seconds, the adiabatic check is I²t ≤ k²S², where S is the conductor size in mm² and k depends on the conductor and insulation, about 115 for copper with PVC insulation. For a 240 mm² copper PVC cable, k²S² is about 762 million A²s.

At the main board’s 27.8 kA it can withstand the fault for about 1.0 s; at the sub-board’s 12.9 kA, for about 4.6 s. A 35 mm² cable connected directly to the 27.8 kA board can withstand only about 0.02 s, which only a current-limiting breaker or fuse can achieve. That check belongs in the same study as the fault levels, because the clearing time depends on the protection settings. See switchboard thermal and busbar engineering.

Fault-level checklist for a generator project

Common mistakes

What to send us

Send the single-line diagram, transformer and generator data and cable lengths. Send your application details. See also fault current basics.

Questions engineers ask

What happens to fault level when a generator parallels with the grid?

The contributions add. A board fed by a 27.8 kA utility supply that is paralleled with a 1000 kVA generator contributing about 9.3 kA sees about 37.1 kA, more than switchgear rated at 36 kA can break, although either source alone was within its rating. Recalculate the maximum fault level for every combination of sources, including momentary paralleling in a closed-transition changeover.

How long can a cable carry a fault current?

Up to about five seconds, use the adiabatic check: current squared times time must not exceed k squared times the conductor size squared, with k about 115 for copper with PVC insulation. A 240 square millimetre copper cable withstands about 27.8 kA for about 1 second and 12.9 kA for about 4.6 seconds. A 35 square millimetre cable on the same 27.8 kA board lasts only about 0.02 seconds.

Why does fault current matter?

Maximum fault current decides the breaking capacity and short-time withstand every device and busbar needs; if it is exceeded, the equipment can fail violently. Minimum fault current decides whether the protection operates at all and how fast. A study that gives only one of the two answers half the question.

Is generator fault current always lower?

Almost always, compared with a strong grid transformer. A generator gives a high subtransient current for a few cycles, about rated current divided by Xd double prime, then decays to a sustained value set by its excitation: about three times rated with a PMG or auxiliary winding, and possibly rated or less with simple shunt excitation.

Should motors be included?

On boards with significant running motors, yes. Induction motors feed current into a nearby fault for the first few cycles, often taken as four to six times their rated current, which adds to the peak and breaking duty of the switchgear. Their contribution decays quickly, so it matters for ratings rather than for time-delayed protection settings.

Do I need to redo the study after changes?

Yes, whenever a source, transformer, generator, large motor group or significant cable changes. A larger transformer can push the fault level past the switchgear rating, and an added generator can do the same in parallel, while a longer cable or a weaker source can stop protection operating. Update the study before the change is energised.

Values here are illustrative screening figures. A full study is needed for design.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 19 October 2026.