In short. Overcurrent protection has two jobs. Overload protection lets a modest excess run for a while and trips before cables and equipment overheat, using an inverse-time curve. Short-circuit protection clears a large fault fast, using short-time and instantaneous elements. Every setting sits in a window: above the highest normal and starting current, and below what the cable can carry and the lowest fault current the circuit can see. On generator supply that lowest fault current is much smaller than on the grid, which is why settings that never nuisance-trip on the grid can fail to clear faults on generator supply.
Who this page is for: For electrical engineers and maintenance teams setting breakers and relays: choose overload and short-circuit settings that are safe on both grid and generator supply.
Key facts
- Overload protection is inverse-time; short-circuit protection is short-time and instantaneous.
- Long-time setting: design current ≤ device setting ≤ corrected cable capacity.
- The short-time pickup must be below the minimum fault current, including on generator supply.
- A 500 kVA generator gives about 4.6 kA initially and about 2.1 kA sustained with PMG excitation.
- Typical grading margin between numerical relays and electronic releases: 0.2 to 0.3 s.
Overload and short circuit are different problems
| Overload | Short circuit | |
|---|---|---|
| Typical current | 1.1 to about 3 times rated | Many times rated, from a few kA to tens of kA |
| Main damage | Slow heating of cable insulation and windings | Arcing, burning and mechanical forces in milliseconds |
| Protection element | Long-time (inverse-time, thermal) | Short-time (definite delay) and instantaneous |
| Trip time | Seconds to minutes | A few milliseconds to a few hundred milliseconds |
The protection elements
| Element | Relay code or release | Purpose | Typical behaviour |
|---|---|---|---|
| Long-time | 51, or the L setting (Ir) of an ACB or MCCB release | Protects cables and equipment against heating | Inverse time: the higher the current, the faster the trip |
| Short-time | 51 with a definite-time stage, or the S setting (Isd, tsd) | Clears faults while letting downstream devices act first | Fixed delay of tens to hundreds of milliseconds |
| Instantaneous | 50, or the I setting (Ii) | Clears severe faults as fast as possible | No intentional delay |
| Earth fault | 50N/51N, or the G setting | Detects earth faults below the phase settings | Low pickup with its own delay |
| Voltage-restrained overcurrent | 51V | Generator backup protection for decaying fault current | Pickup falls as terminal voltage falls |
Inverse-time curves in numbers
Numerical relays use standard curve equations. The three common IEC curves, with I the fault current, Is the pickup and TMS the time multiplier, are:
As a check: a standard-inverse relay with Is = 500 A and TMS = 0.1, seeing 3000 A (6 times pickup), trips in 0.1 × 0.14 ÷ (60.02 − 1) ≈ 0.1 × 0.14 ÷ 0.0365 ≈ 0.38 seconds. Extremely inverse curves suit circuits that must ride through large motor or transformer inrush and grade well with fuses. Standard inverse is the usual choice where fault levels vary a lot, as they do between grid and generator supply.
The setting window
For cable protection, the long-time setting follows the familiar rule that the design current Ib must not exceed the device setting In, which must not exceed the cable’s installed capacity Iz. Iz is the tabulated rating corrected for ambient temperature, grouping and installation method. The cable must also survive the fault until the device clears it: the energy let through, I² × t, must stay below k² × S², where S is the conductor area and k depends on the conductor and insulation.
Why generator supply changes everything
A grid-fed board may see 20 to 40 kA. The same board on a 500 kVA generator sees about 696 ÷ 0.15 ≈ 4.6 kA for the first few cycles, falling within tenths of a second to a sustained value set by the excitation system:
- With a PMG or auxiliary-winding excitation, the sustained fault current is typically around three times rated, about 2100 A for a 500 kVA set, for several seconds.
- With a simple shunt-excited AVR, the field collapses with the voltage and the current can fall to rated or below. An overcurrent element set above that value will never trip.
The answers are a generator-mode setting group with lower pickups, a voltage-restrained (51V) element on the generator, and excitation that holds fault current up. See generator short-circuit contribution.
Worked example: a 630 A feeder on a 500 kVA generator (illustrative)
A factory board is fed from the grid or, in an outage, from a 500 kVA set with PMG excitation (rated 696 A, X″d 0.15). One outgoing feeder has a 630 A MCCB with an adjustable electronic release. The feeder carries a 400 A running load, and its largest motor is a 55 kW direct-on-line motor with a full-load current of about 100 A and a starting current of about 650 A.
| Setting | Value chosen | Check |
|---|---|---|
| Long-time pickup Ir | 0.8 × 630 = 504 A | Above the 400 A load; below the cable’s corrected Iz of 560 A |
| Long-time delay | 12 s at 6 × Ir | Motor start: 300 A of other load + 650 A = 950 A, about 1.9 × Ir, for 5 s. On an I²t characteristic the long-time element at 1.9 × Ir needs roughly 120 s, so the start rides through |
| Short-time pickup Isd | 3 × Ir ≈ 1500 A | Above the 950 A starting current (its first-cycle asymmetric peak dies away well within the 0.2 s delay); below the generator’s sustained 2100 A, a margin of about 1.4 |
| Short-time delay tsd | 0.2 s | Lets downstream MCBs and fuses clear first |
| Instantaneous Ii | 8 × 630 ≈ 5000 A | Operates on grid faults of many kA; on the generator the 4.6 kA initial current is close to or below it (motor contribution or an earth fault can briefly push it higher), so the short-time element must be relied on to do the job |
The common mistake on this feeder would be a short-time pickup of 10 × Ir, about 5000 A, chosen on grid fault levels. On generator supply a fault would then be seen by nothing but the long-time element, and the cable would carry fault current for many seconds. The generator-mode check is what turns a grid design into a safe standby design.
Do not raise breaker settings to stop nuisance tripping without checking the generator-supply fault current. A setting that never trips on a fault is more dangerous than one that trips too often.
Selectivity between levels
Each upstream device must wait long enough for the one below to clear. Typical grading margins are about 0.3 to 0.4 seconds between electromechanical relays and 0.2 to 0.3 seconds between numerical relays and electronic releases. Between breakers with short-time bands, use the maker’s selectivity tables, which often show full selectivity up to a stated fault current. Plot the curves of the generator breaker, the incomer and the largest feeders on one chart at both grid and generator fault levels. See protection coordination and coordination and selectivity.
Motor starting and transformer inrush
A direct-on-line motor draws five to seven times its rated current for several seconds. A transformer can draw a peak inrush of eight to twelve times its rated current, decaying over a few tenths of a second; from a generator the peak is lower but lasts longer and pulls the voltage down. Pickups and delays must ride through both. Where they cannot, the solution is in the starting method (star-delta, soft starter, VFD) or a staged energising sequence, not in raising settings until the protection is useless. See motor starting on generators.
Fuses or breakers
| Fuses (HRC) | Circuit breakers | |
|---|---|---|
| Fault clearing | Very fast and current-limiting on large faults | Fast; current-limiting only in some designs |
| Adjustability | None; choose the rating and class | Adjustable long-time, short-time, instantaneous and earth-fault settings |
| After a fault | Must be replaced with the same type | Reset after inspection |
| On weak generator supply | Slow at low fault current; check the melting curve | Short-time settings can be lowered for generator mode |
Settings worksheet
| Item | Grid supply | Generator supply |
|---|---|---|
| Maximum load current (A) | ||
| Largest start or inrush (A, duration) | ||
| Cable Iz after correction (A) | ||
| Minimum fault current at the far end (A) | ||
| Ir, tr / Isd, tsd / Ii | ||
| Upstream device and grading margin |
Testing
Verify pickups and times by secondary injection for relays and electronic releases, and by primary injection where the whole chain, including CTs, must be proved. Record as-found and as-left settings. See injection testing.
Worked example: voltage-restrained overcurrent on a 500 kVA set (illustrative)
A voltage-restrained element lowers its own pickup as the terminal voltage falls, so it can still operate when a shunt-excited set’s fault current collapses towards rated current. A common characteristic scales the pickup in proportion to voltage, down to a floor of 25%.
| Condition | Working | Pickup |
|---|---|---|
| Full voltage, set at 1.2 × rated 696 A | 1.2 × 696 | about 835 A |
| Voltage at 60%, remote fault | 835 × 0.6 | about 501 A |
| Voltage at 20%, close fault (floor of 25% applies) | 835 × 0.25 | about 209 A |
With a close fault and a shunt-excited set whose current has fallen to about rated, 696 A, a plain overcurrent element set at 835 A never operates; the restrained element, at about 209 A, does. At full voltage it still sits above full load, so normal overloads remain the business of the long-time protection.
Directional overcurrent where two sources feed one board
When a transformer and a generator, or two transformers, run in parallel on one board, a fault on one incoming cable is fed from the board as well as from its own source. Non-directional elements on both incomers see the same current and may both trip, losing the whole board. A directional element on each incomer trips only for current flowing back towards its own source, so only the faulted incomer opens. Directional elements need a voltage reference from a VT and a proven polarity, so include them in the CT and VT checks at commissioning.
Thermal memory after a trip
Electronic releases and numerical relays can remember the heating from a recent overload. Without that memory, a reset and an immediate reclose let the circuit start cold in the relay’s view while the cable is still hot, and repeated resets can overheat it. Keep thermal memory enabled on cable and motor circuits, and record the cooling time it imposes so operators know why a reclose is refused.
Common mistakes
- Setting pickups on grid fault levels and never checking generator supply.
- Instantaneous set too low, so motor starts or transformer inrush trip the feeder.
- Long-time pickup above the cable’s corrected capacity.
- Disabling instantaneous elements for selectivity without checking arc-flash energy.
- Assuming a shunt-excited alternator will sustain fault current.
What to send us
Send the single-line diagram, breaker and relay models with their present settings, cable schedules, the generator data sheet and the largest motors. WhatsApp 98852 01608 or use the enquiry form.
Evidence note. Curve equations are the standard IEC forms. Settings and currents in the example are illustrative; final settings need a protection study and the device makers’ data.
Questions engineers ask
How does a voltage-restrained overcurrent element work?
Its pickup falls in proportion to the terminal voltage, down to a floor, usually 25%. On a 500 kVA generator with the element at 1.2 times rated, about 835 A at full voltage, the pickup is about 501 A at 60% voltage and about 209 A for a close fault. It therefore still operates when the fault current of a shunt-excited set collapses to about rated current.
When is directional overcurrent needed?
When two sources run in parallel on one board, such as a transformer with a generator or two transformers. A fault on one incoming cable is fed from the board as well as its own source, so non-directional elements on both incomers may trip and lose the board. Directional elements trip only the incomer carrying current back towards its own source.
What is inverse-time protection?
Protection whose trip time falls as current rises, matching how cables and equipment heat up. A small overload is allowed to run for minutes, a large one trips in seconds. On the IEC standard inverse curve, a relay at 500 A pickup and time multiplier 0.1 trips in about 0.38 s at 3000 A.
Why does the generator need a special relay?
Because its fault current is high for a few cycles and then decays, to about three times rated with PMG excitation or to rated or below with simple shunt excitation. A standard overcurrent element set above that sustained current never operates. A voltage-restrained element lowers its pickup as the voltage falls during the fault, so it still trips.
Can instantaneous trips be disabled?
Sometimes, on incomers, so that a short-time delay can grade with the feeders below. The price is that a fault near the board, including an arc, lasts for the full delay, raising arc-flash energy and stress on the equipment. Check the arc-flash study and the busbar withstand first, and consider a maintenance setting or arc detection to recover fast clearing.
How do I avoid nuisance tripping?
Set pickups and delays above the largest starting and inrush currents, using measured starting times on every source, and keep thermal memory on. When a trip occurs, read the relay event record before changing anything. Never raise settings above the cable capacity or above the minimum fault current to stop trips; fix the starting method or sequence instead.
This guide gives general principles. Settings need a study and manufacturer data.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.