Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

Power Quality: Stabilisers, UPS, Isolation and Harmonics

Fixing voltage fluctuation, power cuts, noise, surges, harmonics and low power factor: stabilisers, UPS, isolation transformers and APFC.

In short. Power-quality problems are solved by matching the technology to the actual problem. Slow voltage swings need a servo or static stabiliser. Interruptions need a UPS or a generator. Electrical noise and earthing problems point to an isolation transformer. Surges need surge protection. Harmonics and low power factor need filters and correction. Measure first, so the money goes on the right device.

Who this section is for: For facility managers, plant engineers and owners dealing with voltage problems, trips, failures or high electricity charges.

Key facts

  • A stabiliser corrects slow voltage swings; it does not cover outages.
  • An online UPS covers outages and conditions the supply.
  • An isolation transformer helps with noise and earthing problems.
  • Harmonics are worse on generator supply than on mains.
  • Capacitors need care with harmonics and generators.
  • Measure before choosing equipment.

How this section is organised

ProblemTechnologyStart with
Voltage swingsServo or static stabiliserStabiliser selection
Outages and sensitive loadsUPSOnline UPS
Noise and earthing problemsIsolation transformerIsolation transformers
Surges and lightningSurge protectionSurge protection
HarmonicsFilters and mitigationHarmonic mitigation
Low power factorAutomatic correctionPower factor correction
Combined arrangementsStabiliser, UPS and generator togetherIntegrated architecture

Worked example: one site, three problems (illustrative)

SymptomMeasured causeTechnology
Machines reset when voltage sags in the eveningSlow voltage swings on mainsServo stabiliser on the machine feeder
Servers lose power during changeoverBreak between mains and generatorOnline UPS
Capacitor bank failingHarmonics from drivesDetuned correction bank

A single large UPS for everything would have cost more and still left the capacitor problem. See problem to technology and stabiliser or UPS.

Do not buy a stabiliser to solve outages, or a UPS to solve harmonics. Measure the problem, then choose the technology that fixes that problem.

Where to start

If your question is…Start with
What kVA stabiliser do I need?Stabiliser kVA
Servo or static?Servo or static
UPS with a generatorUPS and generator
How do I measure the problem?Power quality monitoring

Problem record

Two columns, because at the intake stage that is all anyone can honestly fill in. A second workshop, separate from the three-problem site in the example above, recorded before any measurement was taken — the symptoms as the maintenance fitter described them. Every one of these five turned out to have a different cause and a different answer.

SymptomWhen, and on mains or generator
Drives trip out at random, no pattern anyone can seeBoth sources, about nine times a week, a little worse on generator
Lights dim and the drives stumbleEvery time the 11 kW coolant pump starts, six times a shift, on both sources
One motor on sub-board 3 runs hotGenerator only, noticeable within twenty minutes of a changeover
Transformer and the neutral bar run hotBoth sources, worst through the afternoon shift
Electronic boards fail after stormsMains, two or three times each monsoon
  
  

The second column does more work than it looks. “On generator only” in row three points at the site rather than the supply, because the generator cannot be the cause of an imbalance it is merely revealing. “Both sources” in rows one and four says the opposite about row one — a disturbance arriving from outside would normally stop when the building is islanded on its own set, and this one does not, which is the first hint that two separate things are happening. And “after storms” in row five is a time signature no amount of voltage correction will address.

Fill this in before buying anything, then record for a week and take it to the problem to technology selection guide, where the same five symptoms appear with their measured causes beside them. The site that started with this record was quoted a single large stabiliser; what it actually needed was a starting method on one pump, reactors on the drives, surge protection and an afternoon of moving single-phase circuits between phases.

What to send us

Send what happens, when, and any readings. WhatsApp 98852 01608 or use the application engineering enquiry.

All 42 guides in this section

Questions engineers ask

Can a servo stabiliser protect against power cuts?

No. A stabiliser corrects voltage only while supply is present. For interruptions you need a UPS, a generator, or both. A UPS bridges short breaks and keeps sensitive loads running without interruption, while a generator carries the site through longer outages. Many sites use all three: a stabiliser for voltage, a UPS for no-break loads and a generator for duration.

Should a stabiliser be fed from the generator?

Usually not, because a healthy generator already regulates voltage closely. Where a stabiliser is used on a DG-backed supply, it must be sized and set to suit the generator’s behaviour. Check that its correction speed does not fight the AVR, and that its frequency window accepts the generator frequency during load steps, or bypass it automatically on generator supply.

Engineering content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026. For advice on your own site, send us your requirement or call 98852 01608.