Automatic Voltage Regulators / AVR Systems

The two meanings of AVR: the alternator excitation controller that holds generator voltage, and the mains-side voltage regulator. How each works, how they differ and what to check.

In short. “AVR” means two different things. On a generator, it is the excitation controller that holds terminal voltage by adjusting the field current. On the mains side, it is a voltage regulator or stabiliser that corrects the incoming supply. Mixing the two up leads to wrong diagnoses and wrong parts. On a generator, most voltage problems trace back to AVR settings, sensing wiring, excitation or engine speed.

Who this page is for: For generator technicians, maintenance engineers and facility managers diagnosing voltage problems on generators or mains regulators.

Key facts

  • Generator AVR: senses terminal voltage, adjusts exciter field, alternator voltage corrects.
  • Under-frequency roll-off lowers voltage as speed falls, helping the engine recover from a load step.
  • Gain and stability settings trade speed of response against hunting.
  • Droop or cross-current compensation shares reactive load between paralleled sets.
  • No voltage build-up usually means lost residual magnetism or an excitation fault.
  • Mains-side AVRs are stabilisers: servo, static or relay types.

Generator AVR settings

SettingEffect
Voltage set point and trimOutput voltage
Gain and stabilityResponse speed versus hunting
Under-frequency roll-off (knee point and slope)Voltage reduction as speed falls
Droop and cross-currentReactive load sharing in parallel

See AVR, PMG and exciter parts.

Worked example: voltage hunting on a 320 kVA set (illustrative)

SymptomCheckFindingFix
Voltage swinging about ±3% at steady loadFrequency steady?Frequency also swinging slightlyGovernor checked first: fuel actuator linkage loose
Still swinging after governor fixAVR stability settingSet too fast after an AVR replacementStability adjusted per maker’s procedure
Large dip on motor startRoll-off knee pointSet at 49.5 Hz, rolling off voltage too earlyKnee point reset to suit the engine and load

The order mattered. Tuning the AVR while the governor was hunting would have hidden one fault behind another. Engine speed problems show up as voltage problems because alternator voltage depends on speed, and below the knee point the AVR deliberately lowers voltage through roll-off.

Do not adjust AVR gain or stability while the engine speed is unstable. Fix the governor first; otherwise AVR settings end up compensating for a mechanical fault.

Typical faults and clues

SymptomLikely cause
Voltage huntingGain or stability, sensing wiring, governor interaction
No build-upLost residual magnetism, excitation circuit fault
OvervoltageSensing lost or AVR failed
Low voltage under loadRoll-off acting due to low speed; excitation weak
Poor reactive sharing in parallelDroop or cross-current settings

Mains-side AVR

On the supply side, an “AVR” is a stabiliser: servo, static or relay type. See servo stabilisers and servo vs static.

AVR settings record

SettingAs foundAs left
Voltage set point  
Stability / gain  
Roll-off knee point  
Droop  

Volts per hertz: why the voltage is allowed to fall

A generator regulator is often expected to hold voltage absolutely steady whatever happens. It deliberately does not, and the setting that decides when it lets go is one of the least understood on the panel. Below a set frequency, called the knee, a generator regulator reduces the voltage in proportion to the speed rather than holding it. On a 415 V set with the knee at 48 Hz and a one-to-one slope:

FrequencyOutput voltageWhat is happening
50 Hz415 VNormal running: the regulator holds the set point
49 Hz415 VAbove the knee: still held
48 Hz415 VThe knee: the last frequency at which full voltage is held
47 Hz406 VVoltage now falls with speed
45 Hz389 VA deep dip during a large load step
43 Hz372 VThe regulator is unloading the engine on purpose

The reason is in the engine, not the alternator. When a large load arrives the engine slows, and the electrical power it is being asked for is roughly proportional to the voltage squared for many loads. Letting the voltage fall with the speed reduces that demand at exactly the moment the engine is struggling, so it recovers faster; holding full voltage would ask the slowing engine for full power and can stall it. The roll-off also protects the exciter and the alternator from the overfluxing that full voltage at low speed would cause.

The setting cuts both ways, and it is a frequent cause of complaints that are diagnosed as regulator faults. A knee set too high, at 49.5 Hz say, makes the voltage sag on every minor load step and the site reports “poor regulation” on a regulator that is doing exactly what it was told. A knee set too low, or the roll-off disabled, holds voltage through a step the engine cannot carry and turns a recoverable dip into a stall. The knee belongs to the engine’s ability to accept load and should be set with it, and the figure belongs in the settings record with the reason it was chosen.

Two regulators in series

Many sites end up with a generator regulator and a mains-side regulator or servo stabiliser in the same path: the stabiliser was installed for the mains, and when the generator runs it is still there. Two controllers trying to hold the same voltage can interfere with each other, and the outcome depends almost entirely on which one is faster.

A generator regulator acts within cycles to fractions of a second. A servo stabiliser drives a motor across a variable transformer and corrects over seconds. Arranged that way round — fast regulator upstream, slow one downstream — the two cooperate: the generator settles the voltage first, and the stabiliser makes small, slow trims on a supply that is already steady.

The trouble appears when the stabiliser is fast, or the generator regulator is slow or badly damped. Each then reacts to the other’s correction, and the voltage at the load swings back and forth in a period of a few seconds that matches neither device on its own, so each looks faulty when examined separately.

Three practical rules follow from that. Tune the generator regulator first, with the stabiliser bypassed, until the set’s own response is stable and well damped. Then bring the stabiliser into circuit and confirm that a load step produces one settling of the voltage, not a slow oscillation. And if the stabiliser has a selectable response speed or a dead band, set it slower and wider for generator operation than for mains, because a generator’s voltage is already regulated and the stabiliser’s job on that supply is only to correct what the cable drop leaves behind.

What the regulator is actually measuring

A regulator can only hold steady the voltage it is connected to sense, and on many sets that is a single line-to-line voltage, taken between two phases. Under balanced load that is a fair proxy for all three. Under unequal single-phase load it is not: the regulator holds its chosen pair correctly while the phase that carries the heaviest load sags and the lightest rises, and the complaint arrives from equipment on a phase the regulator has never seen.

Two decisions improve this, and both are cheap at the design stage. Where single-phase load is significant, specify three-phase sensing, so that the regulator responds to the average of the three rather than to one pair. And where single-phase sensing is what the set has, connect it across the phases that carry the most sensitive load, and record in the settings sheet which phases those are, because the next person to replace a sensing lead will otherwise put it back on whichever pair is nearest.

Finally, the sensing leads themselves are a common fault in their own right. A loose sensing connection reads low, the regulator raises the excitation to compensate, and the output rises above its set point, sometimes far above it. A set that suddenly runs high after maintenance has very often had a sensing lead disturbed, and checking those terminals takes a minute, where replacing the regulator takes a day and changes nothing.

What a regulation figure means in volts

Regulators are sold on a steady-state accuracy expressed as a percentage, and the percentage is easier to compare than to picture. On a 415 V line voltage and its 240 V phase voltage:

Stated accuracyBand on 415 VBand on 240 VTypical of
±0.5%±2.1 V±1.2 VA modern digital generator regulator
±1%±4.2 V±2.4 VA good analogue regulator, or a well-set stabiliser
±2.5%±10.4 V±6.0 VOlder or basic units, still inside most equipment tolerances

Two things are worth reading from the table. Even the widest band is narrower than the tolerance most equipment is built for, so steady-state accuracy is rarely the cause of a complaint; the voltage problems that sites actually report are transient — the dip on a load step and the recovery from it — and the accuracy figure says nothing about those.

And the accuracy applies at the regulator’s own sensing point. A load at the end of a long cable sees the regulated voltage minus the cable drop, which at full load can be several times the regulator’s band, so a regulator chosen for a tighter percentage does not fix a voltage that is being lost in the copper.

Field current as an early warning

A brushless alternator’s exciter field current is set by the regulator to whatever the machine needs to produce its voltage at its load, and that makes it one of the most useful numbers to record. For a healthy machine, the field current at a given load and power factor is repeatable year after year. When a rotating diode fails, or a rotor winding develops a fault, the machine needs more field to produce the same voltage, and the regulator quietly supplies it.

The output voltage therefore looks perfect while the machine is deteriorating, and the only place the change shows is the field current. Record it at commissioning at no load and at a known load, and record it again at the same loads during each annual test. A rise of a noticeable fraction for the same load and power factor is a warning that arrives months before the regulator runs out of range and the voltage finally sags — which is usually when a real event has arrived and the set is needed.

Common mistakes

  • Tuning the AVR while the governor hunts.
  • Replacing an AVR without recording the old settings.
  • Confusing a generator AVR with a mains stabiliser.
  • Sensing wires loose or on the wrong phase.

What to send us

Send the generator rating, AVR details, the symptom and when it occurs. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Settings and values are illustrative; AVR makers’ procedures govern.

Questions engineers ask

What is the volts-per-hertz knee, and how should it be set?

It is the frequency below which the regulator stops holding full voltage and lets it fall in proportion to speed, so that a slowing engine is asked for less power and recovers instead of stalling. With a 48 hertz knee on a 415 volt set, the output is still 415 at 48 hertz and about 389 at 45. Set too high, every small load step sags the voltage; set too low or disabled, a large step can stall the engine. Set it with the engine’s load acceptance in mind and record why.

Can a generator regulator and a servo stabiliser work on the same supply?

Yes, provided the generator regulator is the faster of the two. It acts within fractions of a second and the servo over seconds, so the generator settles the voltage and the stabiliser trims it. If the stabiliser is fast or the regulator poorly damped, each reacts to the other and the voltage swings slowly back and forth. Tune the generator regulator first with the stabiliser bypassed, then set the stabiliser slower and with a wider dead band for generator operation.

Is AVR the same as stabiliser?

No. A generator AVR controls the excitation of the alternator so that the generator holds its own output voltage as the load changes. A stabiliser is a separate unit that corrects the voltage of a supply, grid or generator, on its way to the load. The names are sometimes mixed, but the jobs differ.

What causes hunting?

Hunting comes from AVR gain or stability settings, interaction with the engine governor, loose or poor sensing connections, or the behaviour of the load itself. Check the sensing wiring first, then the governor speed stability, then the AVR settings against the maker guidance, changing one thing at a time while watching voltage and frequency.

Can I replace the AVR myself?

Use a compatible model and a qualified technician. The replacement must suit the alternator excitation system, sensing arrangement and voltage, and its settings for stability, voltage and under-frequency protection are adjusted on load. A wrong model or wiring can damage the exciter or lead to overvoltage on connected equipment.

Why does voltage dip on load steps?

It comes from the alternator and engine response. A sudden load causes an immediate voltage dip in the alternator while the AVR raises excitation, and the engine slows until the governor adds fuel, which the AVR follows. The size of the step, the alternator rating and the AVR and governor settings decide the dip and recovery.

Values are illustrative. Follow the alternator maker’s manual.