In short. Losing a phase, reversing the phase sequence or running on unbalanced voltage overheats motors, runs them backwards and causes nuisance trips. A phase-monitoring relay detects these conditions and opens the control circuit before damage is done. It belongs ahead of motors and pumps, and after every changeover point where the generator’s sequence could differ from the utility’s.
Who this page is for: For maintenance engineers and electricians protecting three-phase motors, pumps and fans on grid and generator supply.
Key facts
- Single phasing makes a motor draw high current on the remaining phases and overheat.
- Wrong sequence runs motors backwards; pumps and motors can be damaged.
- A small voltage unbalance causes a much larger current unbalance and rotor heating.
- Set an unbalance threshold and a trip delay to avoid nuisance trips.
- Check generator phase sequence after any maintenance on its cables or terminals.
- Overload relays alone may not catch single phasing at light load.
The three conditions
| Condition | Effect |
|---|---|
| Phase failure (single phasing) | High current on remaining phases; overheating |
| Wrong sequence | Motor runs in reverse |
| Voltage unbalance | Negative-sequence current heats the rotor |
Worked example: unbalance and motor heating (illustrative)
Line voltages recorded at a pump starter: 415 V, 405 V and 398 V.
| Step | Working | Result |
|---|---|---|
| Average | (415 + 405 + 398) ÷ 3 | 406 V |
| Largest deviation | 415 − 406 | 9 V |
| Voltage unbalance | 9 ÷ 406 | about 2.2% |
| Current unbalance (rule of thumb 6 to 10 times) | 2.2 × 6 to 10 | about 13 to 22% |
| Extra winding temperature rise (rule of thumb 2 × unbalance squared) | 2 × 2.2² | about 10% higher winding temperature rise |
The motor ran hot and its overload tripped in summer. The cause was an uneven distribution of single-phase loads on that board. Rebalancing brought unbalance under 1%. A phase-monitoring relay set at about 2% with a delay was added, so a return to the conditions that overheated the motor would be caught.
After any work on generator cables, terminals or the changeover, check phase sequence before connecting loads. A reversed sequence on the generator side runs every motor backwards the first time the site goes onto the set.
How the relay works and where it goes
- Senses all three phase voltages.
- Checks presence, sequence and balance; often under- and overvoltage too.
- Opens the control circuit after a set delay if out of limits.
- At each important motor starter, or at the incomer of a group of loads.
- After the changeover, so the generator side is checked too. See utility, ATS and DG.
Phase check record
The machine shop from the event classification sheet elsewhere in this section, measured at four points on both sources rather than over time. Unbalance here is the largest deviation from the average of the three line voltages, expressed as a percentage of that average — the figure a relay works from.
| Location | Line voltages | Unbalance | Sequence on grid and generator |
|---|---|---|---|
| Main board, on grid | 414 / 412 / 416 V | 0.5% | Correct on both |
| Main board, on generator | 408 / 425 / 414 V | 2.2% | Correct on both |
| Sub-board 3, on generator | 395 / 428 / 418 V | 4.5% — above the 2% relay threshold | Correct on both |
| Motor terminal box, 90 kW pump, on grid | 410 / 409 / 412 V | 0.4% | Correct on both |
Read rows one and two together. The same board reads 0.5% on grid and 2.2% on generator, and nothing about the wiring changed between the two readings. A utility transformer is a far stiffer source than an alternator, so it absorbs an uneven single-phase load that the generator simply reveals. The imbalance was always there; only the generator made it visible.
Row three is where it becomes a defect. 4.5% voltage unbalance drives a current unbalance several times larger, because the motor presents a very low impedance to the negative-sequence component, and that current does no useful work at all — it heats the rotor. This is the hot motor from the intake record, and the fix is not a relay setting. It is moving single-phase circuits between phases until the three legs carry roughly the same load.
One habit the last column is there to enforce: check the sequence on both sources, every time. A generator reconnected after work on its cables or terminals can come back with two phases swapped, and nothing will show it until a pump runs backwards on the next changeover — by which time it has been running backwards for however long the changeover lasted.
How unbalance reduces motor capacity
A small voltage unbalance causes a much larger current unbalance in an induction motor, and the extra current heats the windings. Motors running on an unbalanced supply must be derated to avoid overheating. The figures below follow a widely used derating curve and are illustrative; the motor maker gives the exact values.
| Voltage unbalance | Approximate allowable motor load |
|---|---|
| 1% | About 98% of rating |
| 2% | About 95% of rating |
| 3% | About 88% of rating |
| 4% | About 82% of rating |
| 5% | About 75% of rating |
Above about 5%, most makers advise against running the motor at all until the supply is corrected.
Choosing a protection relay
| Relay type | Detects | Best use |
|---|---|---|
| Phase failure and sequence relay | Loss of a phase, wrong rotation | Pumps, fans and general motor circuits |
| Voltage unbalance relay | Unbalance above a set level, with time delay | Motors on weak or rural supplies |
| Under and over voltage relay | Voltage outside a set band | Sensitive loads and control panels |
| Motor protection relay | Thermal model, unbalance, phase loss, earth fault | Large or critical motors |
Unbalance on generator supply
On a generator, unbalance usually comes from single-phase loads spread unevenly across the phases rather than from the source itself. The alternator also has a limit on the negative sequence current it can carry. Balancing single-phase loads during installation, and measuring phase currents at full load, protects both the motors and the alternator.
Testing the relays
- Confirm the settings against the schedule.
- Simulate loss of each phase in turn and check the trip and the alarm.
- Reverse two phases at a safe test point and check the sequence trip.
- Check that the relay resets and the motor restarts only as designed.
- Record the results with the date and the tester name.
Phase rotation after maintenance
Any work that disconnects supply cables, such as replacing a generator, transformer or changeover switch, can reverse the phase sequence. Check rotation with a phase sequence meter at the main board on both mains and generator before motors are started, and label the cables so they are reconnected the same way next time.
Calculating voltage unbalance from three readings
A simple method takes the largest deviation from the average of the three line voltages and divides it by that average. With readings of 415, 405 and 400 volts, the average is about 406.7 volts. The largest deviation is 8.3 volts, from the 415-volt phase, so the unbalance is 8.3 divided by 406.7, about 2.0%. On the derating table, a motor on this supply should carry no more than about 95% of its rating. Readings are taken at the motor terminals under normal load, because unbalance at the main board can differ from what the motor actually sees.
Common mistakes
- Relying on overload relays to catch single phasing.
- No sequence check after generator maintenance.
- Thresholds so tight the relay trips constantly.
- Unbalance treated with relays instead of rebalancing loads.
What to send us
Send phase voltage readings and the motor list. WhatsApp 98852 01608 or use the application engineering enquiry. See independent-phase regulation.
Evidence note. The multipliers are common rules of thumb; motor makers’ data govern.
Why an overload relay does not catch single phasing
The commonest assumption about phase failure is that the motor’s overload relay will deal with it. Sometimes it does. The cases where it does not are specific and worth knowing, because they are the cases that burn windings.
When one phase is lost on a three-phase motor, the machine keeps turning on the remaining two and draws roughly 1.7 to 2 times its normal current in them to hold the same torque. On a fully loaded motor that is a clear overload and the relay operates. On a lightly loaded motor — a pump running against a nearly closed valve, a fan on a cool day, a conveyor with nothing on it — the increased current may still sit below the relay setting, so nothing operates while the winding on the two live phases runs hot indefinitely.
Three further cases the overload relay cannot see at all:
- Reversed sequence. The currents are perfectly balanced and perfectly normal. The motor simply runs the wrong way, and a centrifugal pump or a screw machine can be damaged by it within minutes while every meter on the board reads correctly.
- Voltage unbalance without phase loss. As in row three of the sheet above: a few percent of voltage unbalance produces rotor heating out of all proportion to the current rise, and the relay sees a current it is content with.
- A blown fuse on one leg of a star-connected load, where the remaining current path keeps the apparent load plausible.
Which is why a dedicated phase-failure, sequence and unbalance relay is cheap insurance on any motor that matters, and why the threshold and the delay both need setting rather than accepting. A threshold of around 2% unbalance with a few seconds of delay catches real conditions and rides through the momentary unbalance of a large start elsewhere on the bus. Set it tighter and it will trip on every changeover; set it looser and it will allow exactly the condition in row three.
Questions engineers ask
How much should a motor be derated for voltage unbalance?
On a widely used derating curve, about 98% of rating at 1% unbalance, 95% at 2%, 88% at 3%, 82% at 4% and 75% at 5%. Above about 5% most makers advise correcting the supply first, because running a motor on a heavily unbalanced supply shortens its insulation life sharply.
How is voltage unbalance calculated?
Take the largest deviation of a line voltage from the average of the three and divide by that average. With 415, 405 and 400 volts, the average is about 406.7, the largest deviation 8.3 volts, so unbalance is about 2.0%. Measure at the motor terminals under load.
Which relay protects a motor against phase loss and unbalance?
A phase failure and sequence relay covers phase loss and wrong rotation for pumps and fans. A voltage unbalance relay adds an adjustable unbalance trip. For large or critical motors, a motor protection relay combines a thermal model with unbalance, phase loss and earth fault protection.
Why must phase rotation be checked after generator work?
Disconnecting and reconnecting supply cables at a generator, transformer or changeover switch can reverse the phase sequence, making motors run backwards. Check rotation with a sequence meter on both mains and generator before starting motors, and label cables so they go back the same way.
Is a motor overload relay enough?
It helps, because a thermal overload relay trips when the current rises after a phase is lost. But a lightly loaded motor may not draw enough current to trip it quickly, and a dedicated phase failure relay detects loss, unbalance and wrong sequence directly and faster, so critical motors usually have both.
What imbalance trips motors?
Follow the motor maker limits, because even a few percent of voltage unbalance causes a much larger current unbalance and extra heating in the windings. Motors are often derated when voltage unbalance is present, so the protection is set to the maker guidance and the supply unbalance is measured and corrected at its source.
Does a stabiliser protect against phase loss?
It needs separate protection. A stabiliser corrects voltage on phases that are present but does not disconnect motors when a phase is lost, so single-phasing can still burn a three-phase motor. A phase failure relay, set to the motor limits, is installed alongside the stabiliser on every important motor circuit.
Why check sequence on generators?
Because maintenance can swap phases. When generator cables, the changeover or the panel are disconnected and reconnected, two phases can be crossed, and motors then run backwards on generator supply. Check the sequence after any work, and fit a sequence relay so wrong sequence is blocked before damage.
Values are illustrative. Follow motor and relay maker data.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.