In short. “Voltage fluctuation” covers four different problems: slow drift, sudden sags and swells, flicker and very short transients. Each has a different cause and a different cure. Record the supply, classify each event by its size and duration, and work out whether it comes from the utility or from your own loads. Only then choose a stabiliser, UPS, surge protection or a source-side fix.
Who this page is for: For plant engineers and facility managers troubleshooting low voltage, dips, flicker or trips on a factory or building supply.
Key facts
- Drift lasts minutes to hours and is fixed with a servo stabiliser.
- Sags and swells last cycles to seconds; a servo stabiliser is too slow, so use a UPS or conditioner.
- Flicker is repeated small changes from cycling loads; fix it at the source.
- Transients last microseconds to milliseconds; use surge protection.
- Record for at least a full operating cycle, usually a week.
- If your own large load causes the dip, correcting at the victim may not be enough.
Classify first
| Event | Typical duration | Typical cause | Typical cure |
|---|---|---|---|
| Undervoltage or overvoltage | Minutes to hours | Weak or lightly loaded supply | Servo stabiliser |
| Sag or swell | Cycles to seconds | Faults, motor starts, capacitor switching | Online UPS or conditioner |
| Flicker | Repeating small changes | Welders, arc furnaces, cycling loads | Source-side study and mitigation |
| Transient | Microseconds to milliseconds | Lightning, switching | Surge protection |
Worked example: a fabrication shop (illustrative)
A shop reports motors running hot in the evening and CNC controllers resetting during the day. A one-week recording at the main board shows two separate patterns.
| Pattern | Recorded | Class | Cause | Fix |
|---|---|---|---|---|
| Evening low voltage | 415 V falling to about 360 V from 6 pm to 10 pm | Drift (13% low for hours) | Neighbouring load on a weak feeder | Servo stabiliser on the motor bus |
| Daytime dips | Drops to about 85% for 0.2 s, many times an hour | Sag | The shop’s own welders striking | Small UPS on each controller; welders moved to a separate feeder |
The stabiliser alone would have fixed the motors but not the resets: a 0.2 s dip is over before a servo unit moves. The UPS alone would have saved the controllers but left the motors running hot.
Do not buy a servo stabiliser to cure sags or resets. Servo stabilisers correct over seconds; most sags are over in a fraction of a second. Check the recorded duration first.
How each load suffers
- Motors: low voltage raises current and heating; high voltage raises iron loss.
- Drives and electronics: trip on undervoltage or sags.
- Lighting: flicker and shorter life.
- Motors: stall risk at low voltage.
Source or site?
Compare the timing of events with your own plant. If dips line up with your own large starts, the fix may be at that load: soft starting, a separate feeder or reactive compensation. If they line up with nothing on site, the utility is the source. See source impedance.
Measuring
Record voltage per phase with time stamps, current and events, at the supply and at the affected load, for at least a week. Set event triggers below the equipment’s tolerance. See monitoring.
Event classification sheet
A machine shop — not the fabrication shop in the example above — after one week of recording, sorted into classes. Depth and duration together decide the class, and the class decides the equipment — which is why a sheet that records only “low voltage” cannot lead to a correct purchase.
| Event | Depth | Duration | Time and matching plant activity | Class and fix |
|---|---|---|---|---|
| Voltage low all afternoon | 372 V against 415 nominal, 10% low | 3 to 6 pm | Every weekday, no plant activity matches it | Drift — servo stabiliser |
| Sharp dip | To 78%, so 22% deep | 180 ms | Nine times in the week, at random hours, nothing on site running | Sag from the supply — ride-through on the drives and a UPS on controls. A servo stabiliser is far too slow for this |
| Shallow repeated dip | To 89%, so 11% deep | 1.4 s | Six times a shift, every one on an 11 kW coolant pump start | Flicker from our own load — fix at the source with a starting method, not at the victim |
| Spike | 1.8 kV line to neutral | 40 µs | Four events, all during two storms | Transient — surge protection |
| Voltage high | 441 V, 6% high | About 20 minutes | Sundays around 2 am, site almost unloaded | Drift — the same stabiliser covers both ends |
Five events, four classes, and three different pieces of equipment — plus one fix that is not equipment at all. Rows one and five are the same problem at opposite ends and one stabiliser answers both: 372 V to 441 V is a range from 10% low to 6% high, which is comfortably inside what a servo unit corrects.
Row two is the one that catches sites out. A 180 ms sag is over before a servo stabiliser’s motor has meaningfully moved, so a stabiliser bought to stop these trips will not stop them, and the site concludes that power quality equipment does not work. Depth and duration had to be recorded separately for that distinction to be visible at all.
Row three is the cheapest line on the sheet and the only one the site could have found without an instrument: the dip arrives at the same moment as a pump start, every time. Correcting it at the victim means buying equipment to defend the whole workshop against its own coolant pump. Correcting it at the source means a starting method on one machine.
Mitigation options compared
| Option | Works on | Limits |
|---|---|---|
| Soft starter or drive on the disturbing motor | Starting dips at the source | Only the motor it is fitted to |
| Separate feeder or transformer for the disturbing load | Sharing of the voltage drop with sensitive loads | Needs space and cabling |
| Larger or lower-impedance transformer | All voltage drops on the site | Cost and fault level rise |
| Fast reactive compensation | Rapid fluctuation and flicker | Cost; needs a study |
| UPS for sensitive loads | Protecting the victim equipment | Does not cure the cause |
Worked example: welding flicker on a shared feeder (illustrative)
A workshop shares a feeder with an office. Each weld draws a short burst of current, and office lights flicker visibly several times a minute. Recording shows voltage changes of a few percent at each weld, repeated at a rate the eye notices. Moving the welding sets to their own feeder from the main board halves the common impedance, and the flicker drops below the level people notice. A UPS for the office computers was not needed once the cause was separated.
Fluctuation on generator supply
A generator has higher source impedance than a utility transformer, so the same load changes cause larger voltage swings. Loads that are acceptable on grid may cause visible flicker on generator. Checking the largest repetitive loads against the generator voltage response, and starting them only when the set is well loaded, keeps the supply steady.
Checking the cure
After any change, record again at the same points and for a similar period. Comparing the before and after records confirms the improvement and gives a baseline for the future.
Keeping that baseline with the site records also shows quickly whether a later complaint is a new problem or the old one returning.
Common mistakes
- Calling every problem “fluctuation” without measuring.
- Stabilisers bought for sags.
- Recording for a few hours and missing the daily pattern.
- Ignoring your own loads as the source.
What to send us
Send recordings or a description of when problems happen and which loads suffer. WhatsApp 98852 01608 or use the application engineering enquiry. See the problem-to-technology guide.
Evidence note. Voltages and durations are illustrative; recordings at each site decide the fix.
Why depth and duration have to be recorded separately
The classification above is only possible because the instrument captured depth and duration as two independent figures. A great many recordings cannot be classified at all, and the reason is almost always the way the instrument was set up rather than the instrument itself.
- Averaging hides sags completely. An instrument logging ten-minute averages will show the afternoon drift in row one perfectly and will not show row two at all — a 180 ms dip to 78% inside a ten-minute window moves the average by a fraction of a percent. The site sees a flat trace, concludes the supply is healthy, and the drives keep tripping.
- Event capture needs a threshold, and the threshold decides what you learn. Set it at 90% and the 89% pump-start dip in row three is recorded as a borderline event, once. Set it at 95% and you capture every pump start with its timestamp, which is what made the correlation obvious.
- Transients need a different instrument setting again. A 40 µs spike is invisible to anything sampling at cycle level. If storms are part of the complaint, the recorder has to be capturing transients, and most are not doing so by default.
- Log current alongside voltage. Without it, rows two and three look like the same kind of event — both are dips. With current beside them, row three shows a large current step at the same instant and row two shows none, which is the entire difference between a problem the site caused and one that arrived from outside.
Set the recorder to capture averages, events and transients together, over at least a full operating cycle, and log a note of what the plant was doing. One week set up that way answers the question. A month of ten-minute averages does not, however long it runs.
Questions engineers ask
Which options reduce voltage fluctuation on a site?
A soft starter or drive on the disturbing motor, a separate feeder or transformer for the disturbing load, a larger or lower-impedance transformer, fast reactive compensation for rapid fluctuation, and a UPS to protect sensitive equipment, chosen from recordings of the actual problem rather than from symptoms alone.
How can welding flicker in an office be cured?
In the illustrative workshop, welds caused voltage changes of a few percent several times a minute on a feeder shared with the office. Moving the welding sets to their own feeder halved the common impedance, and flicker dropped below the level people notice, without needing a UPS.
Why is voltage fluctuation worse on generator supply?
A generator has higher source impedance than a utility transformer, so the same load changes produce larger voltage swings. Loads acceptable on grid can cause visible flicker on generator, so the largest repetitive loads are checked against the generator response and started when the set is well loaded.
How is a voltage fluctuation fix confirmed?
Record again at the same points and for a similar period after the change, then compare the before and after records. The comparison confirms the improvement and gives a baseline that shows whether a later complaint is a new problem or the old one returning.
Is a stabiliser enough for sags?
Not for fast sags. A servo stabiliser corrects at a limited rate in volts per second, so a sag lasting a fraction of a second passes through before it can respond. Sensitive loads that trip on short sags need a UPS or a fast power conditioner, chosen from logged records of the sag depth and duration.
What is flicker?
Flicker is a repetitive voltage variation, often from welders, arc furnaces, large motor starts or fluctuating loads, that makes lighting visibly change in brightness. It is measured as a severity index by a power quality analyser, and it is reduced at the source or by strengthening the supply, since stabilisers are too slow to correct it.
Can I fix it at the source?
If the cause is within your own installation, yes. Study it first: log which load produces the variation, when, and how large the voltage change is. Remedies include soft starting, separating the load onto its own transformer or feeder, reactive compensation for the fluctuating load and scheduling large starts away from sensitive work.
How long should I record?
Capture at least a full operating cycle of the site, which is often a week, so weekday and weekend patterns, shift changes, peak hours and night-time high voltage all appear. A short recording can miss the event that matters, so the logger stays until the problem has been seen at least once.
Values are illustrative. Follow applicable standards for limits.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.