In short. Oil-cooled servo stabilisers immerse their windings in insulating oil, which carries heat to the tank and radiators. The oil adds thermal mass, so they tolerate continuous heavy loading, dust, heat and short overloads better than air-cooled units. That suits heavy industrial duty and outdoor sites. In return they need oil checks, leak control, space, a suitable floor and attention to fire safety.
Who this page is for: For plant engineers choosing between oil-cooled and air-cooled stabilisers for factories, pump houses and hot, dusty sites.
Key facts
- Heat path: winding losses into oil, oil to tank and radiators, tank to air.
- Thermal mass makes temperature rise slowly during overloads and motor starts.
- Windings stay sealed from dust and humidity.
- Heavier and larger; check floor loading and access.
- Oil level, colour, breather and leaks need regular checks.
- Plan a bund or drainage and clearances for the oil volume.
When oil cooling is the better choice
| Condition | Oil-cooled | Air-cooled |
|---|---|---|
| Large ratings, continuous heavy duty | Preferred | Possible with care |
| Hot, dusty or humid site | Preferred; windings sealed | Filters and cooling needed |
| Frequent motor starts | Thermal mass helps | Check overload rating |
| Clean indoor room, smaller rating | Often unnecessary | Lighter, simpler |
| Outdoor installation | Suits, with a suitable enclosure | Needs a protected room |
Worked example: a pump house (illustrative)
A pump house with four 37 kW pumps (two duty pumps running continuously, a third cycling on and off several times an hour, and the fourth on standby, interlocked so no more than three run) sits in a hot, dusty yard where the supply drifts between about 360 V and 430 V.
| Check | Working | Result |
|---|---|---|
| Running load | 2 × 37 kW at about 0.85 power factor and 0.92 efficiency | about 95 kVA |
| Third pump starting (star-delta, about 2.5 × running) | about 47 kVA × 2.5 | about 118 kVA extra, briefly |
| Ambient | up to 45 °C, dusty | Air-cooled unit would need derating and filters |
| Three pumps running | 3 × about 47 kVA | about 142 kVA continuous at up to 45 °C |
| Peak while the third pump starts | 95 + 118 | about 213 kVA briefly, about 1.07 × a 200 kVA rating, within its short-time overload capacity |
| Choice | 200 kVA oil-cooled servo stabiliser outdoors in a weatherproof enclosure, on a bunded plinth | |
An earlier air-cooled unit in the same yard had needed frequent cleaning and tripped on temperature in summer.
Do not install an oil-cooled unit without planning for its oil: a bund or drainage, clearances, a floor rated for its weight, and the site’s fire-safety requirements. A leak or fire is far harder to deal with after the event.
Inspection list
- Oil level and colour; look for leaks.
- Breather condition and silica gel colour.
- Tank temperature and its trend.
- Brush and roller wear in the servo mechanism.
- Earthing and terminal tightness.
- Oil tests at the interval the maker advises.
Oil-cooled stabiliser record
A year from one pump house, recorded quarterly. Read down the columns rather than across the rows: no single reading here is alarming, and the trend in three of them says the unit needs attention before the next summer.
| Date | Oil level and colour | Breather | Tank temperature | Brush wear |
|---|---|---|---|---|
| 12 January | Full, pale straw | Silica gel blue and dry | 42 °C at 70% load | 2.0 mm left, even across the face |
| 14 April | Full, pale straw | Blue | 48 °C at 70% load | 1.8 mm, even |
| 11 July | 10 mm below full, light amber | Upper third turned pink | 56 °C at 70% load | 1.5 mm, a slight step forming on one brush |
| 9 October | 10 mm below full, amber | Pink throughout, gel replaced | 55 °C at 70% load | 1.2 mm, replacements ordered |
Three things moved together between April and July: the oil darkened, the level dropped and the temperature rose 8 °C at the same load. Taken one at a time each is within tolerance. Together they say the oil is ageing and losing its ability to carry heat away, and the pink breather explains why — moisture has been getting in. The unit needs the oil checked and the breather serviced on a shorter interval, not at the next annual visit.
Oil-cooled and air-cooled units side by side
| Factor | Oil-cooled | Air-cooled |
|---|---|---|
| Typical ratings | Medium to very large, often above 100 kVA | Small to medium |
| Heat handling | Oil carries heat to the tank walls and radiators | Fans move room air across the windings |
| Dust and humidity | Windings sealed in oil, well protected | Exposed to dust and moisture in the cooling air |
| Overload capacity | Good short-time overload because of oil thermal mass | More limited |
| Maintenance | Oil testing, leaks, breather and gaskets | Filters, fans and cleaning |
| Installation | Heavier, may need a bund and fire precautions for the oil | Lighter and simpler |
Keeping the oil healthy
The oil insulates as well as cools, so its condition decides how long the stabiliser lasts. Moisture and contamination lower its dielectric strength and speed up ageing of the paper insulation. A sample is tested for breakdown voltage and moisture, and the results are compared with the maker limits and with previous samples. A falling trend is the early warning; a single low result calls for filtration or replacement before the unit is stressed by a heavy load or a surge.
- Keep the breather silica gel blue or orange as designed, and replace it when it changes colour.
- Check oil level with the unit cool and warm, and look for weeping at gaskets and valves.
- Take samples from the bottom valve after the unit has run, using clean, dry containers.
Sizing for motor starting
A stabiliser feeding motors must carry the starting current without its servo hunting or its carbon track overheating. A common rule is to size the stabiliser so that the largest motor starting current, together with the running load, stays within the short-time overload the maker allows. Soft starters or star-delta starters reduce the step. Where several large motors start together after a supply return, staggering them through the control system protects both the stabiliser and the generator that may be feeding it.
Bypass arrangements for maintenance
A manual bypass switch lets the load run directly from the supply while the stabiliser is serviced. It must be interlocked so the output cannot be connected to the input through the stabiliser and the bypass at the same time, and it must be rated for the full load current. Staff are trained to check the incoming voltage before bypassing, because the load loses its protection while the bypass is closed.
A practical maintenance schedule
| Task | Interval |
|---|---|
| Visual check of oil level, leaks, breather and meters | Monthly |
| Carbon brush and track inspection, servo motor check | Quarterly |
| Oil breakdown voltage and moisture test | Yearly, or after any fault |
| Thermal scan of terminals under load | Yearly |
| Protection and output voltage calibration check | Yearly |
Records that extend service life
Keep each oil test result, brush inspection and thermal scan in one log with the load at the time. Plotted over the years, these figures show when the unit is ageing, so overhaul or replacement can be planned during a shutdown rather than forced by a failure.
Common mistakes
- No bund or drainage.
- Breather silica gel never changed.
- Oil never tested.
- Oil-cooled chosen where a small air-cooled unit would do.
What to send us
Send the load list with motor starts, the site conditions and the supply range. WhatsApp 98852 01608 or use the application engineering enquiry. See industrial servo stabilisers.
Evidence note. Loads, multipliers and ratings are illustrative; makers’ data govern.
Planning the room for an oil-cooled unit
The electrical selection is usually the easy part. What delays these installations is the room, because an oil-cooled unit is heavy, it holds a liquid, and it rejects its heat into the space around it. Four things to settle before the order:
- Floor loading. A 100 kVA oil-cooled unit of the kind we install is commonly in the region of 600 kg including about 150 litres of oil, on a footprint of roughly 0.9 m by 0.7 m. That is 0.63 m² carrying 600 kg, or about 950 kg per square metre — several times what an upper-floor slab is normally designed for. A ground-floor slab or a plinth that spreads the load across a wider area is the usual answer. Confirm the actual weight and footprint against the maker’s drawing.
- Containment. The bund has to hold the whole oil volume with something in hand. For 150 litres, a bund 1.5 m by 1.2 m and 100 mm deep gives 180 litres, which is enough. A unit standing on open floor with a drain nearby is the arrangement that turns a slow leak into a reportable spill.
- Heat. The losses leave as heat into the room. A room with no ventilation path simply rises in temperature until the oil runs hotter, and the record above shows what that looks like: the same load, a higher tank temperature, and oil ageing faster than it should. Give the radiators clear air and a way for warm air to leave.
- Access. Clear space on the service side for the brush gear and the control compartment, room to draw an oil sample and to reach the breather, and an entry route that will actually take the unit — doorway width, lift capacity and turning space on the landing. More than one unit of this size has been craned in through a window because nobody measured the staircase.
None of this applies to an air-cooled unit of the same rating, which is lighter, needs no bund and will go up a staircase. That difference, rather than anything electrical, is what decides the choice on a good many sites.
Questions engineers ask
When is an oil-cooled stabiliser better than an air-cooled one?
For larger ratings, usually above 100 kVA, for dusty or humid sites, and where short-time overload from motor starting is common. The windings are sealed in oil, which carries heat to the tank and radiators, while air-cooled units expose their windings to dust and moisture in the cooling air.
What oil tests does a servo stabiliser need?
Breakdown voltage and moisture, tested yearly and after any fault, with results compared against maker limits and earlier samples. A falling trend is the early warning, and a single low result calls for filtration or oil replacement before the unit faces a heavy load or surge.
How should a stabiliser be sized for motor loads?
So the largest motor starting current, together with the running load, stays within the short-time overload the maker allows. Soft starters or star-delta starters reduce the step, and staggering large motors after a supply return protects both the stabiliser and any generator feeding it from repeated heavy steps.
What makes a stabiliser bypass switch safe?
It must be interlocked so the output cannot be connected to the input through both the stabiliser and the bypass at once, and rated for full load current. Staff check incoming voltage before bypassing, because the load loses its voltage protection while the bypass is closed.
Is oil-cooled safer?
It has different risks rather than fewer. The oil is a fire load and a spill risk, so siting, separation and containment matter, while dust and heat are less of a problem because the windings sit in sealed oil. Choose by the site: dusty, hot or outdoor locations often favour oil cooling.
How often to test oil?
Follow the maker and the site maintenance policy, and trend the results rather than reading each test alone. Breakdown voltage and moisture content show the condition of the oil, and a steady fall points to moisture entering through seals or the breather, which is corrected before it damages the insulation.
Can it be outdoors?
Yes, in a weatherproof design built for outdoor use, with a suitable enclosure rating, protected cable entries, a silica gel breather and a plinth that keeps water away. Shade from direct sun helps cooling, and the electronics compartment is checked for moisture and insects at each service.
Does it need a bund?
Often, depending on the local rules and the oil volume. A bund or containment holds a leak and stops oil reaching drains or soil, and it also limits a fire. Where a bund is not required, a drip tray and regular leak checks are still good practice for any oil-filled unit.
Values are illustrative. Follow maker and local codes.