Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

Servo Voltage Stabilisers

How servo voltage stabilisers work: motor-driven variable transformer, buck-boost correction, accuracy, speed, overload, bypass, wave-form behaviour and where they suit or do not suit.

In short. A servo stabiliser corrects slow voltage variation by moving a carbon-brush contact on an autotransformer, driven by a servo motor, to add or subtract voltage. It gives accurate output and handles overload well, but it is not fast enough for sudden sags.

How it works

Sense output voltage → compare with set value → servo motor moves the variable transformer → buck-boost transformer adds or removes voltage → output returns to the set point.

Characteristics

PropertyTypical behaviour
Output accuracyTight band, such as plus or minus 1% in many models
Correction speedTens to hundreds of volts per second at best, not instant
WaveformPreserved; no added distortion
OverloadGood short-time capability
EfficiencyHigh
MaintenanceBrushes, rollers and motor wear over time

Where they suit

Where they do not

Selection summary

  1. Phase configuration: single or three phase. See selection and sizing.
  2. kVA with margin for inrush and growth. See kVA guide.
  3. Input range from measured data.
  4. Cooling: air or oil. See air-cooled and oil-cooled.
  5. Bypass and protection features.

With generators

On generator supply voltage and frequency vary; check the stabiliser input range and frequency tolerance, and sequence the load so the stabiliser does not hunt. See DG and stabiliser integration.

Illustrative example

A plant at the end of a long feeder sees 340 to 400 V on a 415 V supply. A three-phase servo stabiliser with a wide input range holds 415 V plus or minus a small tolerance. Motors stop tripping on undervoltage, and the starting current falls because voltage is higher.

The physics behind buck-boost correction

A servo stabiliser uses a variable autotransformer to set a voltage, and a series (buck-boost) transformer adds or subtracts that voltage from the incoming supply. The correction needed is the difference between the target and the actual input.

Correction = Target voltage − Input voltage

For a 415 V target and a 360 V input, the series element must add about 55 V. Its rating is only a fraction of the load kVA, which is why the design is economical. At the extremes of the range the series winding carries more of its capacity and the unit is working hardest.

Why response speed is limited

The motor must move the brush along the winding. The control loop deliberately avoids overshoot and hunting, so correction takes time. A step change of 40 V can take a second or more to remove. Loads that cannot tolerate even that need a UPS or fast conditioner behind the stabiliser.

EventServo stabiliser result
Slow rise or fall over minutesFollowed accurately
Step change of tens of voltsCorrected after a delay
Dip of a few cyclesNot corrected
Supply lossOutput lost

What to inspect during service

  1. Carbon brush length and surface; uneven wear marks a mechanical problem.
  2. Roller track cleanliness and smooth travel.
  3. Servo motor current and noise.
  4. Control card voltage settings against a calibrated meter.
  5. Terminal temperature, using thermography under load.
  6. Over and under voltage cut-off operation.

Diagnosis guide

SymptomLikely causeFirst check
Output swings back and forthHunting from control settings or worn brush contactSensitivity setting and brush condition
Output stuck high or lowControl card or motor drive faultControl voltages and limit switches
Tripping on overloadUndersized unit or low input raising currentMeasured current against rating
Excess heatPoor ventilation or loose terminalsRoom temperature and thermography

Commissioning checklist

Local conditions

Dust and heat in industrial areas of Hyderabad and Secunderabad accelerate brush and roller wear and clog ventilation. Plan a cleaning interval that reflects the site, not the brochure default.

The master engineering question

Does the voltage problem change slowly enough for a servo to follow, and does the load need protection from faster events?

Sizing a servo stabiliser step by step

  1. Log the supply voltage for at least a week to find the lowest and highest sustained values.
  2. List the loads with their kW, power factor and starting currents, or measure the running load at peak time.
  3. Convert the running load to kVA by dividing kW by the power factor.
  4. Check the largest motor start against the stabiliser short-time overload rating, with the other loads running.
  5. Add a modest margin for planned growth, not a blanket multiple.
  6. Choose balanced or independent-phase regulation from the load and supply balance.
  7. Check that the input cable and breaker suit the higher input current at the lowest voltage in the range.

A sizing worked through (illustrative)

A small factory has 48 kW of running load at a power factor of 0.85, which is about 56 kVA. Its supply falls to 360 V at evening peak on a nominal 415 V three-phase system. The largest motor is a 7.5 kW pump started direct on line, drawing about six times its running current for a few seconds.

A 75 kVA three-phase servo stabiliser carries the 56 kVA running load at about 75% of its rating, leaving room for the pump start within a typical short-time overload rating and for some growth. At 360 V input, the input current is about 415 divided by 360, or 15% higher than the output current, so the feeding cable and breaker are sized for that.

Because the loads are spread unevenly, with single-phase lighting and office loads on one phase, the factory chooses independent-phase regulation so that each phase is corrected on its own, instead of a balanced unit that would leave one phase high and another low.

Servo, static and relay types side by side

FeatureServoStaticRelay
CorrectionSmooth, steplessSmooth or fine steps, electronicCoarse steps
SpeedModerate, set in volts per secondFastFast but stepped
AccuracyHighHighModerate
Overload and motor startsGenerally tolerantLimited by electronicsLimited by relay rating
Wear partsBrushes or rollers, servo motorFans, capacitorsRelay contacts
Typical useIndustrial and commercial loadsSensitive and fast-changing loadsSmall domestic and office loads

Installation and room conditions

A servo stabiliser turns a small share of its throughput into heat, and its moving parts dislike dust. Place it in a clean, ventilated room or a suitable enclosure, with clear space around for cooling and service access, and away from water. Oil-cooled designs suit dusty and hot sites; air-cooled designs suit cleaner rooms. Cable entries are sealed against dust and pests, and the bypass switch is placed where it can be reached safely.

Keeping it accurate over the years

A well-maintained servo stabiliser gives long service. Accuracy is kept by cleaning the carbon track and checking brush or roller wear, testing the servo motor and its drive, checking the control card calibration against a reference meter, and tightening terminals. Recording output voltage at a few input conditions at each visit shows any drift before the load feels it, and worn brushes or rollers are replaced before they mark the track.

Working with a generator

When the site runs on its generator, the generator AVR already holds voltage closely, so the servo stabiliser has little to correct. Two points still need care. Its control electronics must accept the frequency variation of the set during load steps, and its correction must not chase the small voltage changes the AVR is already correcting, which can make both hunt. Where either is a problem, an automatic bypass on generator supply, selected by a contact from the changeover and interlocked against the stabiliser output, removes the risk. The generator rating includes the small losses of the stabiliser and the starting currents that pass through it.

Common failures and their signs

Specification points that avoid disappointment

State the input range from the survey, the output accuracy the load needs, the correction speed in volts per second, the short-time overload rating for motor starts, balanced or independent-phase regulation, the cooling type, the enclosure rating for the room, protection functions including phase failure and output cut-off, and an interlocked bypass. Ask for the efficiency at full and half load and the expected service intervals for brushes or rollers, so that running cost and maintenance are clear before purchase rather than after.

Comparing offers against the same written list makes it easy to see which unit truly meets the need, rather than choosing on rating and price alone, and it gives a clear basis for acceptance checks when the stabiliser is delivered and commissioned on site.

What to send us

Send voltage records and load details. Send your application details.

Questions engineers ask

How do I size a servo stabiliser for a small factory?

Log the supply, convert the running load to kVA, check the largest motor start against the short-time overload rating and add a modest growth margin. In the illustrative factory, 48 kW at 0.85 power factor is 56 kVA, so a 75 kVA unit runs at about 75% of rating.

Should I choose balanced or independent-phase regulation?

Choose independent-phase regulation where single-phase loads make the phases uneven or the supply voltages differ between phases, because each phase is then corrected on its own. A balanced unit corrects all phases by the same amount and can leave one phase high and another low on such sites.

Can a servo stabiliser stay in circuit on generator supply?

It can, if its electronics accept the frequency variation during load steps and its correction does not hunt against the generator AVR. Where either is a concern, an automatic bypass selected by a contact from the changeover, interlocked against the stabiliser output, is the simplest and safest arrangement.

What are the first signs that a servo stabiliser needs service?

Slow or hunting correction, output stuck high or low, rising temperature and nuisance trips. Most trace to worn brushes or rollers, a dirty carbon track, a weak servo motor, blocked ventilation or a control fault, and regular inspection with output readings catches them before the load is affected.

How fast is a servo stabiliser?

Speed depends on the model, so check the rated correction rate in volts per second on the data sheet and compare it with how fast the supply changes at site. A servo stabiliser suits slow and medium variations; for sudden dips and loads that cannot tolerate a slow correction, a static stabiliser or a UPS is considered.

Does it need maintenance?

Yes. Periodic inspection covers the carbon brushes or rollers and the track of the variable transformer, the servo motor and its drive, the control card and sensing, the contactors and bypass, terminal tightness and cooling. Worn brushes and a dirty track cause slow or erratic correction, so they are checked and cleaned at each service.

Can it run on a generator?

Yes, if its input voltage range and frequency tolerance suit the generator. A generator holds its own voltage through the AVR, so check that the stabiliser does not hunt against it during load steps, and confirm the control electronics accept the frequency variation of the set. Size the generator for the whole connected load.

Does it fix power cuts?

No. A servo stabiliser needs input voltage to work and simply stops when the supply fails. Power cuts are covered by a UPS for short breaks or a generator with an automatic mains failure panel for longer outages; the stabiliser then corrects the voltage of whichever source is supplying the load.

Values are illustrative. Use manufacturer specifications.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 19 October 2026.

CallWhatsAppEnquire