Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

Balanced-Load Servo Stabilisers

When a balanced-load, common-control three-phase servo stabiliser is the right choice, how it behaves under imbalance, sizing, cost trade-offs and checks before choosing it.

In short. A balanced-load servo stabiliser corrects all three phases together with one control and one mechanism. It suits plants where the loads are mainly three-phase and the phase voltages track each other, such as groups of three-phase motors, pumps and fans. It cannot remove differences between phases, so record the phase voltages and currents before choosing it.

Who this page is for: For plant engineers and buyers with mainly three-phase motor loads deciding whether a balanced-load stabiliser is enough.

Key facts

  • One sensing and control circuit drives all three phases together.
  • Any difference between input phases still appears at the output, slightly enlarged by the correction.
  • Suits three-phase motors, pumps and drives with balanced current.
  • Usually simpler and lower in cost than an independent-phase unit of the same rating.
  • Avoid it where single-phase loads are large or phase voltages differ much.
  • Decide from recorded phase voltages and clamp-meter currents, not assumptions.

Worked example: is a balanced unit enough? (illustrative)

CheckPlant A (pump house)Plant B (workshop with offices)
Phase voltages, evening (L-N)214, 213, 215 V203, 224, 213 V
Largest difference2 V (about 1%)21 V (about 10%)
Phase currents150, 148, 152 A140, 85, 110 A
Output of a balanced unit set to 230 V average229 to 231 Vabout 219, 242, 230 V
VerdictBalanced-load is rightIndependent-phase needed

Plant A’s pump motors saw nearly equal voltages, so one control was enough. In plant B, the balanced unit would have left one phase about 5% low and another about 5% high. See independent-phase regulation.

Do not assume the phases are balanced because the loads are “mostly three-phase”. A few large single-phase loads or a weak feeder can make phase voltages differ enough that a balanced unit leaves motors on an unbalanced supply.

When it suits, and when to avoid

SuitsAvoid
Three-phase motors, pumps, drivesLarge single-phase loads on the output
Supplies where phase voltages track each otherLarge differences between input phases
Budget-sensitive sites with small unbalanceEquipment sensitive to voltage unbalance

Checks before selecting

  • Record each phase for a week; compare the largest difference. See monitoring.
  • Clamp each phase current at typical and peak load.
  • Size kVA for the running load plus motor starts. See selection and sizing.
  • Keep phase-failure protection on motors. See phase protection.

Balance check sheet

PhaseVoltage rangeCurrent
R  
Y  
B  
Largest difference and verdict 

Measuring voltage unbalance properly

Voltage unbalance is usually expressed as the largest deviation of any phase from the average of the three, divided by that average. For plant B the evening line-to-neutral readings of 203, 224 and 213 V average 213.3 V; the largest deviation is 10.7 V, so the unbalance is about 5%. For plant A, with 214, 213 and 215 V, it is under half a percent.

For three-phase motors the line-to-line voltages are the ones that matter, because a motor has no neutral connection. Line-to-neutral readings are still useful, since they show which phase carries the extra single-phase load, but the decision on motor protection and on the stabiliser type is made from line-to-line values recorded over at least a week, at the times when the plant load and the network load are both high.

StepPlant APlant B
Average of the three phases214 V213.3 V
Largest deviation from the average1 V10.7 V
Voltage unbalanceabout 0.5%about 5%
What it means for motorsNegligibleWell beyond what motors tolerate without derating

Why unbalance matters to motors

A small voltage unbalance produces a much larger current unbalance in an induction motor, typically six to ten times larger, because the unbalanced part of the supply drives a reverse-rotating field that the rotor resists. The extra current heats the windings without producing useful torque. A widely used rule of thumb puts the extra winding temperature rise at about twice the square of the percentage voltage unbalance: 2% unbalance adds about 8% to the temperature rise, and 4% adds about 32%.

Motor standards therefore derate motors when the unbalance exceeds about 1%, and advise against operating above about 5%. A balanced-load stabiliser does nothing to reduce this, because it raises or lowers all three phases by the same ratio. In plant B the output would still have about 5% unbalance, now around a higher average voltage, and the motors would run hotter than their nameplate suggests.

Why the output difference grows

A balanced unit measures one value, usually the average of the three phases or a single reference phase, and moves all three regulating transformers together. If the input is 10% low on average, it boosts every phase by about 10%. Any difference between the phases is scaled up by the same ratio, so a 21 V spread at the input becomes about a 23 V spread at the output. The effect is small when the boost is small, but on a weak feeder in the evening, when the boost is largest, the unbalance at the output is at its worst.

Distributing single-phase loads

Much of the unbalance inside a plant is created on site, by lighting, office equipment, welding sets and single-phase air conditioners connected without regard to phase. Before deciding on an independent-phase unit, the single-phase loads are listed by phase and moved where possible so the three phase currents are within about 10% of each other. A redistribution costs little and often turns a supply that looked unsuitable for a balanced unit into one that suits it, as long as the incoming network voltages themselves track each other.

Balanced-load and independent-phase units compared

FeatureBalanced-loadIndependent-phase
ControlOne sensing circuit, one servo motorThree sensing circuits and three servo drives
Corrects phase-to-phase differencesNoYes, within its range
Typical useBalanced three-phase motor loadsMixed loads, offices, unbalanced feeders
Wear partsOne set of brushes or rollers per column, driven togetherThree independent sets
Cost and size for the same kVALowerHigher

On generator supply

A generator usually holds its phase voltages closely when the load is balanced, so a balanced-load stabiliser often has little to do while the plant runs on the generator. When the load is unbalanced, however, the phase voltages of a generator also separate, depending on the alternator design and the voltage regulator sensing. The stabiliser and the generator voltage regulator should not fight each other: the stabiliser response speed and dead band are set so that it does not hunt against the regulator after a load step, and the combination is checked on load before the plant relies on it.

Maintenance of a balanced unit

The servo motor, gear train and the carbon brushes or rollers that run on the variable transformer track are the wear parts. On a balanced unit all three columns move together, so wear is usually even, but the track on the most used part of the range wears fastest, and a burnt or pitted track shows as output voltage jumps. The track and brushes are inspected at the interval the maker states, the limit switches and protection are tested, and the output voltage is checked against a calibrated meter at low, normal and high input.

Sizing the unit for plant A

With the balanced-load type confirmed, the rating follows from the measured current and the worst input voltage. Plant A draws about 150 A per phase at about 214 V line-to-neutral, so the running load is about 3 × 214 × 150, or 96 kVA. The output kVA is what the load takes at the corrected voltage of 230 V, which is slightly higher because the motors draw current at the higher voltage: about 3 × 230 × 150, or 104 kVA, as a conservative estimate.

ItemWorkingResult
Running load at 230 V output3 × 230 × 150about 104 kVA
Margin for growth and continuous duty× 1.2about 124 kVA
Largest pump start (direct on line, 15 kW)about 6 × 19 kVA runningabout 115 kVA briefly, on top of the other pumps
Selection125 kVA balanced-load unit, with its short-time overload checked against the pump start, or a soft starter on the largest pump

The input range is set from the week of records: if the lowest evening voltage was 190 V line-to-neutral, the unit must still deliver full output at that input, and its input current at that voltage sets the upstream cable and breaker.

Protection that stays in place

A stabiliser is not a protection device for the motors it feeds. Each motor keeps its own overload relay and, where the supply can lose a phase or reverse its sequence, a phase-failure and phase-sequence relay. The stabiliser has its own protection against output overvoltage and undervoltage, overload and over-temperature, and its output overvoltage trip is checked at commissioning, because a stuck servo at the top of its range can send a high voltage to every motor on the plant.

When the network is the cause

Where the incoming phase voltages differ widely even with balanced plant load, the cause is usually upstream: single-phase loads on the distribution network, a transformer with a faulty tap or winding, or a loose joint on one phase. The week of records is shared with the electricity distribution company with a request to investigate, because a network fault corrected at source helps every consumer on the feeder and avoids buying a larger stabiliser than the plant needs.

What to record before deciding

A useful record covers at least one full working week, includes the evening peak of the local network, logs the three line-to-line and line-to-neutral voltages at one-minute intervals, and logs the three phase currents at the same time. The verdict comes from the worst sustained unbalance during working hours, not from a single reading taken at a convenient moment.

Common mistakes

  • Choosing balanced type without recording phases.
  • Adding single-phase loads later without re-checking.
  • Expecting it to cure unbalance.
  • Removing phase-failure relays.

What to send us

Send per-phase voltage and current readings and the load list. WhatsApp 98852 01608 or use the application engineering enquiry. See three-phase stabilisers.

Evidence note. Readings are illustrative; site recordings govern.

Questions engineers ask

How is voltage unbalance calculated?

Take the average of the three phase voltages, find the phase that deviates most from it, and divide that deviation by the average. Readings of 203, 224 and 213 V average 213.3 V; the largest deviation is 10.7 V, so the unbalance is about 5%. Use line-to-line values for motor decisions.

Why does a small voltage unbalance overheat motors?

The unbalanced part of the supply drives a reverse-rotating field that the rotor resists, so current unbalance is typically six to ten times the voltage unbalance. A common rule puts the extra temperature rise at about twice the square of the percentage unbalance, so 4% unbalance adds about 32%.

Is balanced-load less accurate?

Its accuracy applies to the average or reference phase it measures, not to each phase. Every phase is raised or lowered by the same ratio, so any difference between phases at the input remains at the output, slightly enlarged. On a balanced supply that is fine; on an unbalanced one, individual phases can sit well outside the stated band.

Can it be upgraded?

Usually not economically. Independent-phase regulation needs three sensing circuits, three servo drives and separately moving regulating transformers, which is a different construction. Where unbalance is the problem, first try redistributing single-phase loads and asking the distribution company to check the feeder, then replace the unit if the phases still differ.

Does it fix phase loss?

No. If a phase is lost, a balanced stabiliser cannot create it, and three-phase motors left running on two phases overheat quickly. Keep phase-failure and phase-sequence relays on the motors or the stabiliser output, and check that the protection built into the stabiliser trips on input phase failure as its maker states.

What if the loads change later?

Recheck the balance. Adding large single-phase loads, such as welding sets, offices or air conditioners, can turn a balanced plant into an unbalanced one. Record the phase voltages and currents again after the change, and move to an independent-phase unit only if redistribution of the new loads cannot bring the phases back within a few percent.

Values are illustrative. Use manufacturer specifications.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.

CallWhatsAppEnquire