Buck-Boost Voltage Regulation

The principle behind most voltage correction: adding (boost) or subtracting (buck) a series voltage through a transformer. Includes the kVA saving, limits, a worked example and where to use it.

In short. Buck-boost regulation puts a small transformer winding in series with the supply to add (boost) or subtract (buck) a fraction of the voltage. The series winding carries the full load current but only the correction voltage, so its kVA is a small fraction of the load kVA. That makes it economical for fixed or modest corrections. It gives no isolation, it passes fault current through its series winding, and a fixed boost becomes dangerous if the supply later rises.

Who this page is for: For electricians, maintenance engineers and consultants correcting low or high voltage at a panel or machine, and for anyone comparing buck-boost with a stabiliser or tap change.

Key facts

  • Series transformer kVA ≈ load kVA × (correction voltage ÷ load voltage).
  • The series winding carries the full load current: about 1391 A per 1000 kVA at 415 V.
  • Boost adds voltage; buck subtracts it. A fixed ratio adds or subtracts a fixed percentage, so it suits a steady offset only.
  • There is no isolation: noise, earth faults and neutral problems pass straight through.
  • Full fault current flows through the series winding, which must withstand it or be protected upstream.
  • A stabiliser is a buck-boost stage with sensing and automatic control added.

Principle

Output voltage = input voltage ± correction · Series transformer kVA ≈ load kVA × (correction V ÷ load V)

The secondary of a small transformer is wired in series with the line. Its voltage adds to the supply when connected one way and subtracts when reversed. Because the transformer handles only the correction voltage, a 10% correction needs a transformer of only about 10% of the load kVA, plus margin. A full isolating transformer of the same load would be ten times larger.

Worked example: sizing for a 100 kVA load (illustrative)

A 100 kVA three-phase load at 415 V needs up to 40 V of correction.

StepWorkingResult
Load current100,000 ÷ (1.732 × 415)About 139 A through the series winding
Correction fraction40 ÷ 415About 9.6%
Series transformer kVA100 × 0.096About 9.6 kVA
With margin for taps and lossesAbout 20%A rating of about 12 kVA

The transformer is about one-eighth of the load kVA, but its winding still carries 139 A, so conductor size and terminals are chosen for the full current.

Second example: fixed boost and the over-voltage trap

A 30 kVA lighting and small-power panel at the end of a long cable sees 380 V on a 415 V system. The correction needed is about 35 V, so the series transformer is about 30 × (35 ÷ 415) ≈ 2.5 kVA, plus margin.

Supply at the panelWith a fixed boost (35 V at 380 V, about 9%)Result
380 V (normal)415 VCorrect
400 V (light load at night)About 437 VAbout 5% high: acceptable for most equipment
440 V (supply high)About 481 VAbout 16% high: lamp drivers and electronics at risk

A fixed boost works only if the supply stays near its low value. If logging shows a swing from 360 to 440 V, the right answer is an automatic stabiliser, not a bigger boost. See servo stabilisers and static stabilisers.

Record the supply voltage for at least a week, day and night, before choosing a fixed boost. A single reading taken at the busy hour hides the high voltage that a fixed boost will turn into an over-voltage.

Comparison with other methods

MethodCorrectionIsolationBest for
Fixed buck-boostFixed offsetNoneA steady low or high voltage at one panel
Servo or static stabiliserAutomatic, variableNone in most designsSupplies that swing through the day
Transformer tap changeFixed, set off-loadYes (the transformer itself)A whole site supplied by its own transformer
Isolation transformerRatio set at designYesNoise, earthing and neutral problems. See isolation transformers
Utility-side regulationNetwork levelNot applicableLow voltage caused by the distribution network

Protection concerns

ConcernWhy it mattersResponse
Fault current through the series windingThe winding sees the full prospective fault currentCheck its withstand; protect upstream
Primary (shunt) winding open while load current flowsThe series winding then acts like an open-circuited current transformer and can develop hazardous voltageFollow the maker’s wiring and protection rules
Magnetising inrushSurge at energisationAllow for it in upstream protection
Reversed connectionBucks when it should boostMeasure output before connecting load

Selecting taps and ratios

  1. Log the supply voltage over time, not a single reading.
  2. Decide whether the offset is fixed or varying.
  3. If fixed, pick the ratio that centres the output without exceeding the limit at the highest supply.
  4. If varying, use a stabiliser or an automatically controlled correction.
  5. Size the winding for the full load current and the fault withstand.

Verification

After installation, measure the output at light and heavy load and at the highest and lowest supply. Confirm it stays within the equipment’s tolerance in every case, and record the readings.

Buck-boost worksheet

ItemValue
Load kVA and voltage 
Logged supply range (minimum and maximum V) 
Correction needed (V) and fixed or varying 
Series transformer kVA with margin 
Output at the highest supply (V) 
Upstream protection and fault withstand 

Working out the transformer rating

A buck-boost transformer carries the full load current through its series winding but only the small correcting voltage across it, so its rating is the correcting voltage multiplied by the load current, not the load kVA. For a three-phase load, the rating is roughly the load kVA multiplied by the percentage of correction.

LoadCorrection neededApproximate buck-boost rating
50 kVA10% boostabout 5 kVA
100 kVA8% boostabout 8 kVA
150 kVA5% buckabout 7.5 kVA

The small rating is the attraction of the arrangement: a large load can be corrected with a compact, efficient transformer. The disadvantage is that the correction is fixed for a given tap, so a varying supply is better served by a stabiliser that adjusts the correction automatically.

When a fixed correction is the right answer

A fixed buck-boost connection suits a supply that is consistently high or low by a known amount, such as a site at the end of a long feeder that always sits about 8% low, or equipment built for a different voltage. In those cases a stabiliser would spend its life making the same correction, and a fixed transformer does the same job with fewer parts and lower losses. The supply survey decides: if the voltage stays within a few percent of a steady offset, a fixed correction works; if it swings widely, it does not.

The risk of fixed boost on a varying supply

A fixed 10% boost lifts a supply of 380 V to about 418 V, which is helpful. But if the supply rises to 430 V at night, the same boost gives about 473 V, which may damage equipment. A fixed correction must therefore be chosen for the whole range the supply actually shows, not only its usual low. Where the night-time high would push the output above the equipment limit, a stabiliser or a tap-changing arrangement is used instead.

Connection and safety points

  • The buck-boost winding is in series with the load, so it must withstand the prospective fault current until protection clears it.
  • The arrangement is an autotransformer connection and does not isolate the load from the supply.
  • Polarity determines whether the winding bucks or boosts; a reversed connection doubles the error instead of correcting it.
  • The neutral and earth arrangement is unchanged from the supply, so earth fault protection on the load side still relies on the supply earthing.
  • Labels at the panel state the connection, the tap and the expected output voltage.

On generator supply

A generator holds its voltage closely, so a correction chosen for a low mains supply is usually wrong on generator supply. A fixed boost designed for a mains voltage of 380 V would push a correctly regulated 415 V generator output to about 456 V. Where a site has a buck-boost arrangement, it is bypassed automatically on generator supply, using a contact from the changeover and an interlocked bypass, or the generator voltage is set to suit, after confirming the effect on all connected equipment.

Checking the result

After installation, the output voltage is measured at the lowest and highest supply voltages seen during a week of logging, and compared with the equipment limits. Where the output strays outside them at either end, the tap is changed or the arrangement replaced by a stabiliser. The measurements, tap setting and date are recorded at the panel and in the site file.

The same check is repeated after any change to the supply, such as a new transformer or a change in tariff hours, because the steady offset that justified a fixed correction can change without notice, and an unchecked boost can quietly push equipment beyond its rated voltage.

Common mistakes

  • Choosing a fixed boost from one reading.
  • Sizing the winding by kVA alone and forgetting the full load current.
  • Expecting isolation from a buck-boost connection.
  • Ignoring the fault withstand of the series winding.

What to send us

Send the voltage log, the load kVA and the equipment’s voltage tolerance. WhatsApp 98852 01608 or use the enquiry form.

Evidence note. Figures are illustrative; the transformer maker’s data and the applicable standards govern the design.

Questions engineers ask

How is a buck-boost transformer rated?

By the correcting voltage multiplied by the load current, which for a three-phase load is roughly the load kVA times the percentage of correction. A 100 kVA load needing an 8% boost needs only about an 8 kVA buck-boost transformer, which is why the arrangement is compact and efficient.

When is a fixed buck-boost connection better than a stabiliser?

When the supply is consistently high or low by a known amount, such as a feeder that always sits about 8% low. If the voltage swings widely, a fixed correction can push it too high at times, and a stabiliser that adjusts automatically is the better choice.

Can a fixed boost damage equipment?

Yes, if the supply rises. A 10% boost lifts 380 V to about 418 V, but if the supply rises to 430 V at night the output becomes about 473 V. The correction must suit the whole range the supply shows, not just its usual low.

What happens to a buck-boost arrangement on generator supply?

A boost chosen for a low mains supply over-corrects a regulated generator, pushing 415 V to about 456 V with a 10% boost. It is bypassed automatically on generator supply using a contact from the changeover and an interlocked bypass, or the generator voltage setting is reviewed carefully.

Is it a stabiliser?

It is the correcting element. A buck-boost transformer adds or subtracts a voltage in series with the supply, and a stabiliser adds sensing and control that adjust that correction as the supply changes. A fixed buck-boost connection corrects a steady offset, while a stabiliser follows a varying supply.

Does it isolate?

No. A buck-boost transformer is connected as an autotransformer, so input and output share a conductor and there is no galvanic isolation. Where isolation is needed, for a separate earth reference or to reduce common-mode noise, use an isolation transformer, which has separate primary and secondary windings.

Why smaller than load kVA?

It only carries the correction voltage. The series winding sees the full load current but only the small correcting voltage, so its rating is that voltage multiplied by the current, a small fraction of the load kVA. For example, a ten percent correction needs a buck-boost rating of about one tenth of the load.

What about short circuits?

Fault current flows through the series winding, so the winding must withstand the prospective fault current until the upstream protection clears it. Choose the protection and the transformer short-circuit withstand together, and confirm that the breaker discriminates correctly with the downstream protection for faults on the load side.

Values are illustrative. Design needs a calculation for the actual site.