In short. On generator supply, a servo stabiliser sees voltage dips during load steps, frequency that droops and recovers, and more distortion than on the grid. To work well it needs an input and frequency window that covers the generator’s behaviour. It needs a start delay after transfer so it does not chase the generator’s own regulator. And it needs a deliberate choice of whether it sits before or after the changeover.
Who this page is for: For plant engineers and facility managers running servo stabilisers on sites with generator backup.
Key facts
- A healthy generator already regulates voltage closely; a stabiliser on generator supply is often doing little.
- The stabiliser’s frequency window must cover generator dips, or it cuts out at the worst moment.
- A fast stabiliser and a generator AVR can chase each other and hunt.
- Stabiliser magnetising inrush adds to the load step on a lightly loaded set.
- After the changeover, it corrects both sources but sees generator behaviour; before it, it corrects the utility only.
- Bypassing it on generator is often the simplest stable choice, if the set’s regulation suits the load.
Placement options
| Arrangement | Effect |
|---|---|
| Stabiliser on the utility side, before the changeover | Corrects utility only; generator feeds the load directly |
| Stabiliser on the load side, after the changeover | Corrects both sources; sees generator dips and frequency |
| Separate stabiliser per source | Tailored, but more equipment |
See utility, ATS and DG architecture.
Worked example: hunting after transfer (illustrative)
A plant has a 200 kVA servo stabiliser after the changeover and a 250 kVA generator. In outages, lights pulsed and drives tripped after transfer.
| Finding | Cause | Change |
|---|---|---|
| Output voltage swinging about ±4% every one to two seconds | Stabiliser and generator AVR correcting the same dips at the same time | Stabiliser response slowed; 20 s start delay after transfer |
| Stabiliser cut out on low frequency during a big motor start | Frequency window narrower than generator dip | Window widened within the maker’s limits; largest motor started first, before the other loads |
| Large step at transfer | Stabiliser inrush plus all load at once | Loads re-sequenced in steps |
After the changes, the next outage transferred cleanly with no hunting. An alternative the plant considered was to bypass the stabiliser on generator, since the set held voltage within about ±1% at steady load.
Do not leave a stabiliser’s frequency window set for grid supply when it runs on generator. A window that is too narrow makes it cut out during exactly the motor starts it should ride through.
Sequencing
- Let the generator reach stable voltage and frequency.
- Transfer, with a start delay on the stabiliser.
- Start loads in steps, largest motor first while the set has the most margin. See motor starting.
- Watch for hunting during step changes and adjust.
Common problems on generator
- Cut-out on generator frequency below the window.
- Stabiliser and AVR chasing each other.
- Stabiliser inrush on a lightly loaded set.
See wide-input-range stabilisers and servo stabilisers.
Generator operation settings
| Setting | Value |
|---|---|
| Stabiliser position (before or after changeover) | |
| Frequency window | |
| Start delay after transfer | |
| Bypass on generator? (yes/no, why) |
When the stabiliser is really correcting the cable
A generator’s regulator holds the voltage at the alternator terminals, not at the building. When the set stands well away from the loads, the cable between them drops a voltage that rises with the load current, and the voltage at the far end falls as the load grows even though the generator itself is holding steady. Much of what a stabiliser does on generator at such sites is correct that cable drop.
| Load current | Drop in 120 m of 70 mm² copper at 0.8 power factor | At the building, set at 415 V | At the building, set at 423 V |
|---|---|---|---|
| 0 A | 0 V | 415.0 V | 423.0 V |
| 50 A | 3.2 V | 411.8 V | 419.8 V |
| 100 A | 6.3 V | 408.7 V | 416.7 V |
| 150 A | 9.5 V | 405.5 V | 413.5 V |
| 200 A | 12.6 V | 402.4 V | 410.4 V |
The figures use a resistance of 0.32 Ω/km at working temperature and a reactance of 0.08 Ω/km. Two remedies are open before a stabiliser is needed. Raising the generator’s set voltage by about 2%, to 423 V, centres the building voltage around 415 V across the normal load range, at the cost of a slightly high voltage at light load.
And many regulators offer line-drop compensation, which raises the set voltage in proportion to the load current, holding the far-end voltage nearly constant. Where either is enough, the stabiliser can be bypassed on generator, which is often the simplest stable choice when the set’s own regulation is good. Where the cable is long and the load varies widely, the stabiliser earns its place.
How a stabiliser can undo the generator’s own protection
When a large load is applied, the generator’s speed dips, and a well-set regulator deliberately lets the voltage fall in proportion to the frequency below a set knee. That reduces the power the load draws, which helps the engine recover its speed. A servo stabiliser downstream does not know why the voltage has fallen.
It sees low voltage and boosts it back, restoring the load’s power demand just as the engine needs relief, and the speed recovers more slowly as a result. A slow servo usually arrives too late to matter for a short dip, but a fast stabiliser, or a deep dip that lasts several seconds on a heavily loaded set, can turn a recovery into a stall.
The remedy is to make the stabiliser aware of frequency. Many stabilisers can be set to stop correcting, or to hold their last position, when the frequency falls below a threshold, and that threshold should sit just above the generator regulator’s knee. Where the stabiliser has no such setting, a slower correction rate on generator, or bypassing the stabiliser for the first seconds after a large load step, achieves much the same.
Running the stabiliser itself at low frequency
The stabiliser’s own transformers have a magnetic flux proportional to voltage divided by frequency. At 415 V and 50 Hz they are designed to sit comfortably below saturation. At 415 V and 47.5 Hz the flux is about 5.3% higher, and if the stabiliser is boosting at the same time, the boost winding sees more. A unit designed with little margin then draws a sharply higher magnetising current, runs hot and hums.
A generator that runs steadily below 50 Hz — an old governor, an overloaded set — therefore stresses a stabiliser that would be quite comfortable on the mains. Check that the stabiliser’s rating covers the generator’s frequency range, and treat a stabiliser that hums loudly on generator as a sign that the set’s frequency needs attention.
Motor starts through a stabiliser on generator
A motor started through a stabiliser draws its starting current through the stabiliser’s windings, and on generator that current is also a large reactive load step on the set. Two effects add up. The generator voltage dips while its regulator responds, and the stabiliser, if it is fast enough to react, starts boosting into the start, increasing the current the motor draws.
And the stabiliser’s own series windings add impedance to the motor’s supply, deepening the dip at the motor terminals slightly. On the mains, with its much stiffer supply, neither effect is noticeable. On generator, a large direct-on-line start through a stabiliser can dip the voltage deeply enough to drop contactors elsewhere on the same supply.
Three measures help. Feed large motors from a branch that bypasses the stabiliser, as most designs already do for motors; use a soft starter or star-delta start on any motor that must be fed through it; and confirm that the stabiliser’s short-time overload rating covers the motor’s starting current for the duration of the start.
Where several motors must start after a transfer to generator, start them in sequence with a few seconds between each, largest first while the set is least loaded, so that each start is complete and the voltage recovered before the next begins. The sequence belongs in the AMF or building controls, written down with its delays, not left to whichever motors happen to restart when the supply returns.
The neutral through the stabiliser on generator
Most three-phase servo stabilisers are built around autotransformers, which share the neutral between input and output: the stabiliser does not create a new neutral, it passes the supply’s neutral through to the load. On generator, that neutral is the generator’s, bonded to earth at the set or at the main board depending on the earthing design and on whether the changeover switches the neutral. The stabiliser’s sensing and control refer to that neutral, so a poor neutral connection anywhere between the generator and the stabiliser shows up first as erratic correction on the lightly loaded phases.
Two checks belong in the commissioning of a stabiliser on a generator-backed supply. Confirm that the neutral is continuous and correctly sized from the changeover through the stabiliser to the load board, with no neutral link removed during installation; and measure the neutral-to-earth voltage at the stabiliser output with the load running on generator. A few volts is normal on a loaded system; a figure that rises steadily with load, or that differs sharply from the same reading on mains, points to a neutral connection that needs attention before it becomes a floating neutral.
Proving the stabiliser on generator during routine tests
Monthly generator tests usually prove the set and the changeover, and leave the stabiliser untested on the supply it behaves worst on. Adding a few readings to the test record closes that gap.
| Reading | When | What it shows |
|---|---|---|
| Stabiliser input and output voltage, each phase | Before transfer, on mains, and after transfer, on generator | Whether the stabiliser is correcting on generator, and by how much |
| Whether the servo is moving with a steady load | Five minutes after transfer | Hunting with the generator regulator, if it never settles |
| Generator frequency at the largest load step | During the test load step | Whether the stabiliser’s frequency window and freeze threshold are being reached |
| Stabiliser temperature and noise | At the end of the run | Signs of over-flux from low frequency |
The first reading is the one to watch over months. A stabiliser that corrects little on generator, month after month, is a candidate for a bypass on generator; one whose correction on generator grows over time is reporting a change in the set’s regulation or in the cable, either of which deserves attention before it becomes a fault.
Common mistakes
- Grid settings left on generator supply.
- No start delay, so the stabiliser chases the AVR.
- All load connected at transfer.
- A stabiliser kept on generator where it adds nothing.
What to send us
Send the generator and stabiliser ratings, their position and what happens on transfer. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. Swings, delays and windows are illustrative; makers’ settings govern.
Questions engineers ask
Why is the voltage low at the building when the generator shows 415 volts?
Because the generator regulates the voltage at its own terminals, and the cable to the building drops a voltage that grows with the load. 120 metres of 70 square millimetre copper carrying 150 amps at 0.8 power factor drops about 9.5 volts, so the building sees about 405 volts. Raising the generator set voltage by about 2%, or using line-drop compensation in the regulator, often fixes this without needing a stabiliser on generator.
Can a stabiliser slow the generator recovery after a load step?
Yes. On a large load step the generator regulator lets the voltage fall with the frequency to reduce the load and help the engine recover. A stabiliser downstream sees only low voltage and boosts it back, restoring the load just when the engine needs relief. A fast stabiliser or a long dip can turn a recovery into a stall. Set the stabiliser to stop correcting below a frequency just above the generator regulator knee, or slow its correction on generator.
Do I need a stabiliser on a generator?
Often the generator AVR is enough, because a healthy set holds its voltage within a narrow band. Add a stabiliser only where data shows a need, such as long cables to remote loads, very sensitive equipment, or a set whose AVR cannot hold voltage on varying load.
Why does it hunt?
Hunting comes from interaction between the AVR, the governor and the stabiliser, each correcting the changes the others make. Check the generator alone first, then reduce the stabiliser correction speed or widen its dead band, so that it does not chase the small voltage changes the AVR is already correcting.
Can I bypass it on generator?
It is possible with the right design, using a bypass switch controlled by a signal from the changeover, so the stabiliser is bypassed automatically on generator supply. Interlocks prevent the bypass and stabiliser output from being connected together, and the logic is tested in both supply states.
What frequency window?
Check the frequency window of the model, because generators drift slightly under load and dip during load steps. A stabiliser whose control electronics expect a tight mains frequency may trip or mis-correct on generator supply, so the window is compared with the generator governor performance.
Values are illustrative. Test on site.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.