Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

Servo Stabiliser + Isolation Transformer

How to combine a servo stabiliser with an isolation transformer: order of equipment, sizing, inrush, earthing, protection, losses and when the combination is justified for sensitive equipment.

In short. A servo stabiliser followed by an isolation transformer gives a supply that is both regulated and isolated, with a clean new neutral reference. This combination protects precision equipment on poor, noisy supplies. The order of the units, the transformer’s inrush current, the earthing of the new neutral and the protection on both sides all need deliberate design.

Who this page is for: For lab, instrumentation and production engineers protecting precision equipment from both poor voltage and noise.

Key facts

  • The stabiliser fixes voltage level; the isolation transformer fixes noise and the earth reference.
  • Stabiliser first, then transformer, is the usual order: the transformer sees steady voltage and its output is isolated.
  • Transformer inrush at switch-on can be many times its rated current; size upstream protection for it.
  • Bond the new neutral to earth at one point, with a short path.
  • The isolated system needs its own earth-fault arrangement.
  • Add both units’ losses to the room’s heat load.

Order of equipment

ArrangementConsideration
Stabiliser, then transformerTransformer gets regulated input; output isolated from the stabiliser’s noise; the transformer’s own voltage drop under load is not corrected
Transformer, then stabiliserStabiliser works on the isolated source and also corrects the transformer’s voltage drop; earthing of the secondary matters more

Decide by the fault paths and the earthing design, not by habit.

Worked example: a measurement lab (illustrative)

A lab’s supply drifts between about 200 V and 245 V, and its instruments show noise of about 5 V between neutral and earth. Load: 15 kVA of instruments.

ItemChoiceReason
Stabiliser20 kVA servo15 kVA plus margin for low-input current
Isolation transformer20 kVA, screenedSame load plus harmonic margin
Inrush at switch-onUp to about 10 × rated current for a few cyclesUpstream breaker curve chosen not to trip on it
Neutral-earth bondAt the transformer secondary, one point, short heavy leadClean new reference
ResultOutput held near 230 V; neutral-to-earth noise under 1 V

Neither unit alone would have fixed both problems: the stabiliser does nothing for the noise, and the transformer does nothing for the drift.

Do not leave the transformer secondary neutral unbonded, or bond it in more than one place. Unbonded, earth-fault protection may not operate; bonded twice, circulating currents bring the noise back.

Sizing and heat

Size the stabiliser for load kVA with starting and low-input allowances. Size the transformer for the same kVA plus harmonic margin. Add both units’ losses to the heat budget; together they can be a noticeable load for a small room.

Protection

  • Overcurrent protection on both sides, chosen to ride through inrush.
  • Earth-fault protection for the isolated system.
  • Temperature protection on the transformer.

See isolation transformers and ultra-isolation designs.

Combination design sheet

ItemValue
Load kVA 
Stabiliser rating and input range 
Transformer rating and screen type 
Upstream breaker and inrush check 
Neutral-earth bond location 

The new neutral and the earthing arrangement

An isolation transformer with a separate secondary winding creates a separately derived system. Its secondary neutral has no connection to the incoming neutral, so the earthing of the new system must be designed rather than inherited. In most low-voltage installations fed this way the secondary neutral is bonded to the protective earth at one point, normally at the transformer or at the first distribution board it feeds, which makes the new system a TN-S system with its own neutral-earth bond. That bond is what allows an earth fault on the secondary side to return to the transformer and operate the protection.

The bond is made once. A second bond further downstream lets normal neutral current flow in the protective conductors and in any metalwork connected to them, which brings back the very noise the transformer was installed to remove, and can make earth-fault protection behave unpredictably. Where the secondary is deliberately left unearthed, as an IT system in some specialist applications, the system needs an insulation monitoring device and a design for what happens on the first and second faults; that is a different arrangement with its own rules, not a forgotten bond.

Arrangement on the secondaryNeutral-earth bondEarth-fault protection
Separately derived TN-S, the usual caseOne bond, at the transformer or first boardOvercurrent devices or RCDs, sized for the fault loop of the new system
IT system for special applicationsNo bond; insulation monitoring insteadAlarm on first fault, disconnection on second, by design
Autotransformer or transformer without separate windingsNo new neutral is createdFollows the upstream system; this is not an isolation transformer

The earth electrode or the connection to the main earthing terminal, the size of the bonding conductor and the location of the bond are shown on the drawing and checked against the earthing arrangement of the building.

Checking the fault loop on the secondary

The transformer impedance limits the fault current on its secondary side. A 20 kVA single-phase transformer at 230 V has a full-load current of about 87 A; with an impedance of 4%, the prospective short-circuit current at its terminals is roughly 87 ÷ 0.04, or about 2200 A, and less at the end of each outgoing cable.

Every outgoing circuit breaker must trip within the required time at the lowest fault current on its circuit, which is checked from the loop impedance of the transformer, the bond and the cable. Where a long cable gives too little fault current for a breaker to trip in time, an RCD is used on that circuit.

Inrush and the upstream breaker

When a transformer is switched on, its core may be driven into saturation for the first few cycles and the current can rise to many times its rated value, depending on the point on the wave at switch-on and the remanent flux. The upstream breaker is chosen with a curve that rides through that inrush while still protecting the cable and the stabiliser. Where the stabiliser sits upstream of the transformer, the stabiliser must also tolerate the inrush; the maker of each unit confirms it. A soft energising arrangement or a breaker with a higher magnetic setting is used where nuisance tripping persists.

Measuring before and after

The worked example quotes neutral-to-earth noise before and after the installation. Such figures are only meaningful when measured the same way each time: at the same socket or terminal of the sensitive equipment, with the same load running, using a true RMS meter for the steady value and a power-quality recorder or oscilloscope for spikes and high-frequency noise. The input voltage range is logged for at least a week before the stabiliser rating is fixed, so that the lowest and highest input voltages, not a single reading, set the stabiliser input range.

Losses and room heat

Both units dissipate heat. A servo stabiliser typically loses a few percent of its throughput, and a dry-type transformer of this size loses roughly two to four percent at full load. For the 15 kVA laboratory load at around 0.9 power factor, that could be 600 to 900 W in total, comparable to several people in the room. The losses are taken from the makers data at the expected load and added to the air-conditioning load, and the units are placed where their own cooling air is not recirculated.

When the combination is justified

The two units solve two different problems, so the combination is justified only where both problems are present and measured. A supply that drifts in voltage but has a clean neutral needs only a stabiliser. A supply with good voltage but noise between neutral and earth, or with equipment that needs galvanic isolation, needs only an isolation transformer. Installing both where one would do adds cost, losses, heat and another point of failure. The input voltage log and the neutral-to-earth measurements made before the design are what decide it, and they are kept with the design file so the choice can be explained later.

Where a UPS fits

Neither unit holds the supply up during an outage or a deep dip shorter than the stabiliser response time. Equipment that must ride through interruptions, such as data acquisition or controllers, is fed from a UPS on its own branch, downstream of the transformer where isolation is also needed. The UPS then sees a stable, isolated input and spends less time on battery, and its own output earthing is checked against the same TN-S design. Loads that tolerate a short break stay on the stabilised and isolated supply without the UPS.

Commissioning checks

CheckAcceptance
Insulation resistance of both units and cablesWithin the maker and installation limits
Single neutral-earth bond on the secondaryBond present at the designed point only; no current in the protective conductor at no load
Earth fault loop impedance on each outgoing circuitProtective device trips in the required time
Switch-on with the upstream breakerNo nuisance trip on repeated energising
Stabiliser output at low and high inputOutput within the stated band
Neutral-to-earth voltage at the sensitive equipmentRecorded and compared with the baseline
Temperatures after a full-load runWithin the maker limits; room temperature held

Choosing the isolation transformer

Three features decide most transformer choices for this duty. An electrostatic screen between the windings, connected to earth, reduces the coupling of high-frequency noise from primary to secondary; a double or triple screen is chosen where common-mode noise is the main problem.

Where the load includes electronic power supplies, the transformer is rated for their harmonic current, using a K-factor rating or a derating agreed with the maker, so that it does not overheat at a load that looks well within its kVA. The winding connection and the output voltage are matched to the load, and taps allow the secondary voltage to be set to the stabilised value under real load.

A dry-type transformer is usual indoors, with temperature sensors in the windings connected to an alarm and, where the duty calls for it, a trip.

Common mistakes

  • Upstream breaker tripping on transformer inrush.
  • Neutral bonded in two places, or not at all.
  • Heat from both units ignored.
  • Combination used where only one problem exists.

What to send us

Send the load, supply recordings and noise measurements. WhatsApp 98852 01608 or use the application engineering enquiry. See stabiliser vs isolation transformer.

Evidence note. Ratings and inrush multiples are illustrative; makers’ data govern.

Questions engineers ask

Where should the neutral be bonded to earth after an isolation transformer?

Once, at the transformer secondary or at the first distribution board it feeds, which makes the new system a TN-S system with its own neutral-earth bond. A second bond downstream lets neutral current flow in the protective conductors and brings the noise back, while no bond at all can stop earth-fault protection working.

How much fault current does a small isolation transformer give?

Its impedance limits it. A 20 kVA single-phase transformer at 230 V has a full-load current of about 87 A, and with 4% impedance the fault current at its terminals is about 2200 A, less at the end of each cable. Each outgoing breaker must trip in time at the lowest fault current on its circuit.

Does the order matter?

Yes, for protection, inrush and earthing. With the stabiliser first, the transformer receives regulated voltage and its output is isolated, but its own voltage drop is not corrected. With the transformer first, the stabiliser corrects that drop but works on the new isolated system. The earthing design and fault paths decide which order suits the site.

Add losses?

Yes. Both units dissipate heat, typically a few percent of their throughput each. For a 15 kVA load the total can be several hundred watts, comparable to several people in the room. Take the losses from the maker data at the expected load and add them to the air-conditioning load and to the energy budget.

Can I add a UPS?

Yes, as a separate branch for loads that cannot tolerate an interruption, usually downstream of the isolation transformer so the UPS receives a stable and isolated input. Its output earthing is checked against the same design. Loads that can accept a short break stay on the stabilised and isolated supply without the UPS.

Is it needed everywhere?

No. The combination is justified only where both problems are present and measured: voltage drift that needs a stabiliser, and neutral-to-earth noise or a need for galvanic isolation that needs a transformer. Where only one problem exists, one unit solves it with less cost, loss, heat and fewer points of failure.

Values are illustrative. Design needs site study.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.