APFC and Power-Factor Correction

How APFC panels correct power factor with switched capacitors: sizing kVAr, steps, controllers, detuning reactors for harmonics, generator operation, protection and common failure causes.

In short. An automatic power factor correction (APFC) panel switches capacitor steps in and out to supply the reactive power that inductive loads need. Sized well, it lowers current, losses and penalties. Sized or placed badly it can resonate with harmonics, fail its capacitors or push a generator into leading power factor and overvoltage. Size from measured kW and power factor, detune where harmonics exist, and control it on generator supply.

Who this page is for: For plant electrical engineers and facility managers with power factor penalties, failing capacitors or APFC panels on sites with generators.

Key facts

  • Required kVAr = kW × (tan φ1 − tan φ2), from measured power factor to target.
  • Split the total into steps fine enough to follow the load.
  • Where harmonics exist, use detuned reactors to avoid resonance.
  • Use capacitor-duty contactors and protect with fuses, discharge resistors and temperature sensing.
  • On generator, over-correction gives leading power factor and voltage rise; interlock or limit the panel.
  • Most capacitor failures come from harmonics, heat and overvoltage.

Worked example: sizing a panel (illustrative)

StepWorkingResult
Measured load200 kW at 0.80 power factor250 kVA
tan φ1 at 0.800.75 
tan φ2 at 0.980.20 
kVAr needed200 × (0.75 − 0.20)110 kVAr
After correction200 ÷ 0.98about 204 kVA
Current at 415 Vfrom about 348 A to about 284 Aabout 18% less
Stepse.g. 10 + 20 + 20 + 30 + 30 kVArFollows load in 10 kVAr steps

The site also had about 120 kW of drives, so the panel was built with detuned reactors, using capacitors rated for the higher voltage the reactors cause and steps chosen for their delivered kVAr. A plain-capacitor panel on the same bus had failed twice in two years.

Do not leave the APFC panel switching freely on generator supply. A lightly loaded set with capacitors connected can go to leading power factor, lose voltage control and trip. Interlock the panel or limit its steps when the generator is on.

Design points

ItemWhy it matters
StepsFine steps follow load variation
Controller and CT locationCT must see the total load current, upstream of the panel
Detuning reactorsNeeded where harmonics exist
ContactorsCapacitor-duty rated, to handle switching inrush
ProtectionFuses, discharge, temperature

See harmonics and harmonic and resonance studies.

Why capacitors fail

  • Harmonic currents and resonance.
  • High panel temperature from poor ventilation.
  • Overvoltage from over-correction at light load.
  • Switching without discharge time.

APFC sizing sheet

ItemValue
Measured kW and power factor 
Target power factor 
kVAr needed and step plan 
Harmonic loads present? Detuning chosen 
Generator interlock arrangement 

Where the capacitor bank resonates

A capacitor bank does not sit on its own. Together with the inductance of whatever supplies it — a transformer, or a generator — it forms a resonant circuit, and the frequency at which that circuit resonates decides whether the bank is harmless or dangerous on a site with harmonic load. The resonant harmonic order is the square root of the supply’s short-circuit kVA divided by the bank’s kVAr, which makes it possible to see the problem before it is installed:

Bank sizeOn a 1000 kVA transformer at 5% impedanceOn a 500 kVA generator at 0.12 per unit
100 kVAr14.1th harmonic, 707 Hz6.5th, 323 Hz
200 kVAr10.0th, 500 Hz4.6th, 228 Hz
300 kVAr8.2th, 408 Hz3.7th, 186 Hz
600 kVAr5.8th, 289 Hz, beside the 5th2.6th, 132 Hz

Two readings matter. On the transformer, a bank that grows over the years walks its resonance down towards the 5th and 7th harmonics — exactly the orders that drives and rectifiers produce most strongly — and at 600 kVAr it sits beside the 5th. Harmonic current near a resonance is amplified rather than absorbed, the capacitors overheat, their fuses blow, and the voltage distortion on the whole board rises. That is the commonest reason for capacitor failures that look random.

On the generator, everything moves down at once, because a generator’s short-circuit capacity is a fraction of a transformer’s. The same 300 kVAr that is safely tuned at the 8th harmonic on the mains resonates at about the 3.7th when the site changes over. A bank that has run without trouble for years can therefore fail in its first long outage, for a reason nobody can find afterwards, because the circuit it was in only existed while the generator was running.

What a detuned reactor actually does

The reactor fitted in series with each capacitor step moves the resonance deliberately to a frequency below the lowest harmonic present, so that the combination looks inductive to every harmonic the load produces and cannot be excited by any of them. Its tuning follows directly from its percentage: tuned frequency = 50 ÷ the square root of the reactor percentage.

ReactorTuned toHarmonic orderWhere it is used
5.67%210 Hz4.2Sites where the 5th is the lowest significant harmonic and third-harmonic content is negligible
7%189 Hz3.78The common choice on mixed industrial and commercial load
14%134 Hz2.67Where third-harmonic current is significant, such as large single-phase electronic loads

The detuned bank fixes the resonance on both supplies at once, which is the strongest argument for it on any site with a generator. Plain capacitors that are acceptable on the mains are a gamble on the generator, because the resonance moves with the source. A reactor-detuned bank is tuned by its own components, not by the supply, so it behaves the same way whichever source is running — though it should still be limited or switched out on generator for the leading-power-factor reasons on the generator pages.

Why the kVAr on the label is not the kVAr delivered

A capacitor’s output goes as the square of the voltage across it, and capacitors for harmonic duty are deliberately rated above the system voltage for headroom. The consequence is routinely missed at the sizing stage. A step labelled 50 kVAr delivers its rated output only at its rated voltage:

Capacitor rated voltageOutput on a 415 V systemShortfall against the label
415 V50.0 kVArNone
440 V44.5 kVAr11%
480 V37.4 kVAr25%
525 V31.2 kVAr38%

In a detuned bank the reactor raises the voltage across the capacitor, which is exactly why higher-rated capacitors are used there, and the effective output of the combination is a figure the panel maker should state for the system voltage, not the capacitor label. A bank sized by adding up labels on 525 V capacitors is more than a third smaller than the calculation it was meant to satisfy, and the site wonders why the power factor never reaches its target. Ask for, and record, the delivered kVAr per step at 415 V.

Why a detuned bank needs higher-voltage capacitors

A series reactor does more than tune the step: it raises the voltage across the capacitor above the system voltage, by the factor 1/(1 − p), where p is the reactor percentage. With a 7% reactor on 415 V the capacitor sees about 446 V before any harmonic voltage is added; with 5.67%, about 440 V; with 14%, about 483 V. That is why a 7% bank is built with 480 V or 525 V capacitors and never with 415 V ones, and why a 415 V capacitor fitted into a detuned bank as a like-for-like replacement fails early.

The same factor works in the bank’s favour on output. A 480 V capacitor labelled 50 kVAr delivers 37.4 kVAr on 415 V on its own, but with a 7% reactor in series the step delivers about 40.2 kVAr, because the reactor lifts the voltage across the capacitor. A 525 V capacitor with a 14% reactor gives about 36.3 kVAr. Ask the panel maker for the delivered kVAr of the complete step, capacitor and reactor together, at 415 V: that is the only figure the controller settings and the step-current check can be judged against.

Step size, and why a controller hunts

An automatic panel can only add and remove whole steps, so the size of its smallest step decides how close it can get to the target, and whether it settles at all. Take a 300 kW load at 0.8 power factor, drawing 225 kVAr, with a target of 0.95. The exact correction needed is 126 kVAr, and the panel can only offer multiples of its step.

With 50 kVAr steps, its nearest choices are 100 kVAr, giving 0.923, and 150 kVAr, giving 0.970. Neither is the target. A controller set with a narrow band around 0.95 switches the third step in, sees 0.97, decides it has overshot, switches it out, sees 0.92, and switches it back — every few minutes, all day. Each operation stresses the contactor and the capacitor, and a bank that hunts like this wears out its switching hardware long before its capacitors.

With 25 kVAr steps the same panel can land on 125 kVAr and 0.949, inside any sensible band, and stop. The rule that follows is simple: the smallest step should be no larger than the reactive change the controller is expected to correct within its band, and the band should be at least as wide as the smallest step can move the power factor. Where the load swings widely, a mix of large steps for the bulk and small steps for trimming does both jobs.

The reconnection delay in the controller belongs to the same discussion and should never be shortened to make the panel respond faster. A capacitor that has just been switched out still holds its charge for a short time, and switching it back in at the wrong instant can put close to twice the supply peak across it and its contactor. The delay exists to let the discharge resistors bring that voltage down first. A panel that switches a step out and back in within seconds is either set too tightly or has a delay that someone has reduced, and either way it is shortening the life of the parts it switches.

The one measurement that checks every step

Each step’s delivered kVAr can be checked in seconds with a clamp meter, because a capacitor’s current is fixed by its kVAr and the voltage: current = kVAr × 1000 ÷ (√3 × 415). A step genuinely delivering 25 kVAr at 415 V draws 34.8 A per phase; one delivering 50 kVAr draws 69.6 A; and a 50 kVAr step built from 440 V capacitors, which delivers 44.5 kVAr, draws 61.9 A.

Record each step’s current with the step switched in on its own at commissioning, and measure it again at every annual check. Capacitors lose capacitance as they age, and a step drawing noticeably less current than its commissioning figure is a capacitor on its way out, found before it fails rather than after the power factor has drifted and the bill has said so. An unequal current between the three phases of one step points at a single failed element inside it.

Common mistakes

  • Plain capacitors on a harmonic-rich bus.
  • CT placed where it does not see the capacitor current, so the controller cannot see its own correction and over-corrects or hunts.
  • No interlock on generator.
  • Coarse steps that over-correct at light load.

What to send us

Send the electricity bill’s power factor, load recordings and the list of drives and UPS. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Loads, targets and steps are illustrative; site measurements govern.

Questions engineers ask

Why does a capacitor bank deliver less kVAr than its label?

Because a capacitor’s output goes as the square of the voltage across it, and capacitors for harmonic duty are rated above the system voltage. A 50 kVAr unit rated 440 volts delivers about 44.5 kVAr on a 415 volt system, one rated 480 volts about 37.4, and one rated 525 volts about 31.2, more than a third short. Ask for the delivered kVAr per step at 415 volts, and check it with a clamp meter: a step truly delivering 50 kVAr draws 69.6 amps per phase.

Why does my APFC panel keep switching steps in and out?

Usually because its steps are too large for the band it is set to hold. On a 300 kW load at 0.8 power factor needing 126 kVAr to reach 0.95, 50 kVAr steps can only land on 0.923 or 0.970, so a controller with a narrow band around 0.95 toggles between them all day. With 25 kVAr steps it lands on 0.949 and stops. Use smaller trimming steps, widen the band, and never shorten the reconnection delay.

Why do capacitors fail?

Often from harmonics, heat or over-voltage. Harmonic currents overload capacitors and can create resonance with the supply, high ambient temperature shortens their life, and high supply voltage stresses the dielectric. Regular checks of capacitance, current, temperature and contactor condition catch failing units before they swell or burst.

Do I need reactors?

If harmonics are present, usually yes. Detuning reactors in series with the capacitors shift the resonance of the bank below the harmonics present, which protects the capacitors and stops the bank amplifying distortion. The reactor tuning is chosen from a measured harmonic spectrum and the supply transformer data.

Can it run on a generator?

Only with checks and control logic. Capacitors on a lightly loaded generator can push the power factor leading, which the alternator may not tolerate, causing voltage rise or excitation trips. Most sites switch the APFC off or limit its steps on generator supply, using a contact from the changeover to block the controller.

What target pf?

The target is set by the tariff rules and the site, commonly close to unity but without over-correction to a leading power factor. A typical controller target sits slightly lagging, so the bank does not swing leading at light load, and the steps are sized so the controller can hold the target without hunting.

Values are illustrative. Design needs measured data.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.