In short. Selecting a servo stabiliser starts with data, not with the connected load. You need the measured supply range on each phase and the real load including motor starting. From these, choose the phase type, input range, kVA rating, cooling and protection, and confirm that it behaves well on generator supply. A unit sized from nameplates alone is usually either too small for starts or too narrow for the real supply.
Who this page is for: For buyers, consultants and plant engineers selecting and sizing a servo stabiliser.
Key facts
- Record each phase’s voltage for about a week before choosing the input range.
- kVA required = (kW ÷ power factor) × margin.
- At low input voltage the unit’s current rises, so many units are derated at the bottom of their range.
- Check the largest motor start against the stabiliser’s short-time overload rating.
- Choose balanced or independent-phase from how unequal the phases are.
- Check behaviour on generator supply before ordering.
Step by step
- Measure the supply on each phase for a week. See monitoring.
- List the load: running kW, power factor and motor starting current.
- Convert to kVA, apply diversity carefully and add growth.
- Choose phase type. See three-phase stabilisers.
- Choose input range and accuracy. See wide-range units.
- Choose cooling: air or oil.
- Add protection and a bypass.
- Check generator operation. See DG and stabiliser.
Worked example: a small factory (illustrative)
| Step | Working | Result |
|---|---|---|
| Running load | 60 kW at 0.85 power factor | about 71 kVA |
| Margin for growth and ageing | × 1.2 | about 85 kVA |
| Recorded supply | 340 to 440 V | Lowest is 18% below 415 V |
| Derating at low input (from maker’s curve, say 85% output at 340 V) | 85 ÷ 0.85 | 100 kVA rating needed |
| Largest motor: 15 kW direct-on-line, about 6 × 18 kVA running | about 108 kVA starting, on top of about 53 kVA of other running load | about 161 kVA briefly |
| Short-time overload of a 100 kVA unit (say 150% briefly) | 150 kVA | Short; so the motor got a star-delta starter, cutting starting kVA to about a third |
The final choice was a 100 kVA balanced servo stabiliser with a 320 to 460 V input range, giving margin below the recorded 340 V, plus a star-delta starter on the 15 kW motor. Sizing from running load alone would have led to a 75 kVA unit, overloaded at low input and on motor starts.
Do not size a stabiliser from the connected load or the running load alone. Check the derated output at your lowest recorded voltage and the largest motor start against the short-time overload rating.
Selection table
| Data | Decides |
|---|---|
| Voltage minimum and maximum | Input range |
| Phase differences | Balanced or independent |
| Load kVA and starting | Rating and overload |
| Ambient and dust | Cooling and enclosure |
| Generator on site | Frequency window and placement |
Stabiliser sizing sheet
| Item | Value |
|---|---|
| Recorded voltage range per phase | |
| Running kVA with margin | |
| Derating at lowest input | |
| Largest start and overload check | |
| Phase type, cooling, bypass |
Building the load in kVA, group by group
A stabiliser is rated in kVA, and loads are usually listed in kW, so every group of load has to be converted using its own power factor before anything is added up. Converting the total kW with a single assumed power factor hides the groups that matter most: motor loads with a low power factor need far more kVA per kW than lighting or electronics.
| Load group | Running load | Power factor | kVA |
|---|---|---|---|
| LED lighting | 8 kW | 0.95 | 8.4 |
| Air conditioning | 30 kW | 0.85 | 35.3 |
| Production machines | 25 kW | 0.80 | 31.3 |
| Computers and electronics | 6 kW | 0.95 | 6.3 |
| Pumps | 7.5 kW | 0.82 | 9.1 |
| Total | 76.5 kW | 90.4 |
Adding the kVA arithmetically, as here, slightly overstates the total because the groups’ power factors differ, which is a small and safe error. The next two steps are where judgement comes in. Not every group runs at full load at once, so a diversity factor is applied: with 0.8, the 90.4 kVA becomes about 72.3 kVA of likely maximum demand.
Then a margin is added for growth and for the derating many units suffer at the bottom of their input range: with 1.25, the requirement returns to about 90.4 kVA, and the next standard rating, 100 kVA, is the choice. The diversity factor should come from a measurement wherever there is one, as the next section explains, because an assumed 0.8 applied to a site that runs everything at once undersizes the unit by a fifth.
Measured demand is worth more than the connected load
A list of everything connected to a board almost always overstates what the board actually draws. Machines idle, air conditioners cycle on and off, and many loads never run together. A week of recording at the board, with the maximum 10-minute demand in kVA read from the record, replaces assumptions with the real figure. On a typical commercial or light industrial board, the measured maximum is often around half to two-thirds of the connected total, and sizing from the connected load then buys a stabiliser running lightly loaded for its whole life.
The same recording gives the input voltage range per phase that the existing selection steps call for, so one instrument on site for a week answers both sizing questions at once. Two cautions apply. The week must include the busiest operating pattern — a production peak, a hot afternoon with every air conditioner running — or the measured maximum is too low. And the 10-minute maximum does not include motor starting currents, which are checked separately against the stabiliser’s short-time overload rating.
Checking each phase, not just the total
A three-phase stabiliser is rated for a balanced load, and its kVA rating divides equally between the phases. A 100 kVA unit is good for about 33.3 kVA per phase, about 145 A at 230 V. On sites with substantial single-phase load the phases are rarely equal, and the heaviest phase reaches its limit while the total still looks comfortable.
Add the single-phase loads phase by phase from the distribution board schedule or, better, read the three phase currents from the recording, and size so that the heaviest phase stays within its share with margin. If the phases differ widely, rebalancing the single-phase circuits is often easier than buying a larger stabiliser, and it benefits everything else on the supply too.
Checking the largest motor start
A motor started direct on line draws several times its running current for a few seconds, and that current passes through the stabiliser if the motor is on its output. A 15 kW motor at a power factor of about 0.86 and an efficiency of about 0.91 runs at about 27 A; started direct on line at about 6.5 times that, it draws about 173 A for the duration of the start. On a 100 kVA stabiliser rated at about 139 A per phase, that start alone is about 1.25 times the rating, on top of whatever else is running.
Stabilisers have a short-time overload rating, stated as a multiple of rated current for a stated time, and the starting current plus the running load must sit inside it for the whole start. If it does not, the choices are a soft starter or star-delta starter on the motor, a larger stabiliser, or feeding the motor from a branch that does not pass through the stabiliser at all. The last is often the best: most motors tolerate the supply variation that sensitive equipment does not, and keeping their starts off the stabiliser protects both.
One large unit, or several smaller ones
A site with several distribution boards can be stabilised by one large unit at the main board or by smaller units on the boards that need them. The single unit is simpler to house and maintain, but every load passes through it, motor starts included, and when it is bypassed for service the whole site loses its stabilised supply at once.
Several smaller units cost more in total floor space and maintenance visits, but each serves only the loads that need it, each can be serviced without affecting the others, and the boards whose loads tolerate the supply — plant rooms, workshops — need no stabiliser at all. The measured recording usually decides it: where only a few boards carry sensitive load, stabilising those boards alone gives a smaller total rating and a more resilient arrangement.
Where it will stand: temperature, enclosure and altitude
A stabiliser’s rating assumes a stated maximum ambient temperature, often 40 or 45 degrees, with free air around it. Many sites in this region exceed that in summer in an unventilated electrical room, and outdoor units in sun-facing kiosks run far hotter. Above the rated ambient, the maker’s derating applies, and it should be asked for in writing.
An enclosure chosen for dust or water protection traps heat and may need a larger unit or forced ventilation. Sites at altitude, where the thinner air cools less effectively, also need the maker’s derating. None of this changes the electrical calculation above; all of it can change the rating that has to be bought to deliver it.
Remember that the stabiliser heats its own room. A 100 kVA unit losing 2 to 3% of what it carries puts a couple of kilowatts into the space continuously, and in a small, closed electrical room that alone can lift the temperature above the rated ambient by mid-afternoon. Plan the ventilation for the stabiliser’s losses and every other heat source in the room together, and check the room temperature on a hot afternoon after installation, not only on the day of commissioning.
What to write in the enquiry
Most stabiliser problems trace back to an enquiry that gave only a kVA figure. A short specification, sent to every supplier in the same form, makes the offers comparable and puts the important decisions on paper.
| Item | What to state | Why |
|---|---|---|
| Rating | kVA, and the heaviest phase’s kVA | Balanced rating is not the same as per-phase capacity |
| Input range | Per phase, from the recording, with margin | Sets the size, weight and input current |
| Output | Set voltage and accuracy band | Decides how closely the load is held |
| Correction rate | Volts per second | Matched to how the supply actually moves |
| Protection | Output cut-off levels, delay and restart | Decides what the load sees when the unit cannot cope |
| Short-time overload | Current and duration | Checked against the largest motor start |
| Bypass | Manual or automatic, interlocked | Allows service without a shutdown |
| Environment | Ambient maximum, enclosure, indoor or outdoor | Brings the derating into the offer |
| Testing | Factory test certificate with per-phase results | The evidence that the unit meets the above |
Ask every supplier to confirm each line, or state where their offer differs. Offers that answer the table can be compared on substance; offers that answer only the kVA cannot.
Common mistakes
- Sizing from the connected load.
- Ignoring low-input derating.
- No motor-start check.
- Input range chosen from the brochure, not the recording.
What to send us
Send voltage recordings, the load list with motors and starting methods, and site conditions. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. Derating and overload values are illustrative; makers’ curves govern.
Questions engineers ask
Should a stabiliser be sized from the connected load or the measured demand?
From the measured demand wherever possible. A week of recording at the board gives the maximum 10-minute demand in kVA, which on many sites is around half to two-thirds of the connected total. Convert each load group with its own power factor, apply a diversity factor taken from the measurement, add a margin of about a quarter for growth and low-voltage derating, and choose the next standard rating. Check the heaviest phase and the largest motor start separately.
Can a motor be started through a servo stabiliser?
Only if the starting current plus the running load stays inside the stabiliser short-time overload rating for the whole start. A 15 kW motor started direct on line draws about 173 amps, about 1.25 times the rating of a 100 kVA unit on its own. Use a soft starter or star-delta starter, choose a larger unit, or better still feed the motor from a branch that does not pass through the stabiliser at all.
Can I size from the breaker rating?
No. A breaker is sized for cable protection and future margin, not for the real load, so sizing from it usually oversizes the stabiliser. Use the measured maximum demand from a load logger over a normal operating week, add the largest motor start and planned additions, and size from that figure.
How much growth margin?
Base the margin on the site plan: loads that are confirmed for the next few years, plus a modest allowance for change. Large oversizing raises cost and can reduce accuracy and efficiency at light load, while a stabiliser that runs near its rating all day runs hot, so both extremes are avoided.
Do I need a bypass?
For continuous operations, yes. A bypass lets the load stay supplied, directly from the incoming supply, while the stabiliser is serviced or repaired, and avoids a full shutdown for maintenance. Make it interlocked so that the stabiliser output and the bypass can never be connected together.
What about harmonic loads?
Check the neutral and thermal rating. Nonlinear loads such as drives, computers and LED lighting draw harmonic currents that heat the stabiliser transformer more than the same kVA of linear load, and triple harmonics add up in the neutral. Measure the harmonic spectrum and ask the maker for a suitable rating. See harmonics.
Values are illustrative. Use measured data and maker ratings.