In short. Three-phase servo stabilisers come in two types. Balanced-load units move all three phases together under one control. Independent-phase units regulate each phase separately. The right one depends on how unevenly the phases are loaded and how much the incoming phase voltages differ. Sizing, the neutral and protection must then be chosen for the actual plant, not a typical one.
Who this page is for: For plant engineers, building managers and buyers choosing a three-phase stabiliser.
Key facts
- Balanced-load type: one control moves all three phases; best for three-phase motor loads.
- Independent-phase type: each phase regulated on its own; best for mixed single-phase loads and unequal phase voltages.
- kVA = √3 × V × I ÷ 1000.
- For independent-phase units, the highest phase current sets the module size.
- Keep a solid neutral through the stabiliser and earth it properly.
- Decide from a week’s recording of phase voltages and currents.
Design types
| Type | How it works | Suits |
|---|---|---|
| Balanced-load | One control moves all three phases together | Balanced loads such as motors. See balanced-load |
| Independent-phase | Each phase regulated separately | Unbalanced loads, unequal phase voltages. See independent-phase |
Worked example: choosing the type from a recording (illustrative)
| Site | Phase voltages (L-N, evening) | Phase currents | Choice |
|---|---|---|---|
| Factory, mainly three-phase motors | 212, 214, 211 V | 140, 138, 142 A | Balanced-load; phases move together |
| Hospital wing, many single-phase loads | 205, 226, 214 V | 120, 70, 95 A | Independent-phase; sized on the 120 A phase |
For the factory: kVA = 1.732 × 415 × 142 ÷ 1000 ≈ 102 kVA running, so with margin and motor starts a 125 kVA balanced unit. For the hospital wing, a balanced unit would leave one phase low and another high, so each phase module was sized on the 120 A phase plus surges.
Do not choose a balanced-load stabiliser for a site where phase voltages differ by more than a few volts or single-phase loads dominate. It will correct the average and leave individual phases wrong.
Neutral and earthing
Keep a solid neutral through the stabiliser and earth it properly. With independent-phase units the neutral may carry significant unbalance and harmonic current; size it accordingly. Where a generator changeover switches the neutral, check the stabiliser’s neutral reference on both sources.
Type selection sheet
| Phase | Voltage range | Current | Single-phase loads? |
|---|---|---|---|
| R | |||
| Y | |||
| B |
Input current rises as the supply voltage falls
A servo stabiliser is rated by what it delivers, not by what it draws. Its output is held at 415 V, so its output current is fixed by the load: a 100 kVA unit at full load delivers 139.1 A per phase whatever the supply is doing. The input is a different matter.
To deliver the same power from a lower voltage, the stabiliser must draw more current, and it must also draw its own losses. The input side — the incoming cable, the input breaker, the upstream fuse and the transformer or generator feeding it — therefore has to be sized for the lowest voltage the stabiliser is expected to correct from, not for the nameplate output.
| Supply voltage (line to line) | Input current, 100 kVA output at 97% efficiency | Compared with the output current of 139.1 A |
|---|---|---|
| 460 V | 129.4 A | Below it: the stabiliser is bucking |
| 415 V | 143.4 A | Slightly above it, by the losses alone |
| 380 V | 156.6 A | About an eighth above it |
| 360 V | 165.3 A | About a fifth above it |
| 340 V | 175.1 A | More than a quarter above it |
The lesson is a simple one that is often missed. A stabiliser chosen because the supply sags to 340 V will spend its hardest hours drawing 175 A, and an input breaker set at 160 A on the strength of the 139 A output rating will trip at exactly the moment the stabiliser is most needed. Size the input cable and protection for the bottom of the correction range, check the volt drop in that cable at that current, and remember that the volt drop in the incoming cable is itself a voltage the stabiliser then has to correct.
Why the correction range sets the size and weight
A servo stabiliser does not pass the whole load through a regulating transformer. A motor-driven variable transformer sets a small voltage, and a buck-boost transformer adds that voltage to the supply or takes it away. The buck-boost transformer carries the full load current, but only at the correction voltage, so its rating is a fraction of the load. On a 100 kVA unit correcting from 340 V up to 415 V, the largest boost is 75 V between lines, about 43 V per phase, and the series winding is worth about 18 kVA. Widen the range to start from 300 V and the boost becomes 115 V, and the same winding has to be worth about 28 kVA.
That is why a wide-range unit is physically larger and heavier, and takes more copper and iron to build, than a narrow-range unit of the same output, and why asking for a wider range “to be safe” is not free. It also explains why a wide-range unit run near the bottom of its range draws the high input currents in the table above. The range should be chosen from a recording of the actual supply over at least a week, with a modest margin beyond the worst value seen, rather than from a catalogue default.
The buck-boost arrangement also explains the value of a bypass switch. Because the series winding sits in the load path, the stabiliser cannot be serviced with the load on it unless there is a way round it. A three-position switch — stabiliser, bypass, off — or a pair of interlocked breakers lets the load be fed directly from the supply while the brush, the track or the control card is attended to. Without one, every service visit becomes a shutdown, and shutdowns that are hard to arrange are how maintenance gets postponed until the unit fails. Specify the bypass at the outset; adding it later means rewiring the panel.
Correction speed, and what it means for a dip
A servo corrects by moving a carbon brush or roller along a winding with a motor, so it corrects at a rate, usually quoted in volts per second. It is not instantaneous and is not meant to be. A slow change of supply voltage over minutes — the evening load building on a rural feeder — is exactly what it does well. A sudden step is corrected over a second or more, during which the load sees part of the step.
| Correction rate | Time to correct a 40 V step | Time to correct a 60 V step |
|---|---|---|
| 10 V per second | 4 seconds | 6 seconds |
| 20 V per second | 2 seconds | 3 seconds |
| 40 V per second | 1 second | 1.5 seconds |
Two consequences follow. First, a servo stabiliser does nothing for a dip that lasts less than a second, such as the dip when a large motor starts on the same supply; that needs a starting method or a stiffer supply, not a faster stabiliser. Second, a faster servo is not automatically better. A unit set to chase every flicker wears its brush track and motor faster, and on a generator it can start reacting to the generator’s own regulator. The rate should suit how the supply actually moves, and the stabiliser’s test certificate should state the rate it was set to.
Output protection: the cut-off settings that decide what the load sees
Every three-phase servo stabiliser should be able to disconnect its output when it cannot hold the voltage, and the settings of that cut-off decide whether it protects the load or merely watches it. Typical settings are an output trip at about 10% above and below the set voltage — 457 V and 374 V on a 415 V output — with a short time delay, so that a passing disturbance does not drop the load but a sustained excursion does. The same relay usually covers single phasing and phase reversal on the input.
The settings deserve as much attention as the rating. A cut-off disabled during commissioning “because it kept tripping” turns the stabiliser into a source of overvoltage the day its control fails at the top of its travel. A cut-off with no time delay drops the load on every motor start. Record the trip voltages, the delay, and whether the unit restarts automatically or waits for a reset, and test them by raising and lowering the input on a variable supply at commissioning rather than trusting the factory figures.
Losses, heat and where the stabiliser stands
A well-built air-cooled servo stabiliser is around 97 to 98% efficient at full load, which sounds negligible until it is turned into heat. A 100 kVA unit carrying 80 kW at a power factor of 0.8 loses about 2.5 kW at 97% and about 1.6 kW at 98%, continuously, into the room it stands in. Removing 2.5 kW with a 10 degree temperature rise takes about 780 m³ of air an hour; in a small electrical room with no ventilation the stabiliser simply warms the room until its own windings and the panels beside it run hot.
Give the unit the clearances its maker asks for, front and back, keep it out of direct sun and away from the heat of a generator room, and keep its air paths free of dust, because the brush track and the motor drive are the parts that suffer first. A stabiliser that is cleaned, inspected and has its brush and track checked on a schedule will run for many years; one left in a dusty corner tends to fail at the brush, at the worst possible voltage.
What to check when the stabiliser is delivered
Most of what decides whether a three-phase stabiliser will serve well can be checked on the day it arrives, before any load is connected. The test certificate should show, for each phase, the input range over which the output was held, the output accuracy, the correction rate and the cut-off settings.
On site, measure all three output voltages with the input at its normal value, check that the neutral is continuous from the supply through to the load and is not switched separately from the phases unless the design calls for it, and confirm that the earth is bonded to the frame. Run the unit on light load for an hour and listen to the servo motor: a unit that moves constantly with a steady supply is set too tight, and one that never moves when the supply drifts is not regulating at all.
Common mistakes
- Balanced type on an unbalanced site.
- Independent type sized on average current.
- Neutral undersized.
- No recording before choosing.
What to send us
Send per-phase voltage and current recordings and the load list. WhatsApp 98852 01608 or use the application engineering enquiry. See selection and sizing.
Evidence note. Readings are illustrative; site recordings govern.
Questions engineers ask
Why does the stabiliser input breaker trip when the supply voltage is low?
Because a stabiliser draws more input current as its supply voltage falls. It holds 415 volts at the output, so to deliver the same power from a lower voltage it must draw more current, plus its own losses. A 100 kVA unit delivering 139.1 amps draws about 175 amps at 340 volts. An input breaker chosen from the output rating trips at the moment the stabiliser is most needed. Size the input cable and protection for the bottom of the correction range.
How fast should a servo stabiliser correct the voltage?
Fast enough to follow how the supply actually moves, and no faster. A servo corrects at a rate in volts per second, so at 20 volts per second a 40 volt step takes about 2 seconds. It suits slow changes over minutes and does nothing for dips shorter than a second, such as a motor start. A unit set too fast wears its brush track and can interact with a generator regulator. Choose the rate from a recording of the supply and have it stated on the test certificate.
Can I use single-phase units on three phases?
Three single-phase units can be used in some arrangements, one on each phase with a common neutral, which gives independent correction of each phase. Check the wiring, the neutral current and its conductor size, and the protection, and confirm the arrangement with the maker so the three units behave as one system.
What if the load is unbalanced?
Use independent-phase regulation, in which each phase has its own sensing and correcting mechanism. A balanced-type three-phase stabiliser corrects all phases by the same amount, so with unbalanced loads or unbalanced supply voltages one phase can end up high and another low even though the average looks correct.
Does it correct phase sequence?
No. A stabiliser corrects voltage magnitude and does not change the phase sequence. Its protection can include a phase sequence relay that blocks the output when the sequence is wrong, which protects motors from running in reverse after supply or cable work. Check the sequence after any change to the incoming connection.
What about harmonics?
A stabiliser does not remove harmonics; it corrects the voltage level only, and heavy harmonic currents can even add heating in its transformer. Harmonics are reduced by filters, line reactors or drives with low distortion, chosen from a measurement of the harmonic spectrum at site. See harmonic mitigation.
Values are illustrative. Use manufacturer ratings.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.