In short. An industrial servo stabiliser is built for continuous duty on harsh supplies. It needs enough kVA with margin for motor starts, an input range that covers the worst recorded voltages, cooling suited to the site, protection against overload and phase problems, a bypass so maintenance does not stop the plant, and monitoring. Selection should follow measured supply and load data, not the connected load.
Who this page is for: For plant managers, maintenance engineers and consultants specifying stabilisers for factories and process plants.
Key facts
- Continuous-duty rating with thermal margin; plants run long hours.
- Input range from the worst measured low and high voltages, plus margin.
- Short-time overload capability for motor starts and inrush.
- Cooling (air or oil) chosen for ambient temperature, dust and humidity.
- Protection: overvoltage and undervoltage, overload, phase failure, thermal, short circuit.
- A bypass lets the unit be serviced without shutting the plant.
Key requirements
| Requirement | Why |
|---|---|
| Continuous duty rating | Long running hours need thermal margin |
| Input range | Must cover the worst recorded low and high voltages |
| Overload capability | Motor starts and inrush loads |
| Cooling method | Ambient, dust and humidity. See air-cooled and oil-cooled |
| Protections | Voltage limits, overload, phase failure, thermal, short circuit |
| Bypass | Maintenance without a plant shutdown |
| Monitoring | Voltage, current, alarms, remote interface |
Worked example: a plastics plant (illustrative)
| Step | Working | Result |
|---|---|---|
| Running load | 210 kW at 0.86 power factor | about 244 kVA |
| Growth and continuous-duty margin | × 1.2 | about 293 kVA |
| Recorded supply | 345 to 445 V | Range specified 320 to 470 V |
| Largest motor (55 kW, star-delta) | Start about 2.5 × 70 kVA running | about 175 kVA briefly; with the other running load about 349 kVA (about 116% of 300 kVA) |
| Ambient | Up to 42 °C, plastic dust | Oil-cooled, sealed windings |
| Choice | 300 kVA oil-cooled servo stabiliser with bypass, checked against its short-time overload for the 55 kW start, and remote alarms | |
The plant’s earlier air-cooled unit, sized at 250 kVA with no margin for motor starts or summer derating, had tripped on temperature every summer and could not be serviced without stopping production.
Plan maintenance access before the stabiliser is installed. Where the plant cannot stop for stabiliser service, a bypass is usually the answer, with its type, rating, transfer method and interlocks chosen for the application. Without a planned route, every service visit or fault means a plant shutdown, and the pressure to skip maintenance grows until the unit fails at a worse time.
Installation points
- Ventilation and clearance as the maker specifies.
- Upstream cable and protection sized for current at the lowest input voltage.
- Correct earthing and neutral arrangement.
- Location away from dust and moisture where possible.
- Check behaviour on generator supply. See DG and stabiliser.
Industrial stabiliser specification
| Item | Value |
|---|---|
| Running kVA with margin | |
| Recorded and specified input range | |
| Largest motor start and overload check | |
| Cooling and enclosure | |
| Bypass and monitoring |
Choosing the bypass arrangement
A bypass lets the load be fed directly from the incoming supply while the stabiliser is isolated, so the plant keeps running during service or a fault. Its design depends on the application, and four choices are made deliberately:
- Type: a manual rotary or changeover switch is common; a motorised or contactor bypass is used where the transfer is automatic on a stabiliser fault.
- Transfer method: a make-before-break transfer avoids an interruption but must be interlocked so that it only operates when the stabiliser output and the input are close in voltage; a break-before-make transfer gives a short interruption that some loads cannot tolerate.
- Rating: the bypass carries the full load current, at the lowest input voltage, and the fault level at that point.
- Interlocks and isolation: the stabiliser must be isolated on both its input and output before work starts, with means to lock off and prove it dead.
While on bypass the load receives the unregulated supply. The procedure therefore states when bypass may be used, for example during the day when the input voltage is within the range the load can accept, and who authorises it. For a plant that can stop for a planned stabiliser service, a separate isolating arrangement without an automatic bypass may be all that is needed.
Current at low input voltage
A stabiliser delivers its output power from the input, so when the input voltage falls the input current rises. In the worked example, 293 kVA at 345 V line-to-line draws about 293000 ÷ (1.732 × 345), or about 490 A, compared with about 408 A at 415 V. The upstream cable, breaker and the stabiliser input winding are sized for the current at the lowest specified input voltage, not at nominal, otherwise the breaker trips or the cable overheats precisely when the supply is weakest.
Correction speed and the generator
A servo stabiliser corrects by moving a brush or roller along a variable transformer, so its response is measured in volts per second. A unit that corrects too slowly leaves a dip at the output after a motor start; one that corrects too fast can hunt against the voltage regulator of a generator after a load step. The correction rate is stated in the specification, and the combination of stabiliser and generator is tested on load with the largest motor start, recording the output voltage during the event.
Duty, ambient and derating
Continuous duty in a hot plant is the condition that most often defeats an undersized unit. The rating is stated at a reference ambient, commonly 40 or 45 °C, and the maker gives a derating above it. Dust that blocks air paths reduces cooling further, which is why the plastics plant in the example chose an oil-cooled design with sealed windings. The stabiliser room or enclosure is kept within the stated ambient, with filtered ventilation where the air is dusty.
Maintenance schedule (typical)
| Interval | Task |
|---|---|
| Monthly | Check alarms and the controller log; check input and output voltages against a reference meter |
| Quarterly | Clean air paths and filters; inspect cable terminations for heating |
| Half-yearly | Inspect brushes or rollers and the transformer track; check servo motor, gears and limit switches |
| Yearly | Insulation resistance; protection trip tests; oil condition on oil-cooled units; full-range regulation test |
The intervals are adjusted to the maker instructions and to the hours and conditions of the site. Each visit uses the bypass or a planned stop, which is why maintenance access is designed in from the start.
Acceptance tests at installation
- Insulation resistance of the stabiliser and its cables before energising.
- Output voltage held within the stated band as the input is varied across the specified range, where a variable supply or the site supply allows.
- Protection trips proved: overvoltage, undervoltage, overload, phase failure and over-temperature.
- Bypass operation with its interlocks, under load where the procedure allows.
- Largest motor start on the stabiliser output, with the output voltage recorded.
- Full-load run long enough to reach stable temperatures, with readings recorded.
Monitoring and alarms
An industrial unit should report its state rather than wait to be noticed. The minimum is a volt-free alarm contact for any trip, connected to the plant control room. Better is a monitoring interface that logs input and output voltages, load current, temperature and every trip with its time, so a pattern such as evening overloads or summer temperature trips is seen before it becomes a stoppage.
Specification checklist for an enquiry
| Item | State in the specification |
|---|---|
| Rating | Continuous output kVA at the stated ambient, with derating above it |
| Input range | Lowest and highest line-to-line voltage at which full output is delivered |
| Output accuracy | Band around the set voltage, and whether it applies per phase or to the average |
| Correction rate | Volts per second, and behaviour on generator supply |
| Short-time overload | Percentage and duration, checked against the largest motor start |
| Control type | Balanced-load or independent-phase, from the recorded phase voltages |
| Cooling and enclosure | Air or oil, enclosure protection degree for dust and moisture |
| Protection | Output overvoltage and undervoltage, overload, phase failure, over-temperature, short circuit |
| Bypass and isolation | Type, transfer method, rating and interlocks |
| Monitoring | Alarm contacts and data interface |
Two offers that both say 300 kVA can differ widely on these points. Comparing them line by line against the specification is what makes the offers comparable.
Common causes of failure in service
- Overheating from continuous operation above the derated rating in summer, often because the unit was sized on connected load at nominal voltage.
- Worn or burnt brush tracks from years of operation on one part of the range, showing as output voltage jumps.
- Servo motor or gear failure that leaves the output stuck, which the output overvoltage and undervoltage trips must catch.
- Loose terminations that heat at the higher input current during low-voltage periods.
- Dust blocking air paths, raising winding temperature until the thermal trip operates.
Most of these are found early by the monthly and half-yearly checks in the schedule above, and by watching the trip log for patterns rather than resetting trips one at a time.
Location and installation details
The stabiliser is placed close to the load it serves where possible, so the corrected voltage is not lost again in a long output cable. It stands on a level, non-combustible base with the clearances the maker states for cooling and for opening covers during maintenance. Oil-cooled units need a bund or drip tray sized for their oil volume and a location away from drains.
Input and output cables enter from the sides or base the maker intends, glanded to keep dust out, and the earthing and neutral connections follow the earthing arrangement of the installation, with the neutral carried through where single-phase loads are fed. A clear label at the bypass and isolators shows the switching positions and the procedure reference, so a person attending a fault at night operates them correctly.
Before handover the as-installed drawing, the settings sheet, the acceptance test record and the maintenance schedule are placed in the site file, together with the bypass procedure.
Common mistakes
- Sizing from connected load.
- No bypass.
- Air-cooled unit in a hot, dusty plant without derating.
- No alarms, so faults are found by the production line.
What to send us
Send supply recordings, the motor list with starting methods and the site conditions. WhatsApp 98852 01608 or use the application engineering enquiry. See selection and sizing.
Evidence note. Loads and margins are illustrative; makers’ data govern.
Questions engineers ask
Why must the input cable be sized at the lowest input voltage?
Because the stabiliser takes its output power from the input, so the input current rises as the input voltage falls. A 293 kVA load draws about 408 A at 415 V but about 490 A at 345 V. Cable, breaker and input winding sized only for nominal voltage overheat or trip when the supply is weakest.
What should a stabiliser bypass include?
A transfer switch rated for full load at the lowest input voltage and the fault level, a transfer method that suits the load, interlocks that prevent unsafe switching, and isolation of the stabiliser input and output with lock-off for maintenance. A written procedure says when bypass may be used and who authorises it.
How much kVA margin?
Base it on measured demand rather than connected load: the running kVA at the corrected output voltage, a margin for growth and continuous duty of about 20%, a check of the largest motor start against the short-time overload rating, and derating for ambient temperature above the reference. The worked example on this page shows each step.
Do I need a bypass?
Where the plant cannot stop for stabiliser service or a stabiliser fault, a bypass is usually the right choice, with its type, rating, transfer method and interlocks chosen for the application. Where planned stops are acceptable, isolation without an automatic bypass may be enough. Decide it at design stage, because adding a bypass later costs more.
Is air cooling enough?
For many sites, yes, where the unit room stays within the rated ambient and the air is reasonably clean. Hot, dusty or humid plants often need oil cooling with sealed windings, or air-cooled units derated for the conditions with filtered ventilation. The maker states the reference ambient and the derating above it.
How long do they last?
With good maintenance, many years. The variable transformer and windings last longest; brushes or rollers, the servo motor, gears and contactors are wear parts replaced as they wear. Keeping the unit within its thermal rating, cleaning air paths and inspecting the brush track on schedule are what extend its life most.
Values are illustrative. Follow manufacturer ratings.