In short. Harmonics are currents and voltages at multiples of the supply frequency, drawn by non-linear loads such as drives, UPS rectifiers and LED drivers. They heat transformers, cables and neutrals, distort the voltage and upset generators, which are more sensitive than the grid. Measure the spectrum first, then mitigate with reactors, filters or better equipment choices.
Who this page is for: For plant and facility engineers with drives, UPS or LED loads seeing heating, nuisance trips or generator voltage distortion.
Key facts
- Non-linear current flowing through source impedance creates voltage distortion.
- A generator has several times the source impedance of a typical grid supply, so the same load distorts it more.
- Triplen harmonics (3rd, 9th, 15th) add in the neutral instead of cancelling.
- Capacitors can resonate with system inductance at a harmonic frequency.
- Line reactors or DC chokes are the cheapest first step on drives.
- Measure current and voltage distortion and the spectrum before choosing a filter.
Sources and effects
| Equipment | Effect |
|---|---|
| Transformers | Extra heating; derate or use a K-rated design |
| Neutrals | Triplen currents add; neutral can carry more than phase current |
| Capacitors | Resonance risk. See APFC |
| Generators | Voltage distortion and extra rotor heating |
| Electronics | Mis-operation and trips |
Worked example: the same drives on grid and generator (illustrative)
A plant runs 300 kW of six-pulse drives drawing about 80% current distortion. Voltage distortion depends on the source impedance at the harmonic frequencies.
| Source | Relative impedance | Voltage distortion measured |
|---|---|---|
| Grid through a 1000 kVA transformer | Low | about 4% |
| 500 kVA generator alone | Several times higher | about 14%; controllers misbehaved |
| Generator, after line reactors on the drives | Same | about 7%; current distortion down to about 40% |
| Generator, reactors plus an active filter | Same | about 3% |
The plant was fine on the grid and failed on generator. Reactors were cheap and halved the problem; the filter finished it. See non-linear loads on generators.
Do not add power factor capacitors to a plant with heavy harmonics without a check for resonance. Plain capacitors can amplify a harmonic and fail, or trip the plant. Use detuned reactors where harmonics exist.
Mitigation options
| Option | Best for |
|---|---|
| Line reactors or DC chokes | First step on drives; low cost |
| Passive tuned filters | Steady loads with a dominant harmonic |
| Active harmonic filters | Varying loads and spectra |
| Multi-pulse or active-front-end rectifiers | New drives and UPS |
| Oversizing the source | Generators that must carry heavy non-linear loads |
See harmonic studies.
Measure
Record current and voltage distortion and the spectrum at the main board, at large non-linear loads, and on generator supply, over a full operating cycle. See monitoring.
Harmonic survey sheet
| Point | Current distortion | Voltage distortion | Dominant harmonics |
|---|---|---|---|
| Main board on grid | |||
| Main board on generator | |||
| Largest non-linear load |
THD or TDD: why the percentage can mislead
Harmonic current is usually reported as total harmonic distortion, THD, which expresses the harmonic current as a percentage of the fundamental current flowing at that moment. That makes it a poor measure of how much harm the harmonics are doing, because at light load the fundamental is small and even a little harmonic current looks like a large percentage. Total demand distortion, TDD, divides the same harmonic current by the site’s maximum demand current instead, so it rises and falls with the harmonic amps that actually heat cables and distort the voltage.
| Operating point | Fundamental current | Harmonic current | THD | TDD, on a 200 A maximum demand |
|---|---|---|---|---|
| Light load | 40 A | 18 A | 45% | 9% |
| Half load | 100 A | 32 A | 32% | 16% |
| Full load | 180 A | 50 A | 28% | 25% |
The two measures point in opposite directions. THD is worst at light load, when the harmonics are doing least; TDD is worst at full load, when they are doing most. A survey that reports only THD, taken on a quiet afternoon, can raise an alarm about a problem that does not exist and miss the one that does. Record the harmonic current in amps as well as in percent, note the load at the time of each reading, and judge the result against the maximum demand.
The harmonic amps also have to be added to the cable and breaker loading. Current adds by root sum of squares, so the full-load case above draws about 186.8 A in total although its fundamental is 180 A, and the higher harmonics heat a conductor more than their share because of skin effect. On a busbar or cable sized close to its limit, that difference is the margin. Use the measured RMS current, from a true-RMS meter, when checking cable and breaker loading on any feeder with drives or electronic load; an average-reading meter on a distorted current can read low by a fifth or more.
The limits the industry works to
The most widely used framework for harmonic limits, IEEE 519, sets them at the point where a site connects to the supply, and it sets them in two parts. Voltage distortion is limited by the system voltage: on systems up to 1 kV, each individual harmonic voltage should stay within 5% and the total within 8%. Current distortion is limited by how stiff the supply is compared with the site’s load, measured as the ratio of the short-circuit current to the maximum demand current, Isc/IL.
| Isc/IL at the connection point | Total demand distortion limit |
|---|---|
| Below 20 | 5% |
| 20 to 50 | 8% |
| 50 to 100 | 12% |
| 100 to 1000 | 15% |
| Above 1000 | 20% |
The logic is fair: a site on a weak supply, where its own harmonic current would distort the voltage for its neighbours, is allowed less. A site fed from a 1000 kVA transformer of 5% impedance has a short-circuit current at 415 V of about 27.8 kA. With a maximum demand of 1000 A the ratio is about 28, which falls in the 20 to 50 band and allows a total demand distortion of 8%.
The same site with a maximum demand of 250 A has a ratio of about 111 and is allowed 15%. A generator, with a short-circuit current several times smaller than the transformer’s, is a weak source by this measure, which is the reason the same load distorts the voltage so much more on generator.
What the drive’s front end decides
On most industrial sites the harmonic current comes from variable-speed drives, and the single most important fact about each drive is what sits at its input. The same motor and the same load can draw a current with a distortion of around 90% or under 5%, depending entirely on the front end that was specified.
| Drive input | Typical current distortion at full load | Comment |
|---|---|---|
| Six-pulse rectifier, no choke | 80% to 100% or more | Found on small drives; the worst case |
| Six-pulse with an AC line reactor or DC choke | 30% to 45% | The common standard; a large improvement for a small choke |
| Twelve-pulse, with a phase-shifting transformer | 10% to 15% | Large drives; depends on the transformer and supply balance |
| Eighteen-pulse | 5% to 8% | Large drives where a filter is not wanted |
| Active front end | Below 5% | Clean at the source; also allows energy to be returned |
The best time to deal with harmonics is when the drives are ordered. Asking for a choke on every drive, or an active front end on the largest, often removes the need for a separate filter altogether, and removes it on both the mains and the generator. Once the drives are installed, the same result takes a filter, panel space and a second set of losses.
Mixing front ends on one supply has a useful side effect. Drives with and without chokes, or with different transformer connections, produce harmonics that partly cancel each other, so the total at the main board is usually less than the sum of the individual drives. That is a reason to measure at the main board before sizing any filter, not to add the catalogue figures of every drive together.
Third harmonics and the neutral conductor
Single-phase electronic loads — computers, LED drivers, small chargers — draw current in short pulses rich in the third harmonic. In a balanced three-phase system the fundamental currents of the three phases cancel in the neutral, but the third harmonics do not: they are in step with each other and add. The neutral therefore carries three times the third-harmonic current of each phase, and can carry more current than any phase conductor.
A worked case shows the size of it. Three phases each carry 100 A of electronic load, of which the third harmonic is half the fundamental: about 89 A of fundamental and 45 A of third harmonic per phase. The neutral carries three times 45 A, about 134 A, a third more than any phase. With loads dominated by small power supplies the neutral can approach 1.7 times the phase current.
A neutral sized at half the phase conductor, as was once common, is then overloaded with no breaker to notice, because neutrals are rarely protected. On such sites the neutral should be at least the full size of the phase conductors, and on heavily electronic distribution boards it is often specified larger.
The third harmonics do not pass on beyond a delta-star transformer; they circulate in its delta winding and heat it instead. A transformer or generator feeding a large electronic load should be checked for that heating too, and a generator’s neutral and its alternator winding pitch affect how it responds, which is a matter for the alternator’s maker.
Sizing an active filter in amps
An active filter is sized by the harmonic current it has to supply, in amps, not by the kVA of the load or by a percentage. The required current is the harmonic content of the load current: for a load drawing 300 A of fundamental at a current distortion of 40%, that is about 120 A. Reducing the distortion to 5% rather than to zero barely changes it, to about 119 A, because the residual distortion combines with the original as a root of the difference of squares, not as a simple subtraction. With a margin of a quarter for growth and measurement uncertainty, a 150 A filter is the sensible choice.
The figure should come from a measurement at the busiest time, in amps, at the point where the filter will connect, and the filter’s current transformers must see the load it is to correct and not the filter’s own output. A filter connected where it sees both the load and the capacitor bank of an APFC panel must be co-ordinated with it, or the two will work against each other. Measure again after commissioning, at the same point and the same load, and keep both results: the comparison is the only proof that the filter is doing what it was bought to do.
Common mistakes
- Testing on grid only and assuming generator behaviour is the same.
- Plain capacitors on a harmonic-rich bus.
- Neutral sized at half the phase conductor with many single-phase electronic loads.
- Buying a filter before measuring.
What to send us
Send recordings, the drive and UPS list and the generator rating. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. Distortion figures are illustrative; site measurements and studies govern.
Questions engineers ask
What is the difference between THD and TDD?
Total harmonic distortion divides the harmonic current by the fundamental current flowing at that moment, so it looks worst at light load when the harmonics matter least. Total demand distortion divides the same harmonic current by the maximum demand current, so it rises with the harmonic amps that actually heat cables and distort voltage. A drive at light load can show 45% THD but only 9% TDD. Judge harmonic limits against TDD and record the harmonic current in amps.
Why is the neutral carrying more current than the phases?
Because third-harmonic currents from single-phase electronic loads add in the neutral instead of cancelling. With 100 amps per phase of electronic load and a third harmonic half the size of the fundamental, the neutral carries about 134 amps, a third more than any phase. With loads dominated by small power supplies it can approach 1.7 times the phase current. Size the neutral at least equal to the phase conductors on such circuits and measure it with a true RMS meter.
Is THD always bad?
Not always. High voltage distortion at a weak source, such as a small transformer or a generator, can overheat motors and capacitors and upset electronics, while a modest current distortion at a stiff source may cause no harm. Judge it by measured voltage and current distortion at the point of connection, against the applicable limits.
Do stabilisers fix it?
No. A stabiliser corrects the voltage level and does nothing to remove harmonic currents; heavy harmonics can even add heating in its own transformer. Harmonics are reduced by line reactors, drives with low distortion, passive or active filters, or by changing the arrangement of the loads, chosen from a measured spectrum.
Why is a generator more sensitive?
Because a generator has a higher source impedance than a grid transformer, the same harmonic currents produce a larger voltage distortion at its terminals. That distortion affects every load on the set, can upset the AVR sensing and heats the alternator, so drive-heavy loads are checked against the alternator data before connection.
Passive or active filter?
It depends on the spectrum, how much it changes with load and the budget, so study it first. A passive filter is tuned to particular harmonics and suits a steady load, while an active filter adapts to a changing spectrum but costs more. On generator supply, the leading power factor of a passive filter at light load is also checked.
Values are illustrative. Follow applicable standards.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.