In short. Surge protective devices (SPDs) divert transient overvoltages to earth and clamp them to a level the equipment can survive. Protection works in layers: at the service entry, at distribution boards and at the sensitive load. Two installation details decide whether it works at all: short connecting leads and a low-impedance earth. SPDs wear with each surge and need checking.
Who this page is for: For electrical engineers, facility managers and contractors protecting drives, controllers, generator panels and electronics against lightning and switching surges.
Key facts
- Surges come from lightning, utility switching, large internal loads and transfer events.
- Layered SPDs share the energy: the entry device takes the bulk, downstream devices lower the residual voltage.
- Every metre of connecting lead adds roughly 1 kV of extra voltage during a fast surge.
- Voltage protection level plus the lead voltage must stay below what the equipment withstands, with margin.
- SPDs degrade with use; check indicators and replace after major events.
- SPDs do not fix sustained overvoltage, outages or harmonics.
Layered protection
| Location | Role |
|---|---|
| Service entry or main board | Handles the largest surge energy |
| Sub-distribution boards | Lowers the residual voltage further |
| At sensitive loads | Final clamping close to the equipment |
Understanding SPD ratings
| Rating | Meaning |
|---|---|
| Maximum continuous operating voltage | Highest steady voltage the device tolerates without conducting; must exceed the highest normal supply voltage |
| Voltage protection level | Residual voltage during a surge; lower is better |
| Nominal discharge current | Repeated surge capability |
| Impulse current | Capability for direct lightning currents at exposed entry points |
Worked example: why lead length matters (illustrative)
A building lost drives every monsoon despite an SPD at the main board. The SPD had a voltage protection level of 1.5 kV, but it was connected with 1.2 m of cable to the busbar and 1.3 m to the earth bar.
| Item | As found | After rework |
|---|---|---|
| Total lead length | 2.5 m | 0.4 m |
| Extra voltage from leads (about 1 kV per metre) | about 2.5 kV | about 0.4 kV |
| Voltage reaching the board | about 4 kV | about 1.9 kV |
| Drive withstand (from its data) | about 2.5 kV | |
The same SPD, remounted beside the busbar with short straight leads, plus secondary devices at the drive panels, ended the failures. The device was good; the installation defeated it.
Do not mount an SPD at the bottom of a panel with long, looped leads. During a surge those leads add kilovolts on top of the device’s own residual voltage, and the equipment sees the total.
Installation rules
- Keep connecting leads short and straight; aim for under 0.5 m in total.
- Bond to a low-impedance earth that is bonded to the main earth.
- Coordinate stages so energy is shared as intended.
- Fit the overcurrent backup protection the maker specifies.
- Choose devices with status indicators, and plan replacement.
Generators and changeover panels
Fit SPDs on generator control panels and changeover boards where controllers and electronics are present. Transfer events and long outdoor cable runs make these panels exposed. See utility, ATS and DG architecture.
What surge protection does not do
- Fix sustained overvoltage: use a stabiliser.
- Cover outages: use a UPS and generator.
- Remove harmonics: see harmonic mitigation.
- Replace an external lightning protection system for direct strikes.
SPD inspection record
| Location | Indicator status | Lead length | Last replaced |
|---|---|---|---|
| Main board | |||
| Sub-boards | |||
| Generator and changeover panels | |||
| Sensitive loads |
How much lightning current the entry SPD has to carry
Where a building has a lightning protection system, or an overhead supply that can be struck, the SPD at the service entrance must be able to carry part of a direct lightning current, not just the smaller surges induced by a strike nearby. The usual way to size it, from the lightning protection standards, is a simple split. The design lightning current is set by the protection level of the building’s lightning system. About half of it is assumed to flow into the earth termination; the other half is assumed to leave through the incoming services, and is shared equally between their conductors.
| Lightning protection level | Design lightning current | Share leaving through the supply | Per conductor, four-wire supply | Neutral-to-earth gap in a 3+1 arrangement |
|---|---|---|---|---|
| I | 200 kA | 100 kA | 25 kA | 100 kA |
| II | 150 kA | 75 kA | 18.75 kA | 75 kA |
| III and IV | 100 kA | 50 kA | 12.5 kA | 50 kA |
The figures are for the lightning waveform, written 10/350 µs, which carries far more energy than the 8/20 µs waveform used to rate the downstream devices. That is why an entry SPD is specified by its impulse current, Iimp, and a distribution-board SPD by its nominal discharge current, In: the two numbers are not interchangeable, and a device with a large 8/20 rating is not a substitute for a lightning-current-rated one.
The split above is the simplified method and is deliberately conservative. Where the building has several metallic services — a water main, a data cable, a gas pipe — the current divides further, and the per-conductor figure falls; where the supply is the only service, it does not.
The conductor that carries that current to earth has to be sized for it too. A lightning-current SPD is connected to the main earthing terminal with a bonding conductor of at least 16 mm² copper, as short and straight as the panel allows, while a distribution-board SPD typically needs 6 mm². A thin green-and-yellow wire looped to the nearest earth stud is not a lightning conductor however well the device itself is chosen.
The earth electrode behind the main earthing terminal matters less for surge protection than is often assumed: what protects the equipment is that every conductor rises together, which is the job of the bonding, not of the resistance of the earth pit.
Matching the SPD to the earthing system
An SPD is wired between conductors in a pattern, called its connection type, and the right pattern depends on how the installation is earthed. Fitting a device made for one system on another can leave a path unprotected or, worse, create a fault path through the SPD itself.
| Earthing system | Usual SPD arrangement | Why |
|---|---|---|
| TN-S (separate neutral and earth throughout) | Line to earth on each phase and neutral to earth, or the 3+1 arrangement | Neutral and earth are separate, so both need protecting |
| TN-C-S (combined in the supply, separated at the installation) | As TN-S, downstream of the point where neutral and earth separate | Upstream of the split there is only one conductor to protect against |
| TT (installation earth independent of the supply) | 3+1: line to neutral on each phase, then a spark gap from neutral to earth | A line-to-earth device on a TT system can pass a fault current too small to clear, and overheat |
| IT (unearthed or impedance-earthed) | Line to earth, rated for the full line-to-line voltage | After a first earth fault, the healthy phases rise to line voltage above earth |
Generator installations deserve a second look here. A generator whose neutral is earthed at the set, feeding through a changeover that switches or does not switch the neutral, can change the earthing arrangement seen by the SPDs depending on which source is running. The SPDs have to suit both conditions. Draw the earthing for mains and for generator operation separately, and check every SPD against both drawings.
The backup fuse: what protects the SPD
An SPD that has reached the end of its life fails by conducting, and it needs a fuse or breaker in series to disconnect it before it overheats. Every SPD datasheet gives a maximum backup rating, often in the region of 125 to 160 A for an entry device. If the upstream fuse or breaker is no larger than that figure, it can serve as the backup; if it is larger, the SPD needs its own dedicated backup device of a rating the maker permits.
That choice is a choice between two kinds of failure. With the SPD on its own backup fuse, a failed SPD disconnects itself and the supply continues, unprotected, until someone notices the indicator; with the SPD relying on the main fuse, a failed SPD takes the whole supply down, which is more disruptive but impossible to miss.
Most sites prefer continuity with a dedicated backup, and then need a remote alarm contact on the SPD so that the loss of protection is not left for the next inspection to find. Whichever is chosen, the backup device and its cables are part of the connecting lead, and their length counts in the lead-length rule already set out on this page.
Check, too, that the backup device can survive the surge it is protecting against. A small miniature circuit breaker used as SPD backup can trip, or be damaged, by the very surge current the SPD is diverting, leaving the SPD disconnected after its first real event. The maker’s table of permitted backup devices takes this into account, which is one more reason to use it rather than whatever breaker is spare in the board.
Coordination between stages
Layered protection only shares the energy as intended if the stages are coordinated. A low-voltage-protection device downstream starts conducting at a lower voltage than the entry device, and if it is too close electrically, it tries to take the whole surge itself and fails. The cable between the stages provides the inductance that holds the surge back long enough for the entry device to operate.
As a working guide, makers ask for about 10 m of cable between an entry device and a distribution-board device, and about 5 m between a distribution-board device and a final-circuit device, unless they have tested the pair as coordinated or supply a decoupling inductor for shorter runs.
The same physics applies at the other end. An SPD protects equipment close to it; beyond a few metres, a surge travelling down the cable can reflect from the equipment’s input and rise above the SPD’s clamping level. Sensitive equipment more than about 10 m of cable from the nearest SPD — a controller at the far end of a plant room, a remote monitoring panel — should have a device of its own at its terminals.
The lines that are usually forgotten
A surge does not only arrive on the power cable. Any conductor that enters the building, or runs between buildings, can bring one in: telephone and broadband lines, CCTV cables to an outdoor camera, the serial or Ethernet link from a generator controller to a remote monitoring panel, the sensor cable to a fuel tank outside, a gate motor control line. The equipment at the end of such a cable is often the most expensive electronics on site and the least protected, because the power SPDs cannot protect a path they do not see.
Each of these lines needs an SPD of its own, rated for its signal and installed where it enters the building, and each SPD’s earth must be bonded to the same main earth bar as the power SPDs. Two SPDs referred to two different earths can turn a surge into a large voltage between them, and the equipment connected to both — a controller with a power supply and a communication port — sits across that voltage. One bonding point for every service entering the building is the rule that makes the rest of the surge protection work.
Common mistakes
- Long leads.
- One SPD expected to protect the whole site.
- Indicators never checked.
- Poor earth connection.
What to send us
Send the single-line diagram, photos of existing SPD installations and a history of failures. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. The 1 kV per metre figure is a common rule of thumb for fast surges; device data and site conditions govern.
Questions engineers ask
What impulse current rating does the main SPD need?
It follows from the building lightning protection level. In the simplified method, half the design lightning current leaves through the supply and is shared between its conductors. For level III or IV, 100 kA in total, that is 50 kA through the supply and 12.5 kA per conductor on a four-wire supply, so the entry SPD needs an impulse current rating of at least 12.5 kA per pole on the 10/350 waveform. The neutral-to-earth gap of a 3+1 device needs 50 kA.
Which SPD arrangement suits a TT earthing system?
The 3+1 arrangement: an SPD from each line to neutral, and a spark gap from neutral to earth. On a TT system the earth fault current is limited by the earth electrodes, so a failed line-to-earth SPD may pass a current too small to trip its protection and overheat. Connecting line to neutral avoids that, and the neutral-to-earth gap carries the surge to earth. TN-S systems usually use line-to-earth and neutral-to-earth devices instead.
Is one SPD enough?
Usually layers are better. A coordinated scheme places a high-capacity device at the main incomer, further devices at distribution boards and fine protection near sensitive equipment, each limiting what reaches the next. One device at the incomer alone leaves long cable runs that can pick up or reflect surges.
Do SPDs wear out?
Yes. Each surge consumes some of the capability of the protective components, and large surges or many small ones eventually wear them out. Most devices have a status indicator or remote contact that shows when replacement is needed, and they are checked after storms and at every routine inspection.
Does lead length matter?
Yes. During a surge, the inductance of the connecting leads adds voltage to the clamping level of the device, so long or looped leads raise the voltage the equipment sees. Keep the leads as short and straight as possible, connect to the earth bar directly and follow the maker installation guidance.
Is lightning protection the same?
No. Lightning protection is an external system of air terminals, down conductors and earth electrodes that carries a direct strike safely to ground. Surge protective devices protect the electrical wiring and equipment inside from surges, whether from lightning or switching, and both are designed together where lightning risk is high.
Values are illustrative. Follow applicable standards.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.