Isolation Transformers

How isolation transformers work and where they help: galvanic isolation, separately derived neutral, noise rejection, shielding, sizing, inrush, earthing and common installation mistakes.

In short. An isolation transformer has no electrical connection between its primary and secondary windings. It creates a separately derived supply with its own neutral and earth reference, blocks much common-mode noise and limits how faults travel. It does not regulate voltage. Its value depends on correct sizing for harmonic loads, a plan for magnetising inrush and a single, short neutral-to-earth bond.

Who this page is for: For electrical engineers and facility managers specifying isolation transformers for sensitive loads, labs, medical areas or separately derived supplies.

Key facts

  • Primary and secondary are magnetically coupled but electrically separate.
  • The secondary neutral is bonded to earth at one point, near the transformer.
  • An electrostatic screen between windings improves common-mode noise rejection.
  • Harmonic loads need extra thermal capacity: derate or choose a K-rated design.
  • Magnetising inrush at switch-on can be many times rated current for a few cycles.
  • A 1:1 transformer passes voltage changes straight through; it does not regulate.

Key parameters

ParameterWhy it matters
kVA ratingLoad plus margin; harmonic loads need more
ImpedanceSets voltage drop and fault current on the secondary
Inrush currentUpstream protection must not trip on switch-on
ScreenNoise attenuation between windings
Vector groupNeutral availability and triplen harmonic behaviour
LossesHeat and efficiency

Worked example: sizing for a computer room (illustrative)

StepWorkingResult
Load40 kW of computers and LED lighting at 0.95 power factorabout 42 kVA
Harmonic allowanceElectronic loads: derate a standard unit by about 20%42 ÷ 0.8 ≈ 53 kVA
Chosen ratingNext standard size60 kVA, delta-star, screened
Rated primary current at 415 V60,000 ÷ (1.732 × 415)about 83 A
Inrushup to about 10 × rated for a few cyclesroughly 830 A or more at first peak; breaker curve chosen to ride through
Losses at full loadabout 2 to 3%1.2 to 1.8 kW of heat

The delta primary circulates triplen currents inside the transformer instead of passing them upstream, which helps the supply side; the secondary neutral must still be sized for them.

Do not bond the secondary neutral to earth in more than one place, and do not leave it unbonded unless the supply is deliberately designed as an unearthed (IT) system with insulation monitoring, as in some medical locations. Two bonds bring back circulating earth currents and noise; an unplanned missing bond leaves earth faults undetected.

What it does and does not do

DoesDoes not
Separate two circuits electricallyRegulate voltage
Create a new neutral and earth referenceRemove harmonics generated by the load
Reduce common-mode noiseRide through outages
Change voltage level if the ratio is not 1:1Fix poor upstream earthing on its own

For high-noise environments see ultra-isolation transformers; for voltage problems see stabiliser vs isolation transformer.

Isolation transformer specification sheet

ItemValue
Load kVA and type (linear or electronic) 
Rating after harmonic derating 
Vector group and screen 
Upstream breaker and inrush check 
Neutral-earth bond location 

A new earthing system starts at the secondary

An isolation transformer breaks the metallic connection between supply and load, and that includes the neutral. The secondary winding is a new source, and like any source it needs its own neutral-to-earth bond, made once, close to the transformer. That single connection is what turns a fault from a line conductor to a metal enclosure on the load side into a fault current large enough to trip the secondary breaker. Without it, the secondary floats: the first fault to a frame passes unnoticed and leaves the frame at a voltage above earth, waiting for a second fault or a person to complete the circuit.

Three practical rules follow. The bond is made at the transformer or at the first distribution board after it, and nowhere else downstream, because a second bond creates a parallel path that carries neutral current in the earth conductors and defeats the noise isolation the transformer was bought for. The secondary earth is connected to the same main earthing system as the primary side, so that equipment on both sides cannot rise to different voltages. And the breaker on the secondary is chosen for the earth fault current the secondary can actually deliver through its own cables, which should be checked at the farthest outlet rather than assumed.

A transformer installed “to isolate the load” with no secondary bond, on the understanding that an unearthed secondary is safer, is not an isolation transformer in the sense this page uses. That arrangement belongs only to specialised systems with insulation monitoring, such as medical locations, and it must be designed as such.

Inrush and the choice of breaker

When a transformer is switched on, its core can be driven into saturation for the first few cycles, and the current that flows is many times the rated current — commonly ten times or more as a first peak for a dry-type unit, falling away over a fraction of a second. How large it is on any switching depends on where in the voltage wave the breaker closes and on the magnetism left in the core from the last time it was switched off, so the worst case will happen sooner or later however many smooth switchings came before it.

Breaker magnetic characteristicInstantaneous trip rangeOn a transformer primary
Type B3 to 5 times rated currentTrips on inrush; unsuitable
Type C5 to 10 times rated currentTrips occasionally, on the worst switchings
Type D10 to 20 times rated currentThe usual choice for small transformers on miniature breakers
Moulded-case, adjustableSet by the userSet the instantaneous above the maker’s inrush figure, and keep the short-time setting for real faults

The inrush figure should come from the transformer maker, as a peak current and a duration, and the breaker’s curve should be checked against it. On a generator the inrush is also a load step: a 100 kVA transformer has a rated primary current of about 139 A at 415 V, and ten times that as a magnetising surge is a large reactive demand to put on a small set at once. Energise transformers before the load is connected, one at a time, and on a generator in particular never switch several on together.

Working out the K-factor from a harmonic measurement

Harmonic currents heat a transformer more than their RMS value suggests, because the eddy-current losses in the windings rise with the square of the harmonic order. The K-factor expresses that in one number: each harmonic current, as a fraction of the total, is squared, multiplied by the square of its order, and the results are added. A transformer is then chosen with a K rating at or above the figure for its load.

Harmonic orderCurrent, relative to the fundamentalSquaredSquared, times order squared
11.01.001.00
30.80.645.76
50.60.369.00
70.40.167.84
90.20.043.24
110.10.011.21
Total2.2128.05

The K-factor is the second total divided by the first: 28.05 divided by 2.21, about 12.7. A load of single-phase computer power supplies with this spectrum calls for a K-13 transformer; a standard transformer on the same load would need to be derated heavily.

The spectrum here is typical of a room full of small electronic loads, with a total harmonic distortion of about 110%; a site with drives fitted with chokes would come out far lower. The figure should always be worked from a measurement at the place the transformer will serve, at its busiest, rather than taken from a typical table, because it is the actual spectrum that heats the actual windings.

Where a standard transformer has to be used on such a load, ask the maker to state its derated output for the measured spectrum, in writing, rather than applying a rule of thumb. The derating can be severe: on a heavily electronic load a standard unit may be good for well under its nameplate kVA before its windings reach their temperature limit.

Using the primary taps to correct a steady offset

Most isolation transformers above a few kVA have primary taps, typically at 2.5 and 5% either side of nominal. They do not regulate; they shift the ratio once, at installation, to correct a supply that is steadily high or low. If the supply at the site sits at around 395 V, connecting it to the −5% tap, rated about 394 V, brings the secondary back to about 416 V at no load. If it sits at about 405 V, the −2.5% tap, rated about 405 V, gives about 415 V.

Two cautions apply. Taps are changed with the transformer de-energised and isolated, never on load. And a tap chosen on a recording made at one time of day can be wrong at another: a supply that is 395 V in the evening and 430 V at night will, on the −5% tap, give about 453 V at night. A supply that moves needs a stabiliser; a tap is only for a steady offset.

What a screen’s attenuation figure means

The earthed electrostatic screen between the windings is what stops high-frequency common-mode noise from passing through the winding capacitance, and makers state its effect in decibels. The scale is logarithmic: 20 dB reduces the noise voltage tenfold, 40 dB a hundredfold, 60 dB a thousandfold and 80 dB ten-thousandfold. A figure is meaningful only with the frequency at which it was measured, because attenuation falls as frequency rises, and with the test arrangement, which should be stated on the datasheet.

The screen only works if its earth connection does. It is brought out to its own terminal, and that terminal must be connected by a short conductor to the earth bar at the transformer. A screen left unconnected, or connected through a long looping wire, gives little more attenuation than no screen at all, and the transformer then does half of what it was bought to do.

The loss that runs all year

An isolation transformer draws its core loss whenever it is energised, whether the load is running or not. The figure is on the test certificate, and it adds up: every 1 kW of no-load loss is 8760 kWh in a year of continuous energisation. When comparing two transformers for a load that is on only part of the day, the no-load loss usually matters more than the load loss, and a unit that can be switched off with its load, where the process allows, saves that energy outright.

The temperature-rise rating is the other figure worth comparing. Dry-type transformers are offered with rated winding temperature rises of 80, 115 or 150 degrees above ambient, often in the same insulation class. A unit designed for an 80 degree rise uses more copper and iron for the same kVA, runs cooler, has lower load losses and has more thermal margin for harmonic load or a hot room; a 150 degree unit is smaller and lighter but works its insulation harder. For a transformer that will run near its rating around the clock, the lower-rise design is usually the better one to live with.

Common mistakes

  • Neutral bonded in more than one place.
  • No harmonic derating for electronic loads.
  • Breaker tripping on switch-on inrush.
  • Expecting voltage regulation.

What to send us

Send the load list, the problem (noise, earth, voltage level) and the upstream breaker. WhatsApp 98852 01608 or use the application engineering enquiry. See harmonics.

Evidence note. Derating, inrush and loss figures are illustrative; makers’ data govern.

Questions engineers ask

Where should the neutral be bonded to earth after an isolation transformer?

Once, at the transformer secondary or at the first distribution board after it, and nowhere else downstream. That single bond makes a line-to-frame fault on the load side large enough to trip the secondary breaker. A second bond further down puts neutral current into the earth conductors and spoils the noise isolation. Connect the secondary earth to the same main earthing system as the primary side, so both sides stay at the same potential.

What K-factor rating does an isolation transformer need?

One at or above the K-factor worked out from a harmonic measurement of its load. Square each harmonic current as a fraction of the total, multiply by the square of its order, add the results, and divide by the sum of the squared currents. A room of single-phase computer supplies with a strong third harmonic can come out around 12.7, which calls for a K-13 transformer. Loads of drives fitted with chokes come out far lower.

Does it clean harmonics?

No. A delta-star isolation transformer traps triple harmonics in its delta winding and its impedance limits some others, but it does not remove harmonics in general. Where harmonic distortion is a problem, measure the spectrum and add mitigation such as filters or reactors; the transformer may also need a higher rating for that load.

Do I need a screen?

For noise-sensitive loads, yes. An earthed electrostatic screen between the windings reduces the high-frequency noise coupled from the supply to the load through the capacitance of the windings. It suits laboratory instruments, medical equipment, control systems and communication equipment that are affected by electrical noise on the supply.

What about inrush?

Plan for magnetising inrush in the protection settings. When a transformer is switched on it can draw a brief current many times its rated current while the core magnetises, which can trip an instantaneous breaker. Choose the breaker curve and settings from the maker inrush data, and test by energising several times.

Is it a safety device?

It reduces some risk when installed with correct earthing, by separating the load from the supply earth reference and limiting certain fault paths. It is not a safety device on its own: the secondary still needs correct earthing, residual current protection where required and safe working, just like any other supply.

Values are illustrative. Design earthing per site and codes.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.