In short. A relay stabiliser switches transformer taps with relays, so it corrects in steps and costs less. A servo stabiliser adjusts smoothly with a motor and holds a tighter output. Relay types suit light, non-critical loads with wide voltage tolerance. Servo types suit motors and sensitive equipment, and usually cost less over their life when duty is heavy.
Who this page is for: For shop owners, building managers and small-factory engineers deciding between a low-cost relay stabiliser and a servo stabiliser.
Key facts
- Relay units move the output in steps, often about 10 V or more per tap; servo units move continuously.
- Relay contacts wear with every switching operation, faster under load and with inrush.
- Motors starting through a relay unit can make it chatter and burn contacts.
- Relay units click audibly and can cause visible steps in lighting.
- Judge on life cost: replacements, downtime and damaged equipment, not only purchase price.
- Neither type protects against outages.
How they differ
| Criterion | Relay type | Servo type |
|---|---|---|
| Correction | Stepped, tap by tap | Continuous |
| Output band | Wider | Narrower |
| Switching | Fast but abrupt | Slower, smooth |
| Wear point | Relay contacts | Brushes, rollers, motor |
| Noise | Audible clicking | Quiet motor sound |
| Purchase price | Lower at small ratings | Higher |
| Best use | Lighting, small appliances | Motors, equipment, process |
Worked example: the cold-room upgrade (illustrative)
A small shop runs lighting, signage and billing computers through a 5 kVA relay stabiliser. Output steps of about 9 V are acceptable for these loads. The owner then adds a cold room with a motor drawing about 6 A running and five to six times that while starting: 30 to 36 A, against the unit’s rating of about 22 A at 230 V before any other load.
| What happened | Why |
|---|---|
| Relays chattered at each motor start | The starting current pulled the input down across a tap boundary, the unit switched, the voltage recovered, and it switched back |
| Lights flickered visibly | Each switch was a 9 V step |
| Contacts failed within a few months | Repeated switching under inrush current |
| Fix: servo unit sized for the motor start, relay unit retired | Smooth correction; no contacts switching under load |
The relay unit was right for the original load and wrong for the new one. Re-check the stabiliser whenever a motor load is added.
Do not run motors, pumps or air-conditioners through a relay stabiliser unless it is explicitly rated for their starting current. Chattering relays burn contacts and can damage the very equipment they are meant to protect.
Step size and its effect
A relay stabiliser has a limited number of taps. If each tap moves the output by, say, 9 V, then as the input drifts the output jumps in 9 V steps and stays within a band roughly that wide. Lighting shows the jumps; sensitive equipment may react to them. A servo unit has no steps, so its output band can be a few volts.
When each is the right choice
| Situation | Better choice |
|---|---|
| Light loads with wide voltage tolerance | Relay |
| Budget-limited, non-critical or temporary use | Relay |
| Frequent motor starts | Servo |
| Precision machines and sensitive electronics | Servo, or static if fast dips matter. See servo vs static |
| Continuous heavy industrial duty | Servo |
Counting life cost
Add replacement units, contact repairs, downtime and any damaged equipment to the purchase price. A cheap unit replaced twice in five years often costs more than one servo unit that lasts the period with routine brush and roller service.
Selection sheet
| Item | Value |
|---|---|
| Loads and their kVA | |
| Motors and their starting current | |
| Output band the loads accept | |
| Expected switching frequency (how unstable is the supply?) | |
| Choice and reason |
Relay life in operations, turned into years
A relay stabiliser’s life is counted in switching operations, not in years, and the number of operations it makes depends on the supply, not on the stabiliser. A relay rated for 100,000 electrical operations at its full load current sounds inexhaustible until it is set against a supply that wanders back and forth across a tap boundary all evening.
| Tap changes a day | Years to 100,000 operations | Years to 1,000,000 operations | Typical supply |
|---|---|---|---|
| 50 | about 5.5 | about 55 | Steady urban supply with a daily swing |
| 200 | about 1.4 | about 14 | Supply that drifts through the evening peak |
| 500 | about 0.5 | about 5.5 | Weak rural feeder with constant movement |
The relay is not the only switching part that counts: every operation of a relay also switches the winding it connects, and every switching under load at an unlucky instant erodes the contacts faster than the rated figure assumes. The table therefore gives the best case. The useful question for any relay unit is how many operations its relays are rated for at the load current it will carry, and how many tap changes a day the site’s supply will cause. The second figure comes from a recording: count how often the voltage crosses each tap boundary in a typical day, and the arithmetic does the rest.
Worn contacts do not only stop working; they can weld. A relay whose contacts have welded closed leaves its winding permanently in circuit, so the unit is stuck on one tap whatever the supply does. If that tap is a boost, a normal supply becomes an overvoltage at the output. A relay unit worth considering therefore has an output cut-off that works independently of the relays it is protecting against, and the cut-off should be tested at installation, not taken on trust.
The relay rating that actually applies
A relay’s current rating is stated for a particular kind of load, and the figure on the front of the datasheet is usually the most favourable one, for resistive load. Switching an inductive load, or a load that includes motors, is much harder on the contacts: the arc at opening lasts longer and the current at closing can be several times the running current.
Contactor and relay ratings distinguish these duties, commonly as AC-1 for resistive load and AC-3 for motor load, and the AC-3 rating of the same device can be a fraction of its AC-1 rating. A stabiliser feeding air conditioners, pumps or refrigeration plant is switching a motor load, and its relays should be judged on that duty. Ask which rating the maker has used, and expect a good answer to name the duty, not just the amps.
Response to different kinds of disturbance
The two types are good at different things, and the honest comparison is disturbance by disturbance rather than a single verdict.
| Disturbance | Relay type | Servo type |
|---|---|---|
| Slow drift over minutes or hours | Follows it in steps, switching each time a boundary is crossed | Follows it smoothly; this is what it does best |
| A sudden step that persists | Corrects within a cycle or two, in one or more steps | Corrects over a second or more, at its set rate |
| A dip lasting under a second | May switch in and back out, adding two steps to the dip | Barely responds; the dip passes through |
| A supply hovering at a tap boundary | Can switch repeatedly, the worst case for contact life | Holds steady with a small dead band |
| Motor starting on the same supply | Can switch during the start, under the starting current | Too slow to react, which is usually an advantage |
The pattern is that a relay unit reacts to everything and a servo unit reacts only to what lasts. For a supply that moves slowly, the servo’s smoothness and the absence of switching wear both point the same way. For loads that need fast correction of real steps, neither type is ideal, and a static stabiliser, which switches with semiconductors at the current zero, is the type designed for that duty.
What a step looks like on the lights
The size of a relay unit’s step decides whether people notice it. On a 230 V single-phase output, a 5 V step is about 2.2%, a 10 V step about 4.3% and a 15 V step about 6.5%. Lamps respond to sudden changes of a few percent, and LED drivers vary widely: some hold their light output through a step of several percent, while basic drivers pass it straight through as a visible blink.
A unit with large steps on a supply that keeps crossing a boundary therefore gives a room of lights that blink at irregular intervals, which is one of the most common complaints about relay units and one that no accuracy figure reveals.
Ask the maker for the step size in volts, not only the output accuracy band; a unit with a ±5% band can have steps of over 20 V. Where lighting quality matters — offices, shops, clinics — either a servo unit or a static unit with small steps is the appropriate choice.
Where a servo stabiliser wears, and how to look after it
A servo stabiliser has wear parts too, and knowing them is part of a fair comparison. The carbon brush or roller that moves along the variable transformer’s winding wears with travel, and the track it runs on can pit or discolour if the brush arcs. The servo motor and its gearbox wear with every movement. Dust collects on the track and between the turns of the winding. On a steady supply these parts last for years; on a supply that moves all day, they wear in proportion to the distance the brush travels.
The maintenance is simple and should be scheduled. Inspect the brush and track every few months, more often on a moving supply or in dusty surroundings: replace the brush before it reaches its wear limit, and clean the track with the method the maker specifies. Check the motor drive for backlash and the limit switches for correct operation at both ends of travel. A servo unit maintained like this outlasts a relay unit on the same supply by a wide margin; one left alone eventually fails at the brush, usually at one end of its travel and usually at the most inconvenient voltage.
How to test a stabiliser before relying on it
A short test on a variable supply tells more than any datasheet, and applies to both types. Raise and lower the input slowly through its whole range and record the output: a relay unit should show clean steps of the stated size, with a small difference between the voltages at which each tap switches going up and coming down; a servo unit should show a smooth output with a small, steady dead band.
Then apply a sudden step to the input and record how long the output takes to recover. Finally, hold the input at a value just at a tap boundary for a few minutes. A relay unit that chatters there will do so every day on site, and a servo unit that hunts back and forth has its dead band set too tight. Keep the record with the selection sheet; it is the evidence behind the choice.
Common mistakes
- Keeping a relay unit after adding motor loads.
- Sizing on running current and ignoring starting current.
- Comparing purchase prices only.
- Expecting a stabiliser to cover outages.
What to send us
Send the load list, especially motors, and the supply problem you see. WhatsApp 98852 01608 or use the application engineering enquiry. See servo stabilisers.
Evidence note. Step sizes and currents are illustrative; makers’ ratings govern.
Questions engineers ask
Why do the lights blink with a relay stabiliser?
Because each tap change is a sudden step in voltage. On a 230 volt output a 10 volt step is about 4.3%, enough for many lamps and basic LED drivers to show a visible blink. On a supply that keeps crossing a tap boundary, the steps come at irregular intervals all evening. A servo stabiliser or a static unit with small steps avoids it; ask for the step size in volts, not just the accuracy band.
Which stabiliser type suits a supply that drifts slowly?
A servo stabiliser. It follows a slow drift smoothly, with no switching wear and no visible steps, which is exactly the duty it is designed for. A relay unit follows the same drift in steps and switches each time a tap boundary is crossed, which on a supply that moves all evening can mean hundreds of operations a day. Where real steps must be corrected within a cycle, a static stabiliser is the type designed for that.
Is relay type bad?
No. A relay-type stabiliser suits light loads and modest variation at low cost, which is why it is common for homes and small offices. It corrects in steps rather than smoothly, so its output varies within a band, and it is less suitable for large motors or loads that need tight voltage.
Does it click?
Yes. Each tap change operates a relay, which makes an audible click, and a supply that hovers near a switching point can cause frequent clicking. That is normal behaviour, but very frequent switching shortens relay life, so a unit that clicks constantly may be set badly or unsuitable for that supply.
Can it handle an AC?
Only if it is rated for the starting current of the air-conditioning unit. The motor draws several times its running current at each start, and an undersized relay unit can drop out, chatter or weld its contacts. Check the rating on the data sheet against the unit, including its time delay on restart.
How long do relays last?
It depends on how often the relays switch and the current they carry when they do. A stable supply with rare tap changes gives long relay life, while a fluctuating supply with heavy loads wears contacts much faster. Check for pitting or sticking at service, and replace relays before they fail.
Values are illustrative. Use manufacturer data.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.