Utility + DG + UPS + BESS System Studies Guide

How to study a combined utility, diesel generator, UPS and battery system: operating modes, transitions, step response, fault behaviour, harmonics and control hierarchy for reliable power.

In short. When utility, generator, UPS and battery storage share a site, each can help or harm the others. A system study defines every operating mode and every transition between modes. In each one it checks voltage, frequency, fault current, harmonics and control behaviour. The weakest transition usually decides how reliable the whole system is, so that is where the study spends most of its time.

Who this page is for: For consultants and engineers designing or reviewing multi-source power systems for critical sites.

Key facts

  • List every mode: grid, generator, island with battery, parallel, maintenance.
  • List every transition between them, including failures.
  • Check fault current in each mode; inverter sources give little.
  • Check harmonics on the weakest source, usually the generator.
  • Check that protection operates in every mode.
  • Test the critical transitions on site.

Sources and their character

SourceStrengthWeakness
UtilityStiff, low-cost energyOutages and sags
Diesel generatorLong-duration backupStart time, load steps, higher impedance
UPSNo-break supplyLimited runtime, limited fault current
Battery storageFast response, peak supportLimited energy and fault current

Worked example: fault current in each mode (illustrative)

ModeFault at a 100 A feederFeeder breaker clears?
Gridabout 15 kAYes, instantaneous
Generator onlyabout 3 kAYes, instantaneous
Island on battery inverter onlyabout 0.4 kA (inverter current limit)No: below instantaneous, thermal too slow
FixFeeder breakers fitted with electronic trip units; a lower short-time pickup is selected in island mode, and the inverter is checked to hold its fault current longer than the trip time

Protection set for grid and generator would not have cleared a fault while the site ran on its battery. See inverter fault current.

Do not assume protection that works on grid and generator will work in a battery or UPS-fed island. Inverter fault current is limited, and breakers may not trip at all.

Checks in every mode

Mode and transition matrix

Mode or transitionFault currentProtection OK?Voltage/frequency OK?
Grid   
Generator   
Island on battery   
Grid to island transition   

Worked example: what each transition must survive (illustrative)

For a site with grid, a 1250 kVA generator, a 400 kVA UPS and a 500 kW battery, the study lists every transition and the check that decides it.

TransitionWhat happensDeciding check
Grid lost, battery leadsBattery inverter becomes grid-forming within millisecondsIsland detection speed; battery power above the load at that moment
Generator starts and joinsSet synchronises to the battery-formed busSynchronising window on a weak bus; sharing after closing
Battery exhausted or tripsGenerator carries everythingStep the generator sees; shedding if it exceeds the allowed step
Grid returnsIsland resynchronises and the tie closesSync-check; utility permission; mode changes in every controller
UPS to bypass during generator supplyCritical load sees the generator directlyGenerator voltage and frequency excursions inside the load’s tolerance

Each row becomes a study case and a site test. The transitions, not the steady modes, are where multi-source sites lose their loads, so the study spends most of its effort here.

Worked example: how long the battery can bridge (illustrative)

The battery has 500 kWh usable and a 500 kW converter. If the site imports 350 kW when the grid is lost, the battery can carry it for up to 500 ÷ 350 ≈ 1.4 hours on energy, far longer than the generator’s start and synchronising time of under a minute. Energy is not the constraint for a bridge; power is.

If the site load were 600 kW, the 500 kW converter could not carry it even for a second, and at least 100 kW would have to be shed at the moment of islanding. The study therefore compares the converter rating with the highest import that can occur, and sizes the shedding to cover the difference.

Worked example: the UPS on the generator (illustrative)

A 400 kVA six-pulse UPS at full load draws a 5th harmonic current of roughly a quarter of its input current. On the 1250 kVA generator’s base, that is about 0.25 × 400 ÷ 1250 = 0.08 per unit.

The 5th harmonic voltage it creates is roughly that current times the harmonic order times the generator’s subtransient reactance: 0.08 × 5 × 0.12 ≈ 0.048, about 4.8% from the 5th alone, before the 7th and higher are added. On the grid the same current produces well under 2%. The study must check the generator case, because that is when the voltage regulator, the UPS rectifier and every other electronic load see the worst waveform.

Earthing in each mode

The neutral earthing that is correct on grid supply may not exist in island mode. A transformer earthed at its star point disappears when the tie opens, and an island formed by an inverter or a generator must have its own neutral earth, at exactly one point, or earth faults are not detected and touch voltages are not controlled. The study states which earth point is in service in each mode, how the switching keeps exactly one in service, and how earth-fault protection is set for the fault current available in each case.

What the study should deliver

  • A mode and transition matrix covering every steady mode and every transition, including failures during transitions.
  • Fault current and protection operation in every mode, feeder by feeder for the critical boards.
  • Voltage and frequency response for the worst step in each mode.
  • Harmonic voltage distortion on each source, generator included.
  • Earthing and neutral arrangement in each mode.
  • Control settings each mode depends on: synchronising windows, shedding tables, ramp limits.
  • A site test plan for every transition.

Testing the transitions on site

Each transition in the matrix is tested with real load: the grid opened at a known import, the generator joined to a battery-formed bus, the battery tripped while carrying load, the grid restored and resynchronised, and the UPS forced to bypass on generator supply. Record voltage, frequency and the power of each source through each event, and compare them with the study. Where they differ, the study is corrected as well as the settings, so the next change is assessed against a model that matches the plant.

Keeping the controllers in step

Each source has its own controller with its own idea of the site’s state. When the grid is lost, the battery controller, the generator controller, the UPS and any plant controller must all agree, within a second, on who leads, who follows and what is shed. Map every controller’s mode against every site mode in one table, list the signals that tell each one the mode has changed, and test what each does if that signal is lost. Most multi-source failures turn out to be two controllers acting correctly on different beliefs about the site.

Maintenance modes are modes too

When the UPS is on maintenance bypass, the battery is out of service, or one generator is under repair, the site runs in a configuration the normal-mode study may not cover. List each maintenance mode in the matrix with its own fault current, protection and response checks. A UPS on maintenance bypass with the generator supplying, for example, exposes critical loads to the full generator transient, and should be planned only when the grid is stable and the generator is proven available.

Protection setting groups for each mode

Where fault current differs widely between modes, numerical relays and electronic trip units can switch between setting groups, selected automatically from breaker positions or the plant controller. A group for grid supply, one for generator supply and one for battery or inverter supply lets each feeder clear faults in every mode without compromising selectivity in the others. The selection signal must be reliable and fail to the safest group, and every group must be tested.

Data to collect before the study

  • Utility fault level and its range, from the supply authority.
  • Generator reactances, inertia, governor and regulator data, and step-load performance.
  • UPS input current spectrum, walk-in time, recharge current and output fault current.
  • Battery converter rating, current limit, fault behaviour and grid-forming capability.
  • Load list with priorities, motor starting methods and harmonic sources.
  • Present protection settings and the earthing arrangement of each source.

Data missing at the start becomes an assumption in the study; list every assumption, so the site tests can confirm or correct them.

Faults these studies usually prevent

The same few problems appear on site after site where the sources were added one at a time without a combined study: a UPS that refuses to synchronise to the generator because its frequency window is too narrow, a battery system that trips during a generator load step, protection that cannot clear a fault on inverter supply, and a neutral earth arrangement that leaves one mode without a proper earth fault path. Each is cheap to fix on paper and expensive to discover during a real outage.

Common mistakes

  • Studying grid mode only.
  • Ignoring inverter current limits.
  • Transitions never tested.
  • Harmonics checked on grid only.

What to send us

Send the single-line diagram and source data, and the modes you need. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Fault values are illustrative; studies govern.

Questions engineers ask

How long can a battery bridge until the generator takes over?

Energy rarely limits a bridge; power does. A 500 kWh battery carrying a 350 kW import could run for about 1.4 hours, far longer than the generator needs to start and synchronise. But if the load exceeds the converter rating, say 600 kW on a 500 kW converter, it cannot carry it even for a second, and the excess must be shed at the moment of islanding.

How much voltage distortion does a UPS cause on a generator?

Roughly the harmonic current in per unit of the generator rating times the harmonic order times the subtransient reactance. A 400 kVA six-pulse UPS on a 1250 kVA set with 0.12 reactance gives about 0.08 per unit of 5th harmonic current and about 4.8% 5th harmonic voltage, before higher orders are added, against well under 2% on the grid.

Can a battery replace a generator?

Only for as long as its stored energy lasts. A battery can bridge the start of a generator, cover short outages and supply load steps, but a long outage needs a source of energy such as diesel or gas. The study sizes the battery for its jobs: power for the bridge and steps, energy for the expected outage duration.

Why does the UPS cause trouble on generator?

Because its rectifier draws distorted current, and the generator, with a much higher source impedance than the grid, turns that current into voltage distortion that can upset its own regulator and other loads. Large input steps and full-rate battery recharge after an outage also stress the set. Input ramping and recharge limits help.

What is grid-forming?

A source that sets the voltage and frequency for an island, behaving like a voltage source, as a generator does naturally. Grid-following sources, such as most solar and many battery inverters, need a voltage to follow. An island needs at least one grid-forming source, and the study defines which one leads in each mode.

Is a closed-transition retransfer worth it?

Where loads cannot tolerate a second break when the grid returns, yes. It parallels the sources briefly so the load moves without interruption, but it needs synchronising, a parallel time limit, a fault level check for the parallel condition, protection settings for it and usually utility approval.

This guide gives general principles. Integrated systems need a project-specific study.