Harmonic Studies and Resonance Analysis Guide

How to study harmonics: nonlinear sources, current and voltage distortion, source impedance on generator supply, frequency scans, resonance with capacitors and acceptance limits.

In short. A harmonic study finds which harmonic currents flow, where they come from and what voltage distortion they cause. It also finds whether capacitors and the supply create a resonance that amplifies them. Harmonic voltage equals harmonic current times system impedance at that frequency. The same drives can therefore be harmless on a strong transformer and troublesome on a generator, or with one capacitor step switched in.

Who this page is for: For engineers dealing with drives, UPS, capacitor failures, hot neutrals or generator problems on non-linear loads.

Key facts

  • Six-pulse drives mainly produce 5th, 7th, 11th and 13th harmonics.
  • Single-phase electronics produce triplen harmonics that add up in the neutral.
  • Resonance order is roughly √(fault level ÷ capacitor kVAr).
  • Each capacitor step and each source mode moves the resonance.
  • Generators are weaker sources, so the same current gives more voltage distortion.
  • Measure first, over a full production cycle.

Worked example: where the resonance moves (illustrative)

Source and capacitorsWorkingResonance
1000 kVA, 6% transformer; 300 kVArFault level 1000 ÷ 0.06 ≈ 16,700 kVA; √(16,700 ÷ 300)about 7.5th: close to the 7th
500 kVA generator (subtransient reactance 0.12); 300 kVAr500 ÷ 0.12 ≈ 4170 kVA; √(4170 ÷ 300)about 3.7th
Same generator, one 100 kVAr step√(4170 ÷ 100)about 6.5th: between the 5th and 7th

Capacitor fuses had been failing on mains supply, and the resonance near the 7th explains why. A 7% detuned bank, tuned below the 5th, removed the resonance in every mode. Capacitors were also limited on generator supply. See filter studies and reactive power.

Do not add plain capacitors to a site with drives or UPS without a resonance check in every source mode and step combination. Repeated capacitor failures are a symptom, not bad luck.

Study steps

  1. Measure voltage and current spectra at the main board and large loads.
  2. List harmonic sources and capacitor steps.
  3. Calculate resonance for mains and generator modes.
  4. Check transformers, neutrals, capacitors and the generator alternator.
  5. Choose mitigation and measure again afterwards.

See harmonics and generator sizing.

Harmonic sheet

ModeFault level kVACapacitor kVArResonance orderNear a harmonic?
Mains    
Generator    

What different loads inject

The study starts with the harmonic current each load draws. Values vary with make, loading and supply strength, so the ranges below are for planning only; measurement or the maker’s data replaces them in the study.

LoadMain ordersTypical total current distortion
Six-pulse drive, no choke5th, 7th, 11th, 13thAbout 80 to 130%
Six-pulse drive with AC or DC choke5th, 7thAbout 30 to 45%
Twelve-pulse drive or UPS rectifier11th, 13thAbout 10 to 15%
Active front end drive or UPSHigh orders, smallUnder about 5%
Single-phase electronic loads, LED lighting, IT3rd, 5th, 7thAbout 70 to 120%, with the 3rd dominant

A drive at part load often shows a higher percentage distortion than at full load, but a lower harmonic current in amperes. The study works in amperes, because amperes multiplied by impedance give the voltage distortion that other equipment sees.

Worked example: the same current on grid and on generator (illustrative)

Harmonic voltage at the bus is roughly the harmonic current, in per unit of the source rating, times the harmonic order, times the source reactance in per unit. Take 150 A of 5th harmonic current at a 415 V main board.

SourceRated currentCurrent in per unit5th harmonic voltage
1.6 MVA transformer, 6% impedanceAbout 2226 A150 ÷ 2226 ≈ 0.0670.067 × 5 × 0.06 ≈ 2.0%
1000 kVA generator, reactance about 0.15About 1391 A150 ÷ 1391 ≈ 0.1080.108 × 5 × 0.15 ≈ 8.1%

The same load gives four times the distortion on the generator, from the 5th harmonic alone. That explains the most common complaint on generator sites: equipment that works on mains misbehaves on generator, regulators hunt, and UPS units reject the supply. For generators, the negative-sequence or subtransient reactance from the alternator data sheet is used, and it differs between makes, so the study uses the actual machine.

Triplen harmonics and the neutral

Third-harmonic currents in the three phases are in step with each other, so in the neutral they add instead of cancelling. Take a feeder with 100 A of fundamental current and 70 A of 3rd harmonic in each phase. Each phase carries about 100 × √(1 + 0.49) ≈ 122 A, but the neutral carries 3 × 70 = 210 A, about 1.7 times the phase current. A neutral sized at half the phase conductor, or even equal to it, overheats. The study flags feeders with large single-phase electronic load and checks the neutral, the transformer and the generator, whose own neutral also carries this current.

Parallel and series resonance

A parallel resonance forms between the source inductance and a capacitor bank on the same bus. Near the resonant order the network impedance rises sharply, so a modest harmonic current produces a large voltage distortion and a large current swinging between the capacitor and the source. A series resonance forms between a capacitor and a transformer or reactor in series with it, and gives a low-impedance path that draws harmonic current from elsewhere in the network, sometimes from the utility supply itself.

Resistive load damps both. At night or at weekends, when little resistive load is running but capacitors and drives remain connected, the resonance is sharpest and the distortion highest. That is why measurements taken only during the busy day shift can miss the worst case, and why the study models light load as a separate case.

The cases a complete study covers

CaseSourceCapacitor stateLoad
1GridAll stepsFull
2GridEach step in turnLight
3One generatorAs the controller allowsFull critical load
4Two or more generatorsAs the controller allowsFull critical load
5GeneratorAs allowedLight, after a shutdown
6FuturePlanned additionsPlanned additions

Each case gives a resonant order and a voltage distortion. Any case near the 5th, 7th, 11th or 13th order, or above the distortion target, needs mitigation or an operating rule, such as switching capacitors out on generator supply.

Setting the targets

Targets come from the applicable standards and the supply authority at the point of connection, and from the equipment inside the site. A common design target at low voltage is a total voltage distortion of about 5%, with lower values for sites with sensitive equipment. The generator adds its own limit: alternator makers state the distortion or harmonic current that their machines carry before derating. The study lists every target with its source and checks each case against the strictest one that applies.

Heating in transformers, cables and alternators

Harmonic current heats equipment more than the same RMS current at 50 Hz, because eddy-current and stray losses rise steeply with frequency. Transformers serving heavy electronic loads may need derating or a design rated for harmonic loading. Cables carry extra heat from skin effect at high orders, and especially from neutral current. In alternators, harmonics heat the damper windings and the rotor surface. The study estimates the extra heating and checks that each item stays inside its rating, or states the derating needed.

Mitigation, from source to network

  • Choose low-harmonic drives and UPS, or add chokes, when equipment is bought.
  • Replace plain capacitors with detuned banks wherever drives or UPS are present.
  • Add passive or active filters where the study shows the targets are exceeded.
  • Limit capacitor steps or non-essential drives on generator supply.
  • Size neutrals, transformers and generators for the harmonic duty that remains.

See harmonic filter application studies and reactive power and power factor studies.

What the study report contains

A complete report gives the measured spectra with the dates and operating conditions, the network model and its data sources, the resonant order and distortion for every case, the comparison with each target, the heating checks, the recommended mitigation with its own resonance check, and the measurements to repeat after the changes. Where assumptions replace missing data, they are listed, so that a later measurement can confirm them.

Generator supply: rules that follow from the study

Many sites cannot remove every harmonic problem at source, so the study ends with operating rules for generator supply. Typical rules are to switch capacitor banks out, or limit them to steps that the study shows are safe, whenever the generator carries the load; to delay non-essential drives until the set is loaded with resistive load that damps resonance; to run a second set in parallel when large UPS or drive loads are on, which halves the source reactance and the distortion; and to check the alternator regulator is of a type that is not upset by distorted voltage, such as one supplied from a permanent magnet generator rather than from the main output. Each rule is written into the changeover or plant controller, not left to memory.

See generator sizing and transient performance studies.

When to repeat the study

Repeat the resonance check whenever a capacitor bank is added, extended or replaced, whenever a large drive, UPS or rectifier is installed, whenever a transformer or generator is changed, and whenever the supply authority reports a change in fault level. Each of these moves the resonant order or the harmonic current, and a site that was safe last year can be close to resonance after one small change.

Common mistakes

  • Judging by THD percentage alone.
  • Mains-only study.
  • Only the full capacitor bank checked.
  • Reducing the neutral size on electronic loads.

What to send us

Send any harmonic readings, the drive and UPS list and the capacitor bank data. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Values are illustrative.

Questions engineers ask

How much more harmonic distortion does a generator give than a transformer?

Harmonic voltage is roughly the harmonic current in per unit times the order times the source reactance. 150 A of 5th harmonic gives about 2.0% on a 1.6 MVA transformer of 6% impedance, but about 8.1% on a 1000 kVA generator with a reactance of 0.15, four times as much from the same load.

Why can the neutral carry more current than the phases?

Third harmonic currents in the three phases are in step, so they add in the neutral. With 100 A of fundamental and 70 A of 3rd harmonic per phase, each phase carries about 122 A but the neutral carries about 210 A, roughly 1.7 times the phase current. Neutrals, transformers and generators serving electronic loads must be sized for this.

Why does my generator show more distortion than the mains?

A generator has a much higher source impedance than a grid transformer, often two to four times as high in per unit terms, so the same harmonic current produces proportionally more voltage distortion. Capacitor banks also resonate at a lower order on generator supply. Check distortion in every source mode, not only on mains.

What is resonance?

A condition where the inductance of the supply and the capacitance of a capacitor bank cancel at one frequency. In parallel resonance the network impedance becomes very high at that frequency, so small harmonic currents produce large voltage distortion. It is worst at light load, when little resistive load is connected to damp it.

Do harmonics heat the alternator?

Yes. Harmonic currents induce currents in the damper windings and the rotor surface, and raise iron losses, so the alternator runs hotter than the same RMS current at 50 Hz would make it. Makers state the harmonic loading their machines accept before derating. Sets supplying large drive or UPS loads are often oversized for this reason.

Can I measure instead of model?

Measurement shows the present spectrum and calibrates the model, but it cannot show the effect of a capacitor step not yet switched, a generator mode not yet run, or loads not yet installed. A model is needed to test those cases and the mitigation. Use both: measure first, model second, then measure again.

This guide gives general principles. Limits come from the applicable standards and equipment.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.