In short. A diesel generator’s fault current starts high and then falls. For the first few cycles it is the rated current divided by the sub-transient reactance X″d, typically 5 to 10 times rated. Over the next tenths of a second it falls towards the transient value set by X′d. After that it settles at a steady value that depends on the excitation system. With a PMG or auxiliary-winding excitation it holds at about three times rated for several seconds. With a simple shunt-excited AVR it can collapse to rated current or less. Breakers are rated on the first value; protection must work on the last.
Who this page is for: For engineers rating breakers and setting protection on generator supply: know how much fault current a set delivers, how fast it decays and what the excitation system changes.
Key facts
- Initial fault current = rated current ÷ X″d, typically 5 to 10 times rated.
- A 1000 kVA set gives about 9.9 kA initially at 415 V; a 500 kVA set about 4.6 kA.
- With PMG or auxiliary-winding excitation the current holds at about 3 times rated for several seconds.
- With a shunt-excited AVR it can fall to rated current or less.
- With a solidly earthed neutral, an earth fault can exceed the three-phase fault current.
- Breakers are rated on the initial and peak current; protection must work on the decayed current.
Three reactances, three time zones
| Reactance | Time zone | Typical value (per unit on the set’s rating) | Fault current | Used for |
|---|---|---|---|---|
| Sub-transient X″d | First few cycles | 0.10 to 0.20 | 5 to 10 × rated | Breaker making and breaking duty, peak forces |
| Transient X′d | Up to about a second | 0.15 to 0.35 | 3 to 7 × rated | Protection grading in the short-time zone |
| Synchronous Xd | Steady state | 1.5 to 3.0 | Below rated without excitation forcing | Sustained fault current and long-time protection |
The changes from one zone to the next follow time constants published on the alternator data sheet: T″d, a few hundredths of a second, and T′d, around a tenth of a second or more on LV alternators. A DC component also appears at the moment of the fault and decays with the armature time constant.
Why the excitation system changes the answer
| Excitation | What happens in a close-in fault | Sustained current |
|---|---|---|
| Shunt (self-excited) AVR | The AVR is fed from the alternator’s own terminals. When the voltage collapses, so does the field | Can fall to rated or below within about a second |
| Auxiliary winding | A separate winding keeps feeding the AVR during the fault | Around 3 × rated for several seconds |
| Permanent magnet generator (PMG) | The AVR is fed from permanent magnets, independent of terminal voltage | Around 3 × rated for several seconds, typically up to about 10 seconds |
Sustained fault current is what lets overcurrent devices with time delays operate. On sets that feed motor loads or long cables, PMG or auxiliary-winding excitation is usually specified for this reason. See overcurrent and short-circuit protection.
Worked example 1: a 500 kVA set (illustrative)
Rated current at 415 V is 696 A. With X″d 0.15, X′d 0.25 and Xd 2.0:
| Time after the fault | Current |
|---|---|
| First cycles | 696 ÷ 0.15 ≈ 4.6 kA |
| Around 0.1 to 0.3 s | 696 ÷ 0.25 ≈ 2.8 kA, falling |
| Steady, shunt excitation | 696 ÷ 2.0 ≈ 350 A, half of full load |
| Steady, PMG excitation | About 3 × 696 ≈ 2.1 kA for several seconds |
A feeder breaker with a short-time pickup of 1500 A would trip reliably on the PMG set. On the shunt-excited set it would trip only if the decaying current stayed above 1500 A for the whole short-time delay, which cannot be relied on.
Worked example 2: a 1000 kVA set, peak and earth faults (illustrative)
Rated current at 415 V is 1391 A. With X″d 0.14, negative-sequence reactance X2 0.15 and zero-sequence reactance X0 0.06, and the neutral solidly earthed:
| Fault | Formula (per unit) | Current |
|---|---|---|
| Three-phase | 1 ÷ X″d = 1 ÷ 0.14 ≈ 7.1 | About 9.9 kA |
| Phase to phase | √3 ÷ (X″d + X2) = 1.732 ÷ 0.29 ≈ 6.0 | About 8.3 kA |
| Phase to earth (solid neutral) | 3 ÷ (X″d + X2 + X0) = 3 ÷ 0.35 ≈ 8.6 | About 11.9 kA |
The earth fault is about 20% higher than the three-phase fault. That surprises many people, and it is why some generator neutrals are earthed through a resistor or reactor, and why breaker and busbar ratings must be checked for the earth-fault case too. The peak current in the first half-cycle, with an X/R ratio of about 10, is about κ × √2 × 9.9 kA ≈ 1.75 × 1.414 × 9.9 ≈ 24.5 kA. For the 11.9 kA earth fault the same factor gives about 29.4 kA, and the breaker’s making capacity must exceed the higher of the two peaks. For neutral arrangements, see earthing and neutral grounding.
Never assume a generator will clear a fault the way the grid does. If your set has a shunt-excited AVR, have the feeder protection checked against its decaying fault current before relying on it.
Parallel sets and motor contribution
- Parallel sets add their contributions at the common bus. Four identical 500 kVA sets give about four times the single-set current, around 18.6 kA initially. Breakers on a multi-set bus must be rated for the total.
- Running motors add their own short-lived contribution. On a generator-fed board this can be a large share of the first-cycle current. See motor contribution to fault current.
- Grid in parallel with generators (where permitted) adds the utility’s contribution to the generators’, which raises the duty on every breaker on the shared bus.
What it means for design
| Item | Which current to use |
|---|---|
| Breaker breaking capacity | Initial symmetrical current, with all sources and motors that can run together |
| Breaker making capacity and busbar forces | Peak current |
| Instantaneous and short-time pickups | The decaying current at the time the element must operate, on generator supply alone |
| Long-time and backup protection | Sustained current, which depends on the excitation system; consider voltage-restrained overcurrent (51V) |
| Cable withstand | I² × t up to the actual clearing time |
Study steps
- Obtain X″d, X′d, Xd, X2, X0, the time constants and the excitation type from the alternator data sheet for the exact frame.
- Model the generator with these values and the neutral earthing arrangement.
- Calculate the initial, peak, breaking and sustained currents for three-phase, phase-to-phase and earth faults.
- Plot the decaying generator current on the same chart as the protection curves.
- Repeat for every source combination: grid only, one set, all sets, and grid with sets if paralleling is allowed.
Data sheet extraction worksheet
| Quantity | Value | Source page or table |
|---|---|---|
| Rating (kVA) and voltage | ||
| X″d, X′d, Xd (per unit, on the stated base) | ||
| X2, X0 | ||
| T″d, T′d, armature time constant | ||
| Excitation type and sustained short-circuit current | ||
| Neutral earthing |
Check the base: reactances are sometimes quoted on the alternator’s own rating, which can be larger than the set’s rating. Convert them before use: X on the set’s base = X on the alternator’s base × (set kVA ÷ alternator kVA).
Worked example: one set, current against time (illustrative)
A 1250 kVA set at 415 V has a rated current of about 1739 A. Take a subtransient reactance of 0.12, a transient reactance of 0.25, time constants of about 0.03 s and 0.3 s, and permanent magnet excitation holding about three times rated current. The symmetrical fault current then falls as follows.
| Time after the fault | Fault current | What it matters for |
|---|---|---|
| 0 s | About 14.5 kA | Breaking and making duty, busbar forces |
| 0.02 s | About 10.7 kA | Instantaneous elements and fuses |
| 0.05 s | About 8.1 kA | Breaker contact parting |
| 0.1 s | About 6.7 kA | Short-time elements with small delays |
| 0.3 s | About 5.9 kA | Short-time elements graded for selectivity |
| 1 s | About 5.3 kA | Long-time protection and cable heating |
A short-time element set at 6.4 kA with a 0.3 s delay would pick up in the first tenth of a second and then drop out as the current falls below its setting, so it never trips. Protection on generator supply is set on the current that will still be flowing when the delay runs out, which is why the maker’s decrement curve, not the initial value, drives the settings.
Earth faults on a solidly earthed set
A single-phase-to-earth fault current is about three times the phase voltage divided by the sum of the positive, negative and zero-sequence reactances. Alternators have a low zero-sequence reactance, so with a subtransient reactance of 0.12, a negative-sequence reactance of about 0.13 and a zero-sequence reactance of about 0.05, the earth fault is about 3 ÷ 0.30 = 10 times rated current, against 8.3 times for a three-phase fault: about 20% higher. Some makers limit the earth fault current their windings may carry, and a neutral earthing reactor or resistor may then be required. The earthing study and the alternator data sheet decide.
What to take from the alternator data sheet
- Subtransient, transient and synchronous reactances, and the negative and zero-sequence reactances.
- Time constants for the subtransient and transient periods, and the armature time constant for the DC component.
- The short-circuit decrement curve, showing current against time for a three-phase fault.
- The sustained short-circuit current and how long the excitation system can hold it.
- Winding pitch, which affects third-harmonic current when neutrals are connected.
Values in the study are taken for the actual alternator frame and excitation option supplied, because they differ between frames of the same rating. See maximum and minimum fault current studies.
Common mistakes
- Treating the generator like the grid, with a steady fault current.
- Using reactances from another frame size, or on the wrong base.
- Rating breakers on the three-phase fault only, when the earth fault is higher.
- Setting protection on the initial current, which has gone by the time a delayed element operates.
- Overlooking the excitation type.
What to send us
Send the generator and alternator data sheets, the single-line diagram and the breaker and relay details. WhatsApp 98852 01608 or use the enquiry form. See also fault current from generators and reactance and short circuit.
Evidence note. Reactances and examples are typical values for illustration. Use the alternator maker’s data for the exact frame and the method of the applicable standard.
Questions engineers ask
How fast does a generator fault current fall?
For an illustrative 1250 kVA set at 415 V with permanent magnet excitation, about 14.5 kA at the instant of the fault falls to about 10.7 kA after 0.02 s, 8.1 kA after 0.05 s, 6.7 kA after 0.1 s, 5.9 kA after 0.3 s and about 5.3 kA after 1 s. Protection is set on the current still flowing when its delay runs out.
Can an earth fault on a generator exceed the three phase fault current?
Yes, on a solidly earthed set. Alternators have a low zero sequence reactance, so with reactances of about 0.12, 0.13 and 0.05 the earth fault is about 10 times rated current against 8.3 times for a three phase fault, about 20% higher. Where the maker limits winding earth fault current, a neutral earthing reactor or resistor may be needed.
Why does generator fault current decay?
Because the alternator flux, which drives the fault current, cannot be sustained by the field at the initial level. The current is first limited by the subtransient reactance, then the transient reactance as the damper and field currents decay, and finally by the synchronous reactance, unless the excitation system forces it up.
What does a PMG do?
A permanent magnet generator on the alternator shaft supplies excitation power independent of the output voltage. During a fault, when the output voltage collapses, it keeps powering the regulator, which can hold the fault current at about three times rated for several seconds, long enough for time delayed protection to operate.
Which value do I use for breaker rating?
The initial symmetrical current and its peak, which are the highest values, for breaking and making capacity and busbar withstand. The decayed values, from the maker decrement curve, are used to check that protection actually operates. Both cases are checked, often in different operating modes.
Do all generators have the same behaviour?
No. Reactances, time constants and excitation systems vary between makes and alternator frames, even at the same rating. Two sets of equal kVA can give different initial currents and very different sustained currents. Studies therefore use the data sheet of the actual alternator and excitation option.
Values are illustrative. Use the manufacturer’s data.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.