In short. When a fault pulls the voltage down, running motors briefly act as generators and feed current into the fault. An induction motor’s contribution starts at roughly its locked-rotor current, about five to seven times its rated current, and dies away within a few cycles. It adds to the first-cycle peak and to the duty breakers must make and break. On a grid-fed board it may add 10 to 20%. On a generator-fed board, where the source is weak, it can add more than half again.
Who this page is for: For engineers checking breaker ratings and protection on motor-heavy boards: know how much running motors add to fault current, and when it matters.
Key facts
- Running induction motors feed a fault with about their locked-rotor current: 5 to 7 times rated for one motor, about 5 times for a group.
- The contribution decays within a few cycles.
- Motors on conventional VFDs contribute almost nothing.
- IEC 60909 lets motors be neglected when their rated currents total no more than about 1% of the fault current without them.
- On a generator-fed board motors can add more than three-quarters again to the first-cycle current.
Why motors feed a fault
An induction motor’s rotor carries magnetic flux, and the motor and its load carry rotational energy. When the supply voltage collapses, the flux cannot vanish instantly and the rotor keeps turning, so the motor generates a voltage and drives current towards the fault. With no excitation to sustain it, the flux decays in a few cycles and so does the current. A synchronous motor has its own excitation and keeps contributing for longer, much like a generator.
How much, and for how long
| Motor type | Initial contribution | Duration |
|---|---|---|
| LV induction motor | About its locked-rotor current: 5 to 7 times rated for a single motor; about 5 times for a group of mixed LV motors | Decays in about one to a few cycles |
| Large HT induction motor | Rated current ÷ the motor’s sub-transient reactance, modelled individually | A few cycles |
| Synchronous motor | Similar to a generator of the same rating | Longer, sustained by excitation |
| Motor on a conventional VFD (diode front end) | Negligible; the drive does not pass current back to the supply | None |
| Motor on a regenerative or active-front-end drive | Limited by the drive; check the maker’s data | Short |
Because it decays so fast, motor contribution affects the peak current, the making duty and the initial breaking current much more than the later values that slower protection sees.
When it can be ignored
IEC 60909 allows motor contribution to be neglected where the sum of the motors’ rated currents is no more than about 1% of the initial short-circuit current calculated without them, which keeps their contribution below about 5%. For LV motor groups the standard’s usual modelling is an equivalent motor with a locked-rotor ratio of 5. On motor-heavy boards, such as pump houses, chiller plants, plant room and process MCCs, and on any board that can be fed from a generator, include it.
Worked example: the same board on grid and on generator (illustrative)
A motor control centre at 415 V has 400 kW of induction motors running together. At a typical power factor of 0.85 and efficiency of 0.92, their combined rated current is:
| Case | Source contribution | Motor contribution | Total initial current | Motors add |
|---|---|---|---|---|
| Grid, through a 1600 kVA transformer and the MCC feeder cables | About 20 kA at the MCC | 3.6 kA | About 23.6 kA | About 18% |
| One 500 kVA generator (X″d 0.15) | 696 ÷ 0.15 ≈ 4.6 kA | 3.6 kA | About 8.2 kA | About 78% |
On the grid the motors push the board’s fault level up modestly, which matters only if the breakers are already near their rating. On the generator the motors nearly double the first-cycle current. That helps the instantaneous elements pick up in the first cycles, but it decays quickly, so protection that must operate after the first few cycles still sees only the generator’s decaying current. Grading must be checked with and without the motor contribution.
If a board’s breakers are already close to their rated breaking capacity, do not add large direct-on-line motors or connect it to generators in parallel until the fault level has been recalculated with motor contribution included.
Where it matters
- Breaker making and breaking capacity on motor control centres and main boards near their rating.
- Peak current and busbar forces. The peak is about κ × √2 × the initial symmetrical current, with κ typically about 1.4 to 1.7 on LV boards and up to about 1.8 close to large transformers or generators.
- Arc-flash energy at motor-fed boards, since the contribution lasts through the clearing time of fast devices.
- Feeder protection, because motor current flows backwards through feeder breakers towards an upstream fault. Instantaneous and directional settings must not trip healthy feeders on this reverse current.
How to model it
- List motors by board, with ratings, starting methods and which run together in each study case.
- Exclude motors on conventional VFDs; treat regenerative drives from maker data.
- Model large HT motors individually with their own reactance; group LV motors per board.
- Run the maximum case with all running motors included, for equipment ratings.
- Run the minimum case without motor contribution, for protection sensitivity. See generator short-circuit contribution.
- State the grouping and the locked-rotor ratio in the study report.
Motor contribution worksheet
| Board | Running motor kW | Rated current (A) | Locked-rotor ratio | Contribution (kA) | On VFD (excluded) |
|---|---|---|---|---|---|
| MCC-1 | 5 | ||||
| MCC-2 | 5 | ||||
| Main LV board (total) |
How quickly the contribution fades (illustrative)
An induction motor’s contribution decays as its flux dies away, with a time constant of a few cycles. Taking the 3.6 kA of the example above and an illustrative time constant of 40 ms:
| Time after the fault | Working | Motor contribution |
|---|---|---|
| 0 ms | 3.6 | About 3.6 kA |
| 20 ms, one cycle | 3.6 × e−20 ÷ 40 | About 2.2 kA |
| 60 ms, three cycles | 3.6 × e−60 ÷ 40 | About 0.8 kA |
| 100 ms, five cycles | 3.6 × e−100 ÷ 40 | About 0.3 kA |
The contribution is fully present at the first peak, which is why it counts for making capacity, but a breaker whose contacts part after several cycles sees much less of it. Short-circuit methods apply decay factors to motor contribution when they calculate breaking current, using the motor’s rating, poles and the contact parting time. See IEC short-circuit calculation engineering.
Motors and earth faults
Induction motors are normally connected in delta, or in star with the star point not earthed, so they have no path for zero-sequence current. They therefore add almost nothing to an earth fault current flowing to earth at the fault, although they do support the phase voltages briefly. The earth fault study can usually leave them out, while the three-phase study must include them. This is one reason the earth fault and three-phase fault levels on a motor-heavy board can differ more than on a board without motors.
Large high-voltage motors
A 1000 kW motor at 11 kV, with an efficiency of about 95% and a power factor of about 0.9, has a rated current of about 1000 ÷ (1.732 × 11 × 0.9 × 0.95) ≈ 61 A, and contributes roughly six times that, about 370 A, at the start of a fault. That is small compared with a 13 kA utility fault level, but several such motors on one board, or a weak source, change the result. Each large HV motor is modelled individually with its own subtransient reactance and X/R, because its contribution and decay differ from those of small motor groups.
Effects on protection
- Instantaneous elements on the faulted feeder see a little more current in the first cycles, which can speed operation slightly.
- Undervoltage relays on motor feeders must not trip while the motors feed a nearby fault that other protection is clearing, unless that is intended.
- Directional elements, where used, must account for current flowing from motor boards toward a fault elsewhere.
- Fuses clearing in the first half cycle see the full motor contribution in their let-through.
Data the study needs
For motor groups: the total rated kW or current running at the time of maximum fault, by board, and the share on drives. For large motors: rated power, voltage, current, efficiency, power factor, locked-rotor current or subtransient reactance, X/R and number of poles. Motors that never run at the same time should not all be counted; the operating modes from the load schedule decide which motors are running in each case. See electrical load list and load schedule.
Why it matters most on generator supply
On a generator-fed board the source is weak, so the motors can supply a large share of the first-cycle current, as the worked example above shows. That share helps fuses and instantaneous elements in the first cycles, but it disappears before slower protection acts, leaving only the generator’s decaying current. Protection on generator supply is therefore graded on the generator current alone.
Common mistakes
- Ignoring motors on boards dominated by motor load.
- Including motor contribution in the minimum-fault case used for protection sensitivity.
- Counting motors on conventional VFDs as contributors.
- Counting standby motors that never run with the duty motors.
- Checking breaker ratings on grid supply only, when the board can also be paralleled with generators.
What to send us
Send the motor schedule with ratings, starters and running patterns, the single-line diagram, the transformer and generator data and the breaker ratings. WhatsApp 98852 01608 or use the enquiry form. See also the load list and load schedule guide.
Evidence note. Ratios and examples are typical values for illustration; the study must use the motor and equipment makers’ data and the method of the applicable standard.
Questions engineers ask
How quickly does motor contribution to a fault die away?
Within a few cycles. With an illustrative time constant of 40 ms, 3.6 kA at the instant of the fault falls to about 2.2 kA after one cycle, 0.8 kA after three and 0.3 kA after five. It counts fully for making capacity and peak withstand, but breakers that part their contacts after several cycles see much less of it.
Do induction motors contribute to earth fault current?
Very little. Induction motors are normally connected in delta, or in star with an unearthed star point, so they have no path for zero sequence current and add almost nothing to the current flowing to earth at a fault. The three phase fault study must include them; the earth fault study can usually leave them out.
Do all motors feed a fault?
Running induction and synchronous motors connected directly to the supply do. Motors on conventional drives with diode front ends contribute almost nothing, and motors that are stopped contribute nothing. Regenerative and active front end drives can contribute a limited current set by the drive, which the maker data states.
How long does it last?
For induction motors, a few cycles, as the rotor flux decays without excitation to sustain it. Large motors decay more slowly than small ones. Synchronous motors keep contributing for longer, because their own excitation sustains the flux, behaving much like a generator of similar rating.
Does it affect relay settings?
It affects instantaneous and directional elements, which act in the first cycles, and the let through of fuses. It has little effect on time delayed elements that act after the contribution has decayed. Undervoltage relays on motor feeders must also be set to avoid tripping during faults elsewhere.
Can I lump all motors together?
For low voltage motor groups, yes: an equivalent motor per board, with a locked rotor ratio of about five, is the usual approach. Large high voltage motors, synchronous motors and motors that dominate a board are modelled individually, because their contribution and decay differ from those of a group.
Values are illustrative. Use motor data from the schedule.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.