Fault Current

How a diesel generator contributes fault current, why it decays from sub-transient to sustained levels, and how to estimate it from alternator reactance.

In short. A diesel generator supplies far less fault current than the DISCOM transformer it replaces, and the current decays within cycles. The first-cycle value is set by the alternator’s sub-transient reactance and is typically five to ten times rated current. Within a second it falls to a sustained value set by the excitation system: about three times rated current with PMG excitation, much less with shunt excitation. Protection must be assessed against this decaying contribution.

Why fault current on a generator is a different problem

On a utility supply the source behind the 415 V board is a large transformer on an 11 kV network with a fault level in the hundreds of MVA. The fault current is high and roughly constant for as long as the fault persists. A generator is a rotating machine whose internal reactance is not constant. In the first cycle after a short circuit the damper and field windings hold the flux, so the current is high.

As the damper currents die away the effective reactance rises and the current falls. As the field flux decays it falls again, and what remains depends on whether the excitation system can force field current while terminal voltage is collapsed. The same board therefore sees two different fault environments depending on the source, and the protection must work in both.

The three periods of a generator fault

PeriodGoverning reactanceTypical durationTypical magnitudeWhat it decides
Sub-transientX″d, usually 0.10 to 0.20 puFirst 1 to 3 cycles5 to 10 times rated currentBreaker making capacity, peak forces on busbars, instantaneous relay pick-up
TransientX′d, usually 0.15 to 0.35 puUp to about 1 second3 to 6 times rated currentBreaker breaking capacity, short-time relay elements
SustainedXd with excitation responseUntil clearedAbout 3 times rated for PMG or forced excitation for up to 10 seconds; may fall below rated for shunt excitationTime-delayed overcurrent, fuses, downstream MCCB thermal elements

The values are typical of low-voltage salient-pole alternators on diesel sets and must be confirmed from the datasheet for any real study. The alternator reactance and short-circuit page explains where each figure comes from.

Estimating the first-cycle current

I″k = In ÷ X″d

Here I″k is the initial symmetrical three-phase fault current at the terminals, In is the alternator rated current and X″d is the saturated sub-transient reactance in per unit on the alternator’s own base. Rated current is kVA multiplied by 1000 and divided by √3 times the line voltage. Consider a 500 kVA, 415 V set with a quoted X″d of 0.14 per unit (illustrative).

Rated current is 696 A, so the initial symmetrical fault current is about 4970 A, roughly 5 kA. The asymmetrical first-half-cycle peak can be 1.5 to 1.8 times higher because of DC offset, which is the figure for breaker making duty and busbar bracing. A 1000 kVA, 5% impedance utility transformer on the same board delivers about 28 kA sustained; the generator supplies less than a fifth of that, and only for a few cycles. The generator short-circuit contribution page and the IEC short-circuit calculation page take the same method through to a full study under IEC 60909.

What the excitation system does to the sustained value

The sustained fault current is where generators differ most. A shunt-excited alternator takes its field power from its own terminals. When a close-up fault pulls the voltage down, the AVR loses its supply and the field collapses, so the sustained current may fall below rated current within a second or two. A time-delayed overcurrent relay set above rated current then never operates, and the fault persists until something burns.

A PMG-excited alternator, or one with an auxiliary winding for fault support, keeps the AVR supplied regardless of terminal voltage and holds around three times rated current for up to ten seconds, long enough for downstream protection to clear the fault. For any generator feeding a distribution system with more than one level of protection, we regard PMG or equivalent excitation as the correct specification. The PMG excitation page covers the hardware.

Fault current away from the generator terminals

The figures above are terminal values. Every metre of cable between the generator and the fault adds impedance and reduces the current further, so a 415 V fault at the end of a long run to a remote board may draw little more than a heavy overload from the generator. The protective device there must still see enough current to operate within the time the cable can tolerate. The cable sizing guide deals with cable thermal withstand, and the protection coordination guide explains how to confirm that the minimum fault current still reaches the device’s pick-up. Minimum fault current, not maximum, is usually the limiting case on generator supply.

Multiple generators and other sources

When sets run in parallel their contributions add at the common bus. Four 500 kVA sets with the same X″d deliver about four times the single-set first-cycle current, approaching 20 kA in the example above, and the switchgear must be rated for the largest combination that can be online. Large induction motors also feed current back into a fault for a few cycles, and UPS or BESS inverters contribute a small, current-limited amount. All of these belong in the maximum-duty case and are excluded from the minimum-duty case used for protection sensitivity.

Which value to use for which decision

Related photographs and videos

Electrical fault behaviour.

Worked example: fault current from a 500 kVA set (illustrative)

A 500 kVA set at 415 V has a full-load current of about 696 A. With a subtransient reactance of about 0.12 per unit, the first-cycle fault current at the terminals is roughly 696 divided by 0.12, about 5.8 kA symmetrical, and more with the asymmetric offset in the first half-cycle. Over the next few cycles the current falls as the alternator field responds. With a permanent magnet generator or excitation support, the sustained current may settle at about three times full load, near 2.1 kA. Without support it can fall close to or below full-load current, too little to trip many breakers quickly.

What the protection check compares

ValueUsed for
First-cycle current from all sourcesSwitchgear withstand and breaking rating
Sustained generator currentWhether breakers and fuses trip on generator alone
Earth fault current with the chosen earthingEarth fault protection settings
Fault current at the far end of long feedersWhether remote faults are cleared in time

Data to ask the maker for

The alternator data sheet with subtransient, transient and synchronous reactances, the time constants, the decrement curve showing current against time for a three-phase fault, and the excitation type. These let the protection study use real values instead of rules of thumb.

Faults far from the generator

Cable impedance reduces fault current further at remote boards. A breaker that trips correctly at the main board may not trip quickly at the end of a long feeder on generator supply. The study checks these remote points, and the cure may be lower settings, residual current devices or larger cables.

Common mistakes

What to send us

Send a photograph of the alternator nameplate and, if you have it, the alternator datasheet showing X″d, X′d, Xd, the time constants and the excitation type. Add the single-line diagram with cable sizes and lengths, the number of sets that can run in parallel, the ratings of the existing breakers and any fault level letter from the DISCOM. Send these through the application engineering enquiry and we will tell you whether a short-circuit study is needed.

Questions engineers ask

How is first-cycle generator fault current estimated?

Divide full-load current by subtransient reactance. In the illustrative case, a 500 kVA set at 415 V with about 696 A and 0.12 per unit gives roughly 5.8 kA symmetrical at the terminals, with more in the first half-cycle from the asymmetric offset, which switchgear ratings must cover.

What sustained fault current does a generator provide?

With a permanent magnet generator or excitation support, often about three times full-load current, near 2.1 kA for a 500 kVA set. Without support it can fall close to or below full-load current, too little to trip many breakers quickly on generator alone, which the protection study must check.

Which fault current values does a protection study use?

First-cycle current from all sources for switchgear withstand and breaking, sustained generator current for tripping on generator alone, earth fault current with the chosen earthing for earth fault settings, and fault current at remote boards to confirm long feeders are cleared in time on every source.

What alternator data is needed for fault current studies?

The data sheet with subtransient, transient and synchronous reactances, the time constants, the decrement curve showing current against time for a three-phase fault, and the excitation type. With these the study uses real values for the actual machine instead of rules of thumb, which can be badly wrong.

How much fault current does a 500 kVA diesel generator produce?

With a typical sub-transient reactance of 0.12 to 0.16 per unit the first-cycle symmetrical current is about 4 to 6 kA at 415 V, falling within a second towards roughly three times rated current, or about 2 kA, if the alternator has PMG excitation. A shunt-excited alternator may sustain much less. The exact figures must come from the alternator datasheet.

Why does generator fault current decrease during the fault?

The alternator’s effective reactance increases as the damper winding currents and then the field flux decay after the fault begins. The current therefore falls from the sub-transient value through the transient value to a sustained level set by how hard the excitation system can force the field while the terminal voltage is depressed.

Can I use the same breakers on generator and utility supply?

Usually the breakers are rated for the higher utility fault level and are therefore adequate for the generator in terms of making and breaking duty. The question is whether their trip settings still operate on the much lower generator fault current, especially at the end of long cables. That requires a coordination check for the generator operating mode.

Is an earth fault on a generator smaller than a three-phase fault?

Not necessarily. A three-phase fault is limited by the positive-sequence reactances described here, while a single-phase-to-earth fault is limited by the sum of positive, negative and zero-sequence impedances plus any neutral earthing resistor. On a solidly earthed low-voltage alternator the zero-sequence reactance is small, so the earth-fault current can exceed the three-phase value.