Reactance & Short-Circuit Performance

What subtransient, transient and synchronous reactance mean for a generator alternator, how fault current is estimated, and why the decrement curve matters.

In short. A generator alternator’s short-circuit behaviour is described by three reactances, each valid for a different time window: subtransient for the first few cycles, transient for the next second or so, and synchronous for steady state. Initial fault current is roughly rated current divided by per-unit subtransient reactance, typically six to ten times rated, and it then decays along a decrement curve shaped by the excitation system. Protection on generator supply must be set against that curve.

Three reactances, three time windows

When a short circuit is applied to a running alternator, the current does not settle instantly. Flux trapped in the damper bars opposes the change for a few cycles, then flux in the field winding opposes it for longer, and only after the field flux has adjusted does the machine reach steady state. Each stage is modelled with an internal voltage behind a reactance.

QuantitySymbolTypical per-unit range on the alternator’s own baseTime windowUsed for
Subtransient reactanceXd″0.10 to 0.20First 1 to 3 cyclesPeak and initial symmetrical fault current, breaker making duty, voltage dip at the instant of motor starting
Transient reactanceXd‘0.15 to 0.30Roughly 0.1 to 1.5 sMotor-starting voltage dip after the first cycles, breaker breaking duty, relay operation in the short-time region
Synchronous reactanceXd1.5 to 3.5Steady stateSustained fault current with constant excitation, voltage regulation, reactive capability
Negative-sequence reactanceX2Close to Xd″Unbalanced faultsLine-to-line and line-to-earth fault current, rotor heating under unbalance
Zero-sequence reactanceX00.02 to 0.10Earth faultsEarth fault current with a solidly earthed neutral

The ranges are typical of four-pole brushless alternators from a few hundred kVA to a few MVA. Values for a specific machine come from the manufacturer’s data sheet and are quoted on the alternator’s own kVA base, which is not always the genset’s rated kVA.

Estimating the initial fault current

For a three-phase fault at the terminals with the machine at rated voltage, the initial symmetrical fault current is approximated as follows.

Ik″ = Irated ÷ Xd″

Here Ik″ is the initial symmetrical short-circuit current in amperes, Irated is the alternator’s rated line current in amperes, and Xd″ is the per-unit subtransient reactance on the same kVA base. As a worked example (illustrative), a 500 kVA alternator at 415 V has a rated current of 500,000 ÷ (1.732 × 415) ≈ 696 A. With Xd″ of 0.14 per unit, the initial fault current is 696 ÷ 0.14 ≈ 4970 A, or about seven times rated.

The first peak of the asymmetrical current can reach roughly 1.8 times the square root of two times that value, close to 12,600 A, which is the figure that matters for the making capacity of the breaker and the mechanical bracing of the busbars. These are terminal-fault figures; cable impedance reduces them, which is what makes faults at the end of long feeders hard to detect.

If the reactance is quoted on a different base from the one you are using, convert it first: the per-unit value scales with the kVA base, so 0.14 on a 550 kVA alternator base becomes 0.127 on a 500 kVA genset base. Omitting this step is a common source of a 10% error.

The decrement curve and why excitation matters

The initial current decays within tens of milliseconds to the transient value, which decays over a second or so towards the synchronous value. With constant excitation the synchronous value is rated current divided by Xd, which for 2.5 per unit is only 40% of rated current, less than normal load current, and no overcurrent device will see it as a fault.

What rescues the situation is the excitation system. A regulator with an independent supply, from a permanent magnet generator or an auxiliary winding, drives the field to its ceiling and holds around three times rated current for several seconds. A shunt-excited machine cannot, because its regulator supply has collapsed with the terminal voltage. The manufacturer’s decrement curve shows current against time for each excitation type, and it is this curve, not the single subtransient figure, that must be overlaid on the downstream time-current characteristics. The excitation architectures are compared under PMG and excitation.

Consequences for protection on generator supply

Most low-voltage installations in India are designed around a utility fault level of 25 to 50 kA at the main switchboard. Fed by a 500 kVA generator, the same board sees about 5 kA for a few cycles and 2 kA at best thereafter. Several things follow.

A coordination study that was done for utility supply is therefore not valid for generator supply, and a site with an automatic changeover needs both cases checked. The study method is described under fault current and protection coordination, and the generator’s contribution to a system-wide study under generator short-circuit contribution.

Where motors come in

Running induction motors feed a fault for a few cycles as their rotor flux decays, contributing initially about their own locked-rotor current. On a site with a large motor load this adds materially to the first-cycle current the generator breaker must handle, and it is included in a proper study. It does not help with the sustained current problem, because motor contribution is gone within a few cycles.

Fault level when sets run in parallel

The estimate above gives the fault current one set can deliver. A plant of several sets paralleled on one bus delivers the sum, and the consequence is easy to miss: the switchgear that was correctly rated for the first set may not be rated for the plant it has become. Taking a 1000 kVA set at 415 V, whose full-load current is 1391 A, across the range of subtransient reactance real machines have:

Sets in parallelAt 0.15 per unitAt 0.12 per unitAt 0.10 per unit
19.3 kA11.6 kA13.9 kA
218.5 kA23.2 kA27.8 kA
327.8 kA34.8 kA41.7 kA
437.1 kA46.4 kA55.6 kA, past a 50 kA board
655.6 kA69.6 kA83.5 kA

Read across a row and the importance of the real reactance appears: the same four-set plant is anywhere from 37 to 56 kA depending on a figure from the alternator datasheet. That is the practical answer to whether typical values are good enough. For a single set feeding a board rated well above its fault level they usually are; for a multi-set plant near a switchgear rating they are not, and the difference between 0.10 and 0.15 is the difference between a compliant board and one that cannot safely clear its own worst fault.

The danger in this table is that it grows one set at a time. A plant designed for three sets, with switchgear rated comfortably above 35 kA, gets a fourth set added years later to meet a load increase, and nobody reopens the fault study because nothing about the board has changed. The board has not changed; its duty has. Every set added to a common bus is a switchgear question first and a capacity question second.

Two further contributions push the figure up and are worth listing before a board is rated. If the plant ever parallels with the utility, even briefly during a closed transition, the utility’s fault level adds to the generators’ for that period, and it is usually the larger of the two. And large motors on the bus feed fault current back for the first few cycles as their stored magnetic energy discharges. Neither appears in a calculation done on the generators alone, and both arrive at exactly the moment the breaker is trying to interrupt.

The figures above are the initial symmetrical current. The breaker also has to survive closing onto that fault, where the first peak is higher still because of the offset, and that making duty is a separate rating that has to be checked against its own figure — a board can pass on breaking and fail on making, and the second is the one that is forgotten.

Common mistakes

What to send us

Send the alternator nameplate, the manufacturer’s data sheet or the reactance values and time constants if you have them, the single-line diagram showing the generator breaker and downstream devices with their ratings and settings, and the cable sizes and lengths of the main feeders. If the set is paralleled or has an automatic changeover, say so. Send your application details and we will advise whether a generator-case coordination study is needed and what data is missing.

Questions engineers ask

Does adding a generator to a paralleled plant change the switchgear rating needed?

Yes, and it is the change most often missed. Fault current from sets on a common bus adds, so a 1000 kVA set at 415 volts that delivers about 11.6 kiloamps alone makes a four-set plant about 46 kiloamps, and up to 56 if the machines have a low subtransient reactance. A board rated comfortably for three sets may not be rated for four. Every set added is a switchgear question before it is a capacity question.

What adds to generator fault current that a set-only calculation misses?

Two things. If the plant ever parallels with the utility, even briefly during a closed transition, the utility fault level adds for that period and is usually the larger contribution. And large motors on the bus feed current back into a fault for the first few cycles as their stored magnetic energy discharges. Both arrive at exactly the moment the breaker is trying to interrupt, and neither appears in a calculation done on the generators alone.

Is a lower subtransient reactance better?

It depends on the aim. Lower reactance gives higher initial fault current, which helps protection operate, and a smaller instantaneous voltage dip on motor starting. It also raises the breaker making duty and the forces on busbars. Manufacturers choose a balance, and the designer works with the value given.

Why does my 1000 kVA generator trip on a fault that a 100 A breaker should have cleared?

Because the fault current at that breaker, after cable impedance and after the first few cycles, was probably below its magnetic trip threshold, and the thermal element needed longer than the generator protection allowed. A coordination check against the decrement curve, and in some cases a PMG upgrade or revised settings, resolves it.

What is the difference between the generator fault level and the utility fault level?

The utility fault level at a 415 V board is set by the upstream transformer and network and is commonly 25 to 50 kA. The generator fault level is set by the alternator reactance and is roughly six to ten times the generator’s rated current, decaying quickly. The two can differ by a factor of ten or more at the same busbar.

Do I need manufacturer data or can I use typical values?

Typical values are acceptable for preliminary screening of small sets with simple distribution. For any installation with downstream coordination, paralleled sets, large motors or a critical load, use the data sheet values for the actual machine, because the typical range spans a factor of two.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 19 October 2026.