In short. Every site has a range of fault currents, not one number. The maximum, near the strongest source with all permitted sources connected, decides whether switchgear and cables can survive. The minimum, at the far end of a long feeder on one generator, decides whether protection operates quickly enough. A design must pass both, and they often occur in different operating modes.
Who this page is for: For consultants and protection engineers on sites with generators, long feeders or UPS and battery systems.
Key facts
- Maximum fault: strongest supply, all permitted sources, fault close to the source.
- Minimum fault: weakest supply, fewest sources, fault at the far end.
- Only sources that can actually be connected together are added.
- Hot cable resistance lowers minimum fault current.
- Earth faults need their own maximum and minimum.
- Below the instantaneous setting, clearing can be slow or may not happen.
Worked example: a 160 A feeder, 120 m of 35 mm² copper (illustrative)
| Case | Working | Fault current | Check |
|---|---|---|---|
| Maximum: mains, fault at main board | From the board study | about 21.7 kA | 36 kA breaker: pass |
| Low case: one 500 kVA generator, three-phase fault at feeder end | Generator 0.069 Ω (transient reactance 0.2 per unit) + hot cable 0.078 Ω resistance, 0.010 Ω reactance; total about 0.111 Ω; 240 V ÷ 0.111 Ω | about 2.2 kA | Instantaneous at 10 × 160 = 1.6 kA: trips |
| Same, if the generator falls to its sustained value | From the maker’s decrement curve | Lower | Must still clear before the current decays below the trip setting |
The feeder passes both checks for a three-phase fault. A phase-to-phase fault is about 0.87 × 2.2 = 1.9 kA, close to the 1.6 kA setting plus tolerance, and a phase-to-earth fault is lower again because the return conductor adds impedance; both must be checked separately. A 300 m run on the same cable would drop below 1.6 kA and need a lower setting or a larger cable. See cable sizing and coordination.
Do not prove protection with maximum fault current. A breaker that trips instantly on mains can take seconds, or never trip, on one generator at the end of a long cable.
Cases to build
| Case | Used for |
|---|---|
| Strong mains, transformers in parallel if permitted, motors running | Switchgear and busbar duty |
| All permitted generators in parallel | Generator bus duty |
| One generator, feeder ends | Protection sensitivity |
| UPS on inverter. See inverter fault current | Branch protection |
Fault range sheet
Both ends of the range at every point that matters on one installation: a 2000 kVA transformer on a 350 MVA utility with two 1250 kVA generators. The example above works one 160 A feeder on 35 mm² through its low case and finds it close to its setting; this sheet puts two feeders of different lengths side by side on a larger site, and the comparison is the finding — one of them clears comfortably and the other does not clear at all.
| Location | Maximum kA | Equipment rating | Minimum kA | Trip setting |
|---|---|---|---|---|
| Main board | 45.3 on mains with motors | 50 kA breaking | 5.2 on one generator, sustained | Incomer short-time 6.4 kA at 0.3 s. 5.2 kA is below it, so this case clears on the long-time curve |
| Sub-board 1 | 31 on mains with motors | 36 kA breaking | 3.4 on one generator, sustained | Incomer short-time 2.5 kA. Picks up |
| Sub-board 2 | 14 on mains with motors | 25 kA breaking | 2.3 on one generator, sustained | Incomer short-time 1.26 kA. Picks up |
| Feeder F1 end, 250 A, 90 m of 95 mm² | 42.3 at its origin | 50 kA breaking at the origin | 5.8 (5811 A) three-phase, one generator | Instantaneous at 10 × 250 = 2500 A. Trips, with better than twice the margin |
| Feeder F1 end, phase to phase | — | — | 5.1, being 0.87 × 5811 = 5056 A | 2500 A. Still trips |
| Feeder F2 end, 400 A, 160 m of 95 mm² | 42.3 at its origin | 50 kA breaking at the origin | 4.2 (4188 A) three-phase, one generator | Instantaneous at 10 × 400 = 4000 A. Only 5% above the setting, which is inside the device tolerance |
| Feeder F2 end, phase to phase | — | — | 3.6, being 0.87 × 4188 = 3644 A | 4000 A. Does not trip instantaneously. Instantaneous lowered to 6 × 400 = 2400 A and proved by injection |
The two feeder rows are built the same way and come out differently, which is the point of putting them next to each other. One 1250 kVA generator at a transient reactance of 0.2 per unit has an impedance of 415 squared divided by 1,250,000, times 0.2 — about 0.028 ohm, all reactance.
F1 adds 90 m of 95 mm² copper, which hot is about 0.022 ohm of resistance and 0.007 ohm of reactance, so the total impedance is the vector sum of 0.022 and 0.035, which is 0.0413 ohm. Dividing 240 V by that gives 5811 A, or 5.8 kA. F2 adds 160 m of the same cable: 0.040 ohm of resistance and 0.013 ohm of reactance, a total of 0.0573 ohm, and 4188 A, or 4.2 kA.
Then the two settings pull in opposite directions. F1 is a 250 A feeder, so its instantaneous element sits at 2500 A and a 5.8 kA fault is more than twice it. F2 is a 400 A feeder, so its element sits at 4000 A and a 4.2 kA fault is 5% above it — which is no margin at all once device tolerance is counted.
Take the phase-to-phase case, which is about 0.87 of the three-phase value, and F2 drops to 3644 A: below its own instantaneous setting, so the fault would sit on the long-time curve for seconds on a generator whose current is already decaying. The longer cable and the larger breaker both work against it, and either one alone would have been survivable.
The main board row carries the same shape of problem one level up. A sustained generator fault of 5.2 kA is below the 3200 A incomer’s 6.4 kA short-time pickup, so a fault on the main board in single-generator mode is cleared by the long-time curve rather than in 0.3 seconds. Nothing is damaged by that — the equipment ratings are untroubled by 5.2 kA — but it is the row the arc-flash study then has to work from, and it is invisible to any study that only computes maximum fault levels.
Three rules keep a range sheet honest. Only sources that the switchgear permits together appear in the maximum column, which on this site means the mains and the generators never add. The minimum column uses hot cable resistance rather than the twenty-degree figure, because a cable that has been carrying load is the condition a fault actually finds. And the phase-to-phase and phase-to-earth cases get their own rows rather than a footnote, because on both feeders here the three-phase figure passes and it is the lower cases that do not.
What changes between the two cases
| Parameter | Maximum case | Minimum case |
|---|---|---|
| Voltage factor at low voltage | 1.05 or 1.10 | 0.95 |
| Utility fault level | Highest stated | Lowest stated |
| Transformer impedance | Low end of tolerance | Nominal or high end |
| Sources | All that can be connected together | Fewest that can supply the load |
| Motors | Included | Excluded |
| Cable temperature | 20 °C | At the end of the fault, hotter |
Hot cables carry less fault current
Copper resistance rises by about 0.39% per degree. A cable at 70 °C has about 1 + 0.00393 × 50 ≈ 1.20 times its resistance at 20 °C, and higher again during the fault. On long final circuits, where the cable dominates the loop impedance, that 20% increase lowers the minimum fault current by nearly as much, which can take it below the instantaneous trip of the protection. The minimum case therefore uses the hot resistance.
Worked example: the earth fault loop on a final circuit (illustrative)
A 32 A, B-curve breaker on a 230 V final circuit trips instantaneously at about 5 times its rating, 160 A. To reach that current with the minimum voltage factor of 0.95, the earth fault loop impedance must not exceed about 230 × 0.95 ÷ 160 ≈ 1.37 Ω, including the source, the phase conductor and the protective conductor, at operating temperature. On grid supply this is usually easy; on generator supply the source impedance is higher and long circuits may fail. Where they do, the answer is a residual current device, a larger protective conductor or a shorter circuit. See cable sizing and voltage drop studies.
Arcing faults sit below the bolted minimum
The minimum bolted fault assumes a solid connection. A real fault often arcs, and at low voltage the arc resistance lowers the current further, commonly to something like half of the bolted value. Protection that only just picks up on the minimum bolted current may not pick up on the arcing current at all. Where the arc flash study shows long clearing times, the minimum case is rechecked with the arcing current, and settings or devices changed so that arcing faults clear quickly. See arc flash study architecture.
Sustained generator current sets the floor
On generator supply the current that protection sees after the first few tenths of a second depends on the excitation. With a permanent magnet or auxiliary excitation system, the regulator can hold about three times rated current for several seconds, enough for time-delayed protection to operate. Without it, the current can fall below rated, and protection set above rated current may never trip. The minimum case uses the maker’s decrement curve for the actual set and the clearing time of each device on it.
Common mistakes
- Minimum taken as a percentage of maximum.
- Generator mode not studied.
- Cold cable resistance for minimum fault.
- Earth faults left out.
What to send us
Send the single-line diagram with cable lengths, generator data and breaker settings. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. Values are illustrative.
Questions engineers ask
How much does cable temperature change the minimum fault current?
Copper resistance rises by about 0.39% per degree, so a cable at 70 C has about 1.20 times its resistance at 20 C, and more during the fault. On long final circuits, where the cable dominates the loop impedance, that lowers the minimum fault current by close to 20%, which can take it below the instantaneous trip.
What earth fault loop impedance does a 32 A B curve breaker need?
It trips instantaneously at about five times rating, 160 A. With a minimum voltage factor of 0.95 on a 230 V circuit, the loop impedance must not exceed about 230 times 0.95 divided by 160, about 1.37 ohm, at operating temperature. Generator supply adds source impedance, so long circuits may need a residual current device.
Which case is more important?
Both, for different reasons. The maximum case decides whether switchgear, busbars and cables survive a fault without damage. The minimum case decides whether protection operates quickly enough to clear the fault at all. A design that passes only one has a serious gap, and the two often occur in different operating modes.
Why exclude motors in the minimum case?
Because motors may not be running when the fault occurs, and their contribution decays within a few cycles anyway. Including them would overstate the current that time delayed protection sees. The minimum case assumes the weakest realistic conditions, so motors are left out unless they are certain to be running.
What if one setting cannot cover both?
Use setting groups selected by the operating mode, a maintenance or generator setting, devices with lower instantaneous settings on long circuits, residual current devices for earth faults, or larger cables to raise the minimum fault current. The study shows which option keeps both selectivity and sensitivity.
Does the minimum case include arc resistance?
The bolted minimum does not, but real faults often arc, and at low voltage the arcing current can be around half the bolted value. Where clearing time matters, as in arc flash studies, protection is also checked against the arcing current, so that arcing faults are cleared quickly as well.
This guide gives general principles. Cases should follow the chosen standard.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.