Arc-Flash Study Architecture Guide

How an arc-flash study is built: data, fault cases, clearing times, incident energy method, boundaries, mitigation scenarios, labels and the generator-specific traps that raise energy.

In short. Arc-flash energy depends on arcing current, clearing time, equipment layout and working distance, not on fault level alone. A weaker source can give a lower arcing current that drops below a breaker’s fast trip, so the arc lasts much longer and releases more energy. A study must therefore check every operating mode, including generator and bypass, and use the settings actually installed.

Who this page is for: For facility managers, safety officers and electrical engineers responsible for safe work on switchboards and generator panels.

Key facts

  • Arcing current is lower than bolted fault current.
  • Clearing time is often the biggest single factor.
  • The worst case can be the lowest fault current, not the highest.
  • Generator mode often gives the longest clearing times.
  • Results are specific to each board and each mode.
  • Any change to settings, transformers or generators means repeating the study.

Worked example: one main board, two sources (illustrative)

CaseArcing currentBreaker operates inClearing timeCurrent × time
Mains, 21.7 kA boltedabout 12 kAShort-time region0.3 s3.6 kA·s
One generator, 5.8 kA bolted initially, falling with timeabout 3.5 kALong-time regionabout 4 s14 kA·s

Arc energy rises roughly with arcing current × time, so the generator case is about four times worse even though its fault current is a quarter of the mains value. The generator figures must be taken from the maker’s decrement curve, because the current falls during those 4 seconds. A maintenance setting that gives fast tripping while people work on the board was added for generator mode. See coordination.

Do not assume the highest fault level gives the worst arc flash. Check the generator and lowest-current cases, and never shorten clearing time by changing settings without rechecking coordination.

Ways to reduce arc energy

MethodEffect
Maintenance mode settingFast trip while work is done; must be switched back
Zone selective interlockingFast upstream trip for faults in its own zone
Busbar differential or arc detectionVery fast clearing inside the board
Remote racking and switchingKeeps people away; energy unchanged

See busbar protection and short-circuit studies.

Arc-flash case sheet

Every board and every mode on one installation: a 2000 kVA transformer on a 350 MVA utility with two 1250 kVA generators. The example above contrasts two cases on one board and finds the generator case about four times worse; this sheet runs six cases across three boards on a larger site, where the ratio comes out differently and the last row is the answer rather than the problem. Arcing current is taken as roughly half the bolted value, and the clearing time from where that current lands on the device curve.

BoardModeArcing kAClearing timeAction
Main boardMains, with motors. 45.3 kA bolted240.3 s, on the incomer short-time element24 × 0.3 = 7.2 kA·s. The baseline case, and not the worst
Main boardBoth generators. 29.0 kA bolted150.3 s, on the short-time element15 × 0.3 = 4.5 kA·s. The mildest case on the sheet
Main boardOne generator, sustained. 5.2 kA bolted2.8About 5 s. 5.2 kA is below the 6.4 kA short-time pickup, so the long-time curve clears it2.8 × 5 = 14 kA·s. The worst case on the site, at the lowest current on the sheet
Sub-board 1One generator, sustained. 3.4 kA bolted1.8About 6 s1.8 × 6 = 10.8 kA·s
Sub-board 2One generator, sustained. 2.3 kA bolted1.3About 8 s1.3 × 8 = 10.4 kA·s
Main boardOne generator, with the maintenance setting enabled2.80.1 s2.8 × 0.1 = 0.28 kA·s. Fifty times better than the same case without it
     
     

Read the last column rather than the third and the sheet inverts. The highest arcing current on it is 24 kA and the worst case is 2.8 kA, because a current nine times smaller is allowed to burn seventeen times longer. The main board in single-generator mode is about twice as severe as the same board at full mains fault level, and the two sub-boards in that mode are worse than the mains case too — at 1.3 kA, the lowest bolted figure anywhere on the site, sub-board 2 is still 10.4 kA·s against the main board’s 7.2.

The cause is in the fourth column and it is a protection setting, not an arc. A 3200 A incomer has its short-time element at about 6.4 kA; a sustained single-generator fault is 5.2 kA, which is below it, so the element never picks up and the long-time curve takes seconds. Every one of the three bad rows is the same mechanism at a different board.

That also means the fix is a setting rather than equipment, which is why the sheet ends with a sixth row instead of a recommendation: a maintenance setting that drops the instantaneous element while people are working on the board takes the main board case from 14 kA·s to 0.28, a fiftyfold improvement, and costs nothing but the discipline of enabling and disabling it.

Two cautions about the figures themselves. The generator rows have to come from the maker’s decrement curve rather than from a single number, because the current is falling throughout those five to eight seconds — a calculation that holds 5.2 kA constant for five seconds overstates the energy, and one that uses the subtransient 14.5 kA understates the duration badly.

And the arcing-current assumption of roughly half the bolted value is a working figure for a low-voltage board; on a specific enclosure with specific gaps it has to come from the method being used, which is also why every row names its bolted current so the assumption can be re-applied if the method changes.

One last point about who the sheet is for. Three of these six rows describe a condition that only exists while the site is running on one generator — which is to say, during an outage, which is exactly when somebody is most likely to be at the board. A study that reported a single figure per board, taken at the maximum fault level, would have reported this site as safer at every one of its three boards than it actually is at the moment it matters most.

The inputs each board needs

InputSourceWhy it matters
Bolted fault current at the board, every modeShort-circuit studySets the arcing current
Upstream device and its settingsSettings schedule, verified on siteSets the clearing time
Electrode configuration and gapBoard constructionVertical bars in a box focus energy toward the worker
Enclosure sizeMeasuredSmaller boxes concentrate the arc
Working distanceTask and equipment typeEnergy rises steeply as distance falls
VoltageSystem dataChanges arcing current and arc stability

The settings must be the ones actually installed. A study built on the design settings, when the site has since changed them, gives labels that understate the hazard. See existing electrical system and brownfield study.

Incident energy, the boundary and protective clothing

The study reports incident energy at the working distance, in cal/cm². About 1.2 cal/cm² is the level at which bare skin can suffer a second-degree burn, so the arc flash boundary is the distance at which the energy falls to that value. Inside the boundary, workers wear arc-rated clothing with a rating above the calculated energy. A common working distance for low-voltage switchboards is about 455 mm; for some tasks it is less, and the energy is then higher.

Distance has a strong effect. In an enclosed board, energy rises roughly with the inverse of distance raised to a power between about 1.5 and 2, so halving the distance raises the energy about three to four times. Tools that let the worker stand further back, and remote operation, reduce exposure without changing the system.

The order of controls

  1. Remove the hazard: isolate and prove dead before work. Most tasks do not need live work.
  2. Reduce the energy: faster protection, maintenance settings, zone interlocking, arc detection.
  3. Increase distance: remote racking, remote switching, longer tools.
  4. Procedures and permits: who may work live, on what, and why.
  5. Protective clothing: the last line, rated above the calculated energy.

Protective clothing appears last because it limits injury but does not prevent the arc. A study that leads only to heavier clothing has missed the cheaper and safer options above it.

What the label must tell the worker

Label itemPurpose
Nominal voltageShock hazard and approach limits
Incident energy and working distanceSelects protective clothing
Arc flash boundaryWhere protection becomes necessary
Operating mode the figure applies toGenerator mode may differ from grid mode
Date and study referenceShows whether the label is still valid

Where the worst case is generator mode, the label states it, or the board carries the worst figure of all modes. A label showing only the grid case on a board that is often on generator supply misleads the person reading it.

Generator panels and AMF boards

Generator output boxes, AMF panels and changeover boards are often worked on during tests and maintenance, when the set is running alone. They see the lowest fault current on the site, and their protection, often the generator breaker’s long-time element, can take seconds to clear an arcing fault. These boards frequently carry the highest incident energy on the site, and need either a maintenance setting on the generator breaker or a rule that work is done only with the set stopped and locked out. See generator short-circuit contribution.

Keeping the study current

Review the study whenever a transformer, generator, protective device or setting changes, whenever the utility fault level changes, and at a regular interval, commonly no more than about five years. Each review checks that the installed settings match the study and that labels are present and legible. A study is only as good as its match to the board it describes.

Common mistakes

  • Mains case only.
  • Settings from drawings, not from the breakers.
  • Old labels kept after changes.
  • Maintenance mode left on.

What to send us

Send the single-line diagram, breaker settings and generator data. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Values are illustrative; arc-flash results need a full study.

Questions engineers ask

How much does working distance change arc flash energy?

A great deal. In an enclosed board, incident energy rises roughly with the inverse of distance raised to a power between about 1.5 and 2, so halving the working distance raises the energy about three to four times. A common working distance for low voltage switchboards is about 455 mm; closer tasks need their own figure.

Why are generator and AMF panels often the worst arc flash locations?

They see the lowest fault current on the site when the set runs alone, so their protection, often the generator breaker long time element, can take seconds to clear an arcing fault. Incident energy rises with clearing time, so these panels need a maintenance setting on the generator breaker or a rule that work is done with the set stopped and locked out.

What is the arc-flash boundary?

The distance from the arc at which the incident energy falls to about 1.2 cal per sq cm, the level at which bare skin can suffer a second degree burn. Anyone closer than the boundary while equipment is live and exposed needs arc rated protective clothing suited to the calculated energy, and must be qualified for that work.

Why does a lower fault current sometimes raise energy?

Because the arcing current may fall below the fast trip threshold of the upstream breaker, so it clears on the slow long time curve. Energy rises with time, so a current several times smaller can burn many times longer and release more energy. Generator mode is the usual example.

How often should studies be refreshed?

Whenever a transformer, generator, protective device or setting changes, or the utility fault level changes, and at a regular interval, commonly no more than about five years. Each review checks that installed settings match the study, that labels are present, legible and correct, and that workers know which operating mode each label describes.

Is software required?

For anything beyond a single simple board, yes in practice. The calculation methods involve electrode configuration, enclosure size, arcing current variation and device curves at each board in every mode. Software applies them consistently, but its results are only as good as the verified site data and settings put into it.

This guide gives general principles. Arc-flash studies must be done by qualified engineers.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.