In short. A generator can have enough kW to run a motor and still fail to start it. A direct-on-line start draws about six times running current at low power factor. That pulls the alternator voltage down and loads the engine suddenly, so both voltage and frequency dip. The cure is usually a better starting method, unloaded starts and a starting sequence, rather than a much larger generator.
Who this page is for: For plant engineers and consultants starting motors, pumps, chillers and crushers on generator supply.
Key facts
- Starting kVA = 1.732 × voltage × starting current.
- Voltage dip depends on starting kVA and the alternator’s transient reactance.
- Star-delta cuts starting current and torque to about one third.
- Soft starters limit current; set too low, the motor stalls.
- Variable speed drives start gently but add harmonics.
- Start the largest motor before the other motors, once the base load is stable.
Worked example: 75 kW motor on a 320 kVA set carrying 120 kW (illustrative)
| Starting method | Starting current | Starting kVA | Estimated dip |
|---|---|---|---|
| Direct-on-line, 6 × 130 A | 780 A | about 561 kVA | about 26% |
| Soft starter, 3.5 × 130 A | 455 A | about 327 kVA | about 17% |
| Star-delta, 2 × 130 A | 260 A | about 187 kVA | about 10% |
Estimated dip = starting kVA × 0.2 ÷ (320 + starting kVA × 0.2), using a transient reactance of 0.2 per unit from the alternator data. The plant limit was 20%. Star-delta with an unloaded motor start was chosen. The engine’s response to the kW step was confirmed with the maker’s transient data. See motor starting studies.
Do not judge a generator by running kW alone. Check voltage dip and frequency dip for the largest motor start, with the other loads already connected.
Options in order of cost
- Start unloaded, then load the machine.
- Start the largest motor first, then sequence the others.
- Star-delta, soft starter or variable speed drive.
- Alternator with better transient performance.
- Larger set. See generator sizing.
Motor start sheet
Every motor start on one installation — a 2000 kVA transformer with two 1250 kVA generators in N+1 — checked against one 1250 kVA set carrying the 885 kW generator-mode load. The example above takes one 75 kW motor on a 320 kVA set through three starting methods; this sheet takes five motors on a set four times larger, which moves every dip but not the conclusion. Dips are calculated with the same expression: starting kVA times 0.2, divided by the generator kVA plus starting kVA times 0.2.
| Motor | kW | Starting method | Starting kVA | Dip | Start order |
|---|---|---|---|---|---|
| M-02 motor, 185 A running | 110 | Direct on line, 6 × = 1110 A | 798 | 11%. Past the plant’s 10% limit | Rejected |
| M-02 motor | 110 | Soft start, 3 × = 555 A | 399 | 6% | 1, once the UPS and lighting base load is stable |
| M-02 motor | 110 | Star-delta, 2 × = 370 A | 266 | 4%. Rejected on torque: the motor cannot accelerate on one third of its starting torque | Rejected |
| M-01 chilled water pump, 78 A running | 45 | Star-delta, 2 × = 156 A | 112 | 2% | 2, then the second pump 10 s later |
| AHU-01 fan, 54 A running | 30 | Direct on line, 6 × = 324 A | 233 | 4% | 3, one fan at a time, 5 s apart |
| M-03 cooling tower fan, 40 A running | 22 | Direct on line, 6 × = 240 A | 173 | 3% | 4, all four within 20 s |
| M-04 effluent pump, 129 A running | 75 | Soft start, 3 × = 387 A | 278 | 4% if it were started | Not started on generator. It is a shed load |
The first three rows are the same motor three ways, and putting them on the same sheet is what makes the choice defensible. Direct on line gives 1110 A, which at 415 V is 798 kVA, and 798 times 0.2 divided by 1250 plus 798 times 0.2 is 11% — just past a 10% limit, which is the most awkward kind of failure because it invites somebody to argue about the limit.
Star-delta would give the smallest dip on the sheet at 4%, and it was rejected anyway: a motor against pressure cannot accelerate on a third of its starting torque, and a motor that stalls in star is worse than a dip. The soft starter at three times running current lands at 6% with torque under control, which is why it appears in the load list as a constraint rather than an option.
The sixth column carries as much of the engineering as the fifth. Every dip on this sheet is calculated for one motor starting against a stable base load — so the order has to secure that condition. The UPS and the lighting come up first because they are not motor loads and they settle quickly.
The largest motor goes next, while the set has the most headroom. The two pumps are separated by 10 seconds and the six air handling fans by 5, because six 233 kVA starts arriving together would be a 1400 kVA step that no entry on this sheet describes. The individual dips are all small; it is only the sequencing that keeps them individual.
Two cautions about what the dip figure does not cover. It is a voltage dip from the alternator’s transient reactance, and it says nothing about frequency: the engine sees a kW step and its governor takes time to recover, which has to be checked against the maker’s transient response data rather than calculated here. And the figures assume one set. On both sets in parallel the same 1110 A direct-on-line start gives a dip of about 6% rather than 11% — which is exactly the trap, because the plant will pass its commissioning test on two sets and fail on the night one set is out.
The last row is on the sheet although the motor never starts on generator, and for the same reason the load list keeps it at zero kW: it records that somebody checked. If the effluent pump is ever reclassified as essential, its 4% dip is already known and the only new question is whether the 885 kW load can carry another 75.
The frequency side of a motor start
A starting motor draws mostly reactive current, but not only reactive. At a starting power factor of about 0.3, the 798 kVA start on the sheet above is also a real power step of about 0.3 × 798 ≈ 240 kW, plus the losses in the motor and cables, arriving in one step on an engine already carrying the base load.
That step makes the frequency dip at the same moment as the voltage. The alternator’s reactance sets the voltage dip; the engine and governor set the frequency dip. A set can pass one check and fail the other, so the study checks both against the maker’s load acceptance data for the actual engine.
How the regulator protects the engine
Most generator regulators include an under-frequency roll-off: when the speed falls below a knee point, often about 47 to 48 Hz on a 50 Hz set, the regulator lowers the voltage in proportion to the speed. Lower voltage means less load on the engine, which helps it recover rather than stall. The price is a deeper voltage dip during a heavy start. The knee point and the slope are settings; set too high, every start becomes a deep voltage dip; set too low, the engine can be dragged down. They are reviewed with the motor starting study, not left at factory defaults.
Excitation systems and heavy starts
| Excitation | Behaviour during a large start | Suits |
|---|---|---|
| Self-excited, powered from the main output | Excitation power falls with the voltage it is trying to restore, so recovery is slower | Moderate starts relative to the set rating |
| Permanent magnet generator | Excitation power stays available whatever the output voltage, so the regulator can force recovery | Large direct-on-line starts, distorted loads, fault current support |
| Auxiliary winding | Similar benefit to a permanent magnet generator in many designs | As above, depending on the make |
A larger alternator frame on the same engine lowers the transient reactance on the load base, which reduces the voltage dip without changing the engine. Where the voltage dip decides the size but the engine has spare capacity, this is often cheaper than a larger set.
Starting the machine unloaded
- Centrifugal pumps: start against a partly closed discharge valve, which reduces the power drawn while the motor accelerates, then open it.
- Fans: start with dampers or inlet vanes closed, then open them once at speed.
- Conveyors and mixers: start empty where the process allows, and load only after the motor reaches speed.
- Machines that start against pressure: use the unloading device fitted for that purpose, so that the motor accelerates without the working load.
An unloaded start shortens the acceleration time and the time the dip lasts, and lets a reduced-voltage starter work where it would otherwise stall the machine.
Restarts after a transfer
After a grid failure and transfer to the generator, motors whose contactors held in, or whose controls restart them automatically, all try to start at once. That combined start can be several times the largest single start on the sheet above. Every motor that restarts automatically needs a restart delay, set so that the starts follow the order the study chose, and motors still spinning down need time for their residual voltage to decay before they reconnect. See automatic load restoration and restart control.
Proving the start on site
| Record during the test start | Compared with |
|---|---|
| Lowest voltage at the generator and at the motor | Study prediction and the plant limit |
| Lowest frequency and recovery time | Maker load acceptance data and the load tolerance |
| Motor current and time to reach speed | Motor safe stall time |
| Other loads that dropped out or alarmed | Their ride-through settings |
Use a power quality analyser with fast recording, because a dip lasting a few hundred milliseconds is invisible on ordinary instruments. If the measured dip is worse than predicted, check the cable, the regulator settings and the base load before blaming the set.
Common mistakes
- Sizing from running kW.
- Soft starter current limit set too low.
- Loaded motor starts.
- All motors restarting together after transfer.
What to send us
Send motor ratings, starting methods and the generator data. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. Values are illustrative.
Questions engineers ask
Why does a motor start make the generator frequency dip as well as the voltage?
Starting current is mostly reactive but not entirely. At a starting power factor of about 0.3, a 798 kVA start is also a real power step of about 240 kW, plus losses, arriving at once on the engine. The alternator reactance sets the voltage dip and the engine and governor set the frequency dip, so both are checked against the maker load acceptance data.
Does a permanent magnet excitation system help with large motor starts?
Yes. A self-excited alternator draws its excitation power from its own output, so it weakens as the voltage dips. A permanent magnet generator keeps excitation power available whatever the output voltage, so the regulator can force faster recovery after a large start and support fault current. A larger alternator frame on the same engine also reduces the voltage dip.
Why does my generator stall on a motor it can carry running?
Because starting draws about six times running current at a low power factor, which pulls the alternator voltage down and loads the engine suddenly. The motor torque falls with the square of the voltage, the frequency dips as the engine takes the step, and the motor may never reach speed. Running kW says nothing about this transient.
Does a bigger generator always fix it?
Not always, and it is usually the most expensive answer. A better starting method, an unloaded start, starting the largest motor first, a larger alternator frame on the same engine, or permanent magnet excitation often solve the problem at lower cost. A much larger set may then run lightly loaded for years.
What is under-frequency roll-off?
A regulator function that lowers the output voltage in proportion to speed when the frequency falls below a knee point, often about 47 to 48 Hz on a 50 Hz set. Lower voltage reduces the load on the engine and helps it recover, at the cost of a deeper voltage dip. The knee and slope are settings to review.
Can the motor be started with load connected?
Sometimes, if the motor torque at the reduced voltage still exceeds the load torque at every speed. Starting unloaded, against a partly closed valve, with dampers closed or with the machine empty, shortens the start and reduces the dip, and lets reduced voltage starters work where they would otherwise stall the machine.
This guide gives general principles. Confirm with manufacturer data and simulation.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.