Motor Starting and Voltage-Dip Studies Guide

How to study motor starting: starting current and torque, source and cable impedance, voltage dip at motor and bus, acceptance limits, starting methods and sequencing.

In short. A starting induction motor draws five to eight times its running current at a low power factor, and that current pulls the voltage down across the source, the transformer and the cable. A motor-starting study checks two things. At the motor: will it still produce enough torque to accelerate? At the bus: will contactors, drives, UPS inputs and controls ride through the dip? It also compares starting methods. On generator supply the source is far weaker than the grid, so the same motor that starts easily on the grid can stall a generator.

Who this page is for: For engineers and plant teams starting large motors, especially on generator supply, and for anyone whose motor hums, trips or drops other loads when it starts.

Key facts

  • Screening formula: dip ≈ starting kVA ÷ (starting kVA + source short-circuit kVA).
  • A generator’s effective short-circuit kVA for a motor start is roughly its kVA ÷ X′d.
  • Motor torque falls with the square of voltage: a 20% dip leaves about 64% torque.
  • Many sites aim to keep the bus above about 80 to 85% during a start; contactors may drop out near 70%.
  • Star-delta cuts starting current to about one-third; soft starters to about 2.5 to 4 times running current.
  • Start the largest motor first, while the set is lightly loaded.

What happens when a motor starts

At standstill an induction motor behaves like a transformer with its secondary short-circuited. It draws its locked-rotor current, typically five to eight times full-load current, at a power factor of about 0.2 to 0.3. As it accelerates, the current falls and the power factor rises. The voltage dip is this starting current multiplied by the impedance between the source and the motor. While the voltage is low, the motor’s torque is low, so a deep dip both slows the start and lengthens the time the dip lasts.

The screening estimate

Dip ≈ Sstart ÷ (Sstart + Ssc) · for a generator, Ssc ≈ generator kVA ÷ X′d

Worked example: a 90 kW motor on grid and generator (illustrative)

Starting kVA is the locked-rotor multiple times the motor’s running kVA. A 90 kW motor at 415 V draws about 155 A at full load, which is about 1.732 × 415 × 155 ≈ 111 kVA. At seven times, its starting demand is about 780 kVA.

SourceEffective short-circuit kVADip with a 90 kW direct-on-line start (780 kVA)
Grid through a strong transformerAbout 8000 kVA780 ÷ 8780 ≈ 9%
500 kVA generator, X′d 0.25500 ÷ 0.25 = 2000 kVA780 ÷ 2780 ≈ 28%: contactors may drop and the motor may stall
Same generator, soft starter at about 3 × running current (about 335 kVA)2000 kVA335 ÷ 2335 ≈ 14%: acceptable for most sites

The screening ignores cable impedance and the voltage regulator’s response, so it is for a first decision only. Full studies use the motor’s torque curve, the load’s torque curve, inertia and the generator’s transient model. See the voltage dip guide.

Why the dip matters to the motor

Torque at reduced voltage ≈ rated-voltage torque × (V ÷ Vrated)²

At a 20% dip, the motor produces about 0.8² = 64% of its normal starting torque. A pump or fan, whose load torque is low at low speed, may still accelerate. A loaded conveyor, crusher or reciprocating-type machine may not, and the motor will hum and draw high current until its protection trips.

Starting methods compared

MethodStarting current (× running)Starting torqueNotes
Direct-on-line5 to 8FullSimplest; largest dip
Star-deltaAbout one-third of DOLAbout one-third of DOLSwitching transient at changeover; light-torque loads
AutotransformerReduced by the tap ratio squaredSame reductionSelectable taps (typically 50, 65 and 80%) match torque to the load; closed transition avoids the star-delta switching transient
Soft starterAbout 2.5 to 4Adjustable rampGood for pumps and fans; limited breakaway torque
Variable frequency driveAbout 1 to 1.5Full torque at low speedLowest dip; adds harmonics. See non-linear loads

Acceptance checks

CheckTypical criterion
Motor acceleratesMotor torque exceeds load torque at every speed during the dip
Acceleration timeBelow the motor’s safe stall time with margin
Bus voltageOften not below about 80 to 85%; set by the most sensitive load
Contactors and relaysDo not drop out; many drop near 70%
Generator recoveryVoltage and frequency back within limits in a few seconds
ProtectionUndervoltage and overload settings allow the start

Do not start a large direct-on-line motor on a generator that is already heavily loaded. Start the largest motor first with the set lightly loaded, and stagger the rest so that each start has recovered before the next.

Sequencing on generator supply

  1. Start the largest motor first, when the set carries the least other load.
  2. Add the other motors in steps, each after the voltage and frequency have recovered, typically a few seconds apart.
  3. Use start permissives and timers in the controller or PLC so that restarts after a changeover do not all happen at once.
  4. Re-check the sequence whenever a large motor is added.

See large motor starting on diesel generators.

Motor starting worksheet

ItemValue
Motor kW, full-load current and locked-rotor multiple 
Starting method and setting 
Starting kVA 
Source: grid fault level or generator kVA and X′d 
Estimated dip (%) and the limit for this bus 
Other loads running at the time of the start 

Worked example: how long the start takes (illustrative)

The time to accelerate is roughly the total inertia times the final speed, divided by the average accelerating torque, which is motor torque minus load torque. Take a 90 kW, four-pole motor driving a fan, with a combined inertia of about 10 kg·m² and a full speed of 1480 rpm, about 155 rad/s. Rated torque is 90,000 ÷ 155 ≈ 581 N·m.

CaseAverage accelerating torqueWorkingStarting time
Full voltageAbout 465 N·m, 0.8 of rated10 × 155 ÷ 465About 3.3 s
Voltage held near 80%About 232 N·m, 0.4 of rated10 × 155 ÷ 232About 6.7 s

The deeper dip doubles the starting time, and the motor draws starting current, heating its rotor, for twice as long. If the motor’s safe stall time when hot is, say, 12 s, the second case still passes, but with far less margin, and a high-inertia load or a weaker source could take it past the limit. That is why the study checks starting time against the motor’s thermal limit, not only the voltage dip.

The cable adds its own dip

The screening estimate gives the dip at the source bus. The motor terminals see that dip plus the drop in the motor cable, which is large during starting because the current is high and its power factor low. A 90 kW motor drawing about 1085 A at a power factor of 0.3 through 150 m of 70 mm² copper, with a resistance of about 0.268 Ω per km and a reactance of about 0.075 Ω per km, loses about 1.732 × 1085 × 0.15 × (0.268 × 0.3 + 0.075 × 0.95) ≈ 43 V, about 10% of 415 V, in the cable alone.

Added to a 9% dip at the bus, the motor sees nearly 20% less voltage and only about two thirds of its torque. A larger cable, or a starter that reduces the current, helps the motor; it does nothing for the other loads on the bus. See cable sizing and voltage drop studies.

Reduced-voltage starting by tap

Autotransformer tapMotor voltageLine current and torque, as a fraction of direct on line
50%0.50.5² = 0.25
65%0.650.65² ≈ 0.42
80%0.80.8² = 0.64

Line current and torque fall together, by the square of the tap. The tap is chosen as the lowest that still gives the load enough torque to accelerate within the allowed time.

Protection settings that must allow the start

  • Motor overload: its trip class, often 10, 20 or 30, must allow the starting time with margin; a class 10 relay on a high-inertia start may trip before the motor reaches speed.
  • Short-circuit protection: instantaneous settings must sit above the peak starting current, including the first-cycle asymmetry, which can be well above the rms locked-rotor current.
  • Undervoltage relays on other loads: need a time delay longer than the dip, or they will drop loads every time a large motor starts.
  • Generator protection: overcurrent and undervoltage settings must ride through the start without tripping the set.

Repeated starts and starting duty

Each start heats the motor far more than running does. Makers state how many starts are allowed per hour, cold and hot, and a minimum time between them. Processes that cycle a large motor on and off, or a restart sequence that tries again and again after a failed transfer, can exceed that limit and damage the rotor. The study lists the starting duty of each large motor and, where starts are frequent, considers a soft starter or a drive, which both reduce the heating and the dip.

When a screening check is not enough

SituationWhy a dynamic study is needed
Motor kVA is a large share of the source, especially on a generatorThe source voltage and frequency both move, and the screening ignores the regulator and governor
High-inertia loads such as large fans, crushers and centrifugesStarting time and rotor heating decide the result, not the dip alone
Loads with high breakaway torque, such as loaded conveyors and reciprocating pumpsThe motor may not break away at reduced voltage
Several large motors restarting after a transferTheir dips and recoveries interact

A dynamic study models the motor and load torque curves, the inertia, the source impedance and, on generator supply, the alternator, regulator, engine and governor, step by step through the start. See large motor starting on diesel generators.

Data the study needs from the motor maker

Rated output, voltage, current, efficiency and power factor; locked-rotor current and its power factor; the torque-speed and current-speed curves; rotor inertia; hot and cold safe stall times; and the allowed starts per hour. For the driven machine: its torque-speed curve and inertia. With these, the study replaces typical values with the real motor, and the result can be trusted for a design decision.

Common mistakes

  • Checking only the steady-state kVA.
  • Mixing amps and kVA in the starting calculation.
  • Ignoring the load’s torque during acceleration.
  • Assuming the generator behaves like the grid.
  • Starting several motors together after a changeover.

What to send us

Send the motor data sheets or nameplates, the starter types, the source details and what else runs during the start. WhatsApp 98852 01608 or use the enquiry form.

Evidence note. The screening formula and examples are for first decisions; final designs need motor and generator data and, for large motors, a dynamic study.

Questions engineers ask

How much does the motor cable add to the starting voltage dip?

Often a lot. A 90 kW motor drawing about 1085 A at 0.3 power factor through 150 m of 70 mm² copper loses about 43 V, about 10%, in the cable alone. With a 9% dip at the bus, the motor sees nearly 20% less voltage and only about two thirds of its torque.

How does a deeper voltage dip affect the starting time?

Accelerating torque falls with the square of voltage, so starting time rises. An illustrative 90 kW fan with 10 kg m2 of inertia accelerates in about 3.3 s at full voltage but about 6.7 s with the voltage near 80%. The motor carries starting current twice as long, so starting time is checked against its hot safe stall time.

What dip is acceptable?

It depends on the most sensitive load on the bus and on the motor itself. Many sites keep the bus above about 80 to 85% during a start, because contactors may drop out near 70% and drives or UPS units may trip earlier. The motor also needs enough voltage to accelerate its load within its safe stall time.

Why does the motor hum and not start?

Because at the reduced voltage its torque, which falls with the square of voltage, is below the torque the load needs to break away or accelerate. The motor sits at low speed drawing high current, which deepens the dip further, until its protection trips. Reducing the dip or the load torque at start solves it.

Is a soft starter always best?

No. A soft starter reduces current and dip, but also reduces starting torque, so loads with high breakaway torque may not start. Star delta suits light torque loads, autotransformers allow the tap to suit the load, and a variable speed drive gives full torque at low current but adds harmonics and cost.

Does cable length matter?

Yes. The motor cable carries the full starting current at a low power factor, so a long or small cable adds a large voltage drop of its own, on top of the dip at the source bus. The motor terminal voltage, which sets its torque, is the bus voltage minus that drop.

Values are illustrative screening figures. Use motor data and dynamic simulation for design.