Reactive Power and Power-Factor Studies Guide

How to study reactive power: kW, kVAr and kVA relationships, power-factor targets, capacitor sizing, effects on generators and transformers, and the risks of leading power factor and resonance.

In short. Reactive power does no useful work, but it loads cables, transformers and generator alternators. A reactive power study finds where kVAr is needed, how much correction is justified and how the system behaves on generator supply. Too much capacitance there can push a lightly loaded set to a leading power factor and unstable voltage, while a very low lagging power factor can load the alternator beyond its kVA rating.

Who this page is for: For plant engineers and consultants dealing with power factor, transformer and generator loading.

Key facts

  • kVA² = kW² + kVAr².
  • Correction needed = kW × (tan φ₁ − tan φ₂).
  • Better power factor frees transformer and cable capacity.
  • Generators are rated in kVA at about 0.8 power factor; very low power factor overloads the alternator.
  • Leading power factor on a generator can cause loss of voltage control.
  • Harmonics change how capacitors behave; check resonance.

Worked example: freeing transformer capacity (illustrative)

ItemBeforeAfter correction to 0.97
Load800 kW at 0.78800 kW at 0.97
kVA = kW ÷ power factorabout 1026 kVAabout 825 kVA
Transformer 1000 kVAOverloadedAbout 82% loaded
Correction = 800 × (tan φ₁ − tan φ₂)800 × (0.80 − 0.25) ≈ 440 kVAr
On generator, lightly loaded at 200 kWCapacitors switched by steps or disconnected so power factor stays lagging

Correction avoided a transformer upgrade. The generator case was handled by limiting capacitor steps on generator supply. See kW and kVAr.

Do not leave fixed capacitors connected to a lightly loaded generator. The set can go to a leading power factor, lose voltage control and trip; control capacitor steps on generator supply.

What the study covers

  • Load power factor by area and by time.
  • Correction location: central, group or individual.
  • Behaviour on generator supply at light and full load.
  • Harmonics and resonance. See harmonic studies and harmonics.
  • Filters where needed. See filter studies.

See load list and maximum demand.

Reactive power sheet

The reactive survey for one installation, area by area: a 2000 kVA transformer with two 1250 kVA generators in N+1, 1104 kW in mains mode and 885 kW on generator. The example above corrects a site from 0.78 to 0.97 and avoids a transformer upgrade; this sheet reaches the opposite conclusion on a larger site, and the opposite conclusion is the more useful one to see worked through — because the proposal was declined on arithmetic rather than on judgement.

AreakWPower factorkVAr neededGenerator behaviour checked
M-01 chilled water pumps900.8653Runs on generator. No correction proposed
M-02 process compressed-air plant1100.8859Runs on generator. No correction proposed
M-03 cooling tower fans880.8555Runs on generator
AHU-01 air handling1620.85100Runs on generator
L-01 lighting700.9523Runs on generator
U-01 UPS input3650.9952Runs on generator. This is the line that sets the site’s power factor
Generator mode8850.933342949 kVA, so 76% of one 1250 kVA set
Mains mode, with the shed loads added11040.9364141179 kVA, so 59% of the 2000 kVA transformer
Proposed 300 kVAr fixed bank—0.995 on mains−300Declined. On mains it frees 69 kVA on a transformer already at 59%; on one generator it leaves only 42 kVAr lagging, which is too close to leading
     
     

Every kVAr figure is the area’s kW times the tangent of its angle, and the totals are the sums: 342 kVAr against 885 kW gives a power factor of 0.933 and 949 kVA, and adding back the shed loads gives 414 kVAr against 1104 kW, 0.936 and 1179 kVA. Before rounding the generator-mode figure is 342.7, which is why the demand comes out at 949 kVA either way.

A site at 0.936 has nothing wrong with its power factor, and the reason is sitting in the sixth row: the UPS input is 365 kW, a third of the whole load, at a power factor of 0.99. A rectifier that good drags the average up far enough to cover a plant full of motors at 0.85.

The last row is the output of the study and it is a refusal. A 300 kVAr bank would take the mains power factor to 0.995 and the demand from 1179 to 1110 kVA — 69 kVA freed on a transformer that is 59% loaded, which buys nothing anybody needs.

And on one generator the same bank would leave 342 minus 300, so 42 kVAr of lagging reactive load against 885 kW: still lagging, but with so little margin that shedding one air handling unit would tip the set into leading power factor, where an alternator loses voltage control. The correction is not wrong because capacitors are bad; it is wrong because this site has nothing to correct and a generator mode that punishes overcorrection.

The fifth column is why that was caught. Had the sheet carried only a mains-mode total, a 300 kVAr bank would have looked harmless and faintly virtuous. Checking each row against generator behaviour forces the question of what the bank does when two thirds of the load has been shed — and on a site where shedding is designed in, the answer changes by a factor the mains case never reveals. If a bank were ever justified here it would have to be switched in steps, with the steps disabled on generator supply.

One more reading of the sheet is worth taking before leaving it. The fourth column is a requirement, not a measurement: it says how many kVAr each area is drawing, and the sum of those is what the supply has to carry. Nothing on the sheet says any of it is wasteful, because reactive load is not waste — motors need magnetising current and will draw it whatever anybody prefers.

What correction does is move where that current comes from, closer to the load, and the only reason to do it is a constraint somewhere upstream. This site has no such constraint, and a sheet that recorded only power factors without the kVA and the loading percentages beside them would never have shown that.

One thing this sheet does not do, and should not be read as doing: it says nothing about harmonics. The UPS rectifier and the soft starter both inject current harmonics, and capacitors interact with them in ways that a kVAr calculation cannot see — a bank that is correctly sized at the fundamental can still find a resonance with the supply impedance. On this site that question never arose because no bank was fitted. On a site where one is, it is a separate study and it has to be done before the capacitors are ordered, not after they start failing.

Correction needed per kW (illustrative)

The kVAr needed to raise the power factor is the kW times the difference of the tangents of the two angles.

FromTotan φ₁ − tan φ₂kVAr per 100 kW
0.700.951.020 − 0.329About 69
0.780.950.802 − 0.329About 47
0.800.950.750 − 0.329About 42
0.850.970.620 − 0.251About 37

The last few hundredths of power factor cost the most kVAr and free the least kVA, which is why a target near 0.95 to 0.98 is usual and correction to unity rarely pays.

Where to put the correction

LocationBenefitCaution
Central bank at the main boardFewest units, automatic control, easy maintenanceCables to the loads still carry the reactive current
Group banks at sub-boardsRelieves the main cables as wellMore units to control and maintain
Individual capacitors at large motorsSwitches with the motor; relieves its feederMust not exceed the motor’s no-load magnetising kVAr

A capacitor at a motor that is larger than the motor’s no-load magnetising requirement can keep the motor excited after it is switched off, so it generates a voltage while it runs down. That can damage the motor and endanger anyone working on it, and it causes severe transients if the motor is reconnected while still spinning. A common rule keeps such capacitors below about 90% of the no-load magnetising kVAr.

What the alternator can supply and absorb

An alternator’s capability chart shows how much kVAr it can deliver at each kW: supplying reactive power is limited by field heating, and absorbing it, at a leading power factor, by stability and end-winding heating. Many alternators can absorb far less reactive power than they can supply. A 1250 kVA set carrying 200 kW of light load with a 300 kVAr fixed bank and 100 kVAr of lagging load is asked to absorb about 200 kVAr, which may sit outside its capability, with voltage rising and the regulator losing control. The study plots each generator case on the maker’s chart.

Settings for automatic capacitor control

  • Target power factor, slightly lagging, so the bank never drives the site leading.
  • Step sizes small enough to follow the load without hunting between steps.
  • A reconnection delay long enough for each step to discharge before it is switched again, as the capacitor maker specifies.
  • A generator signal from the changeover that blocks or limits steps whenever the generator supplies the load.
  • An alarm for steps that fail to switch or for persistent leading power factor.

Power factor and the electricity bill

Where the supply is billed on kVA or kVAh, or carries power factor terms, a low power factor raises the bill directly. The study compares the cost of correction with the saving from the supply terms and the capacity freed in transformers, cables and generators. On sites where the load already runs near 0.95, as in the reactive power sheet above, correction may not pay at all, and the right answer is to leave it alone.

Common mistakes

  • Fixed capacitors on generator supply.
  • Correction sized for peak load only.
  • No harmonic check.
  • Generator rated in kW only.

What to send us

Send load and power factor recordings and the generator rating. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Values are illustrative.

Questions engineers ask

How much kVAr is needed to correct power factor?

The kW times the difference between the tangents of the two angles. Correcting from 0.78 to 0.95 needs about 47 kVAr per 100 kW, from 0.80 to 0.95 about 42, and from 0.85 to 0.97 about 37. The last few hundredths of power factor cost the most kVAr and free the least kVA, so targets near 0.95 to 0.98 are usual.

Why must a capacitor at a motor be kept small?

A capacitor larger than the motor no load magnetising requirement can keep the motor self excited after it is switched off, so it generates voltage while running down. That can damage the motor, endanger people working on it and cause severe transients on reconnection. A common rule keeps the capacitor below about 90% of the no load magnetising kVAr.

Why can’t the generator use capacitors?

It can, with care. Capacitors left connected when a generator carries light load can drive it to a leading power factor, which many alternators can absorb only in small amounts before voltage rises and the regulator loses control. Capacitor steps are therefore limited or blocked on generator supply by a signal from the changeover.

What is detuning?

Placing a reactor in series with each capacitor step so that the combination resonates below the lowest significant harmonic, usually below the 5th. The step then behaves inductively at harmonic frequencies, so it cannot form a parallel resonance with the supply or absorb harmonic current from elsewhere, while still correcting power factor at 50 Hz.

What target power factor is right?

Usually about 0.95 to 0.98 lagging, chosen from the supply terms, the capacity freed and the cost of the correction. Correcting to unity costs much more kVAr for little gain and risks a leading power factor at light load. Sites already near 0.95 may need no correction at all.

Does low power factor reduce generator kW?

It does not reduce the engine kW, but it loads the alternator with more kVA for the same kW. Below the rated power factor, usually 0.8, the alternator reaches its kVA and field heating limits before the engine reaches its kW rating, so the usable kW falls unless a larger alternator is fitted.

Values are illustrative. Confirm with measured data.