In short. A harmonic filter must be chosen for the problem, not the product. The study sets a target distortion level and picks a solution: detuned capacitors, a tuned passive filter or an active filter. It sizes that solution from the measured spectrum, then rechecks resonance and the plant’s behaviour on generator supply. Measurement before and after proves the filter worked.
Who this page is for: For plant engineers and consultants dealing with harmonic heating, failing capacitors or generator voltage distortion.
Key facts
- Detuned reactors protect capacitor banks and move resonance away from harmonics.
- Tuned passive filters absorb a dominant harmonic; they suit steady loads.
- Active filters inject cancelling current; they suit varying loads.
- Size from the measured spectrum at the point of connection.
- Recheck resonance with the filter in, on grid and on generator.
- Passive filters supply reactive power; check leading power factor at light load.
Filter types
| Type | Best for | Watch for |
|---|---|---|
| Detuned reactor with capacitors | Protecting capacitor banks; shifting resonance | Does not remove much distortion |
| Tuned passive filter | Steady loads with one dominant harmonic | Leading power factor at light load; ageing |
| Active filter | Varying loads and spectra | Rating in amps; heat; cost |
Worked example: sizing an active filter (illustrative)
| Item | Measured or chosen |
|---|---|
| Load fundamental current | 800 A |
| Current distortion before | about 30%: 240 A harmonic |
| Target current distortion | 8%: 64 A |
| Harmonic current to cancel | 240 − 64 = 176 A |
| Filter chosen | 200 A, with margin for growth |
| On generator supply | Voltage distortion fell from about 11 to 4% |
The arithmetic is simplified; harmonic currents add as root-sum-square, and the study used the measured spectrum. See harmonic studies.
Do not install capacitors or a passive filter without a resonance check on every source. A filter tuned for grid conditions can resonate on generator supply, where the source impedance is much higher.
Study steps
- Measure the spectrum on grid and on generator.
- Set the target.
- Choose the type.
- Size it and check resonance and power factor.
- Measure again after installation.
See reactive power studies, load flow and short-circuit studies.
Filter study sheet
| Item | Before | Target | After |
|---|---|---|---|
| Current distortion | |||
| Voltage distortion (grid) | |||
| Voltage distortion (generator) |
Worked example: sizing from the spectrum, not the total (illustrative)
Harmonic currents of different orders add as the square root of the sum of their squares, not arithmetically. Take the 800 A load in the example above with a measured spectrum:
| Harmonic | Measured current | Square |
|---|---|---|
| 5th | 180 A | 32,400 |
| 7th | 120 A | 14,400 |
| 11th | 70 A | 4900 |
| 13th | 50 A | 2500 |
| Total | √54,200 ≈ 233 A | 54,200 |
The total harmonic current is about 233 A, a current distortion of 233 ÷ 800 ≈ 29%. To reach 8%, 64 A, every order must be reduced to about 64 ÷ 233 ≈ 27% of its present value, so the filter must cancel about 72.5% of each: about 0.725 × 233 ≈ 169 A in total. A 200 A active filter covers that with margin. The study also checks that the filter’s rating at the 5th harmonic alone, 0.725 × 180 ≈ 131 A, is within what the maker states for that order.
Detuning: where the reactor puts the resonance
A detuned capacitor bank has a reactor in series with each capacitor, chosen so the combination resonates below the lowest significant harmonic. The tuning frequency is 50 Hz divided by the square root of the reactor percentage.
| Reactor | Tuning frequency | Harmonic order | Suits |
|---|---|---|---|
| 7% | 50 ÷ √0.07 ≈ 189 Hz | about 3.8 | Networks dominated by 5th and 7th, little 3rd |
| 14% | 50 ÷ √0.14 ≈ 134 Hz | about 2.7 | Networks with significant 3rd harmonic |
Below its tuning frequency the branch looks capacitive and corrects power factor; above it, at the 5th and higher, it looks inductive and cannot resonate with the source. The reactor raises the voltage across the capacitors, so the capacitors must be rated for it.
Worked example: the same capacitors on grid and on generator (illustrative)
A plain capacitor bank forms a parallel resonance with the source at roughly the square root of the source short-circuit capacity divided by the capacitor kVAr.
| Source | Short-circuit capacity | Resonant order with 300 kVAr | Risk |
|---|---|---|---|
| 1000 kVA transformer at 5% | 1000 ÷ 0.05 = 20,000 kVA | √(20,000 ÷ 300) ≈ 8.2 | Between the 7th and 11th: moderate |
| 1250 kVA generator, X″d about 0.15 | 1250 ÷ 0.15 ≈ 8333 kVA | √(8333 ÷ 300) ≈ 5.3 | Almost on the 5th: severe amplification |
A bank that is tolerable on the grid sits almost exactly on the 5th harmonic when the generator supplies, which is where six-pulse drives and UPS inject the most current. That is the case the study exists to catch, and the reason capacitor banks on generator-backed boards are detuned or switched out on generator supply.
Setting the target
Targets come from the equipment and from the utility. Widely used guidance for low-voltage systems limits total voltage distortion to about 8% with individual harmonics around 5%, with stricter current limits at the point of connection that depend on the ratio of short-circuit current to load current. Sensitive equipment, or a generator whose maker limits voltage distortion, may need tighter targets. Write the target for each source before choosing the filter, because a filter that meets the grid target can still leave the generator outside its own.
Leading power factor at light load
A tuned passive filter supplies a fixed amount of reactive power whether the load is there or not. A 150 kVAr filter on a board carrying 100 kW at night gives a strongly leading power factor, which a generator tolerates poorly: it drives the regulator towards its under-excitation limit and can trip loss-of-excitation protection. Switch passive filters in steps with the load, or choose an active filter, on any board a generator may supply at light load.
Keeping the filter effective
Capacitors lose capacitance with age and heat, which moves a tuned filter’s frequency upwards and can bring it closer to a harmonic. Measure each step’s kVAr or current once a year, check reactor and capacitor temperatures by thermography, and repeat the harmonic measurement after any significant change in drives or UPS. Active filters need their cooling and fans checked, since they derate quickly when hot.
Choosing by load pattern
| Load pattern | Usual choice | Reason |
|---|---|---|
| Steady six-pulse drives, power factor correction needed | Detuned capacitor bank, sometimes with a tuned 5th branch | Corrects power factor safely and absorbs some 5th |
| Large steady load with one dominant harmonic | Tuned passive filter, switched with the load | Low cost per ampere for a known spectrum |
| Varying load, mixed drives, UPS and IT | Active filter | Follows the spectrum as it changes; cannot resonate |
| New installation | Low-harmonic drives and UPS | Removes the problem at source |
Measuring the spectrum properly
A filter is only as good as the measurement behind it. Use a power quality analyser of a recognised measurement class, record for at least a full week so every shift and load pattern is captured, and measure at the point where the filter will connect. Record on generator supply as well, during a test run at realistic load, because the voltage distortion there is what the alternator and every sensitive load will see. Note which drives, UPS and capacitors were in service during each recording.
The generator’s own limit
Alternator makers state how much harmonic current or voltage distortion their machines tolerate before derating, because harmonic currents add heating in the windings and the rotor surface. A distortion that a grid transformer shrugs off can force a generator down to 80 or 90% of its rating. Include the maker’s limit in the targets, and check the filter’s effect at the generator terminals rather than only at the main board.
Central filter or filters at the loads
A single filter at the main board is easy to maintain and protects the source, but leaves the harmonic currents flowing in every cable between the board and the loads, heating them and their neutrals. Filters at the largest loads remove the current where it starts and relieve the cables too, at the cost of more units to look after. The study compares both, often ending with a central filter for the many small loads and local treatment of the few large drives.
Checks after installation
Once a filter is in service, measure again under the same conditions as the original survey, on grid and on generator. Compare the voltage and current distortion with the targets, check the filter current and temperature against its rating, and listen for unusual noise from reactors. Record the results as the new baseline for the site. A filter that meets the targets on the day it is commissioned can drift out of tune as capacitors age, so repeat the check at each annual maintenance visit and whenever large non-linear loads are added.
Protecting the filter itself
A passive filter needs its own protection: fuses or a breaker sized for the filter current including harmonics, an overload function that sees the true RMS current, and unbalance protection on larger capacitor banks to detect failing units early. Discharge resistors bring the capacitor voltage down after disconnection, so allow the stated time before reclosing or working on the bank. An active filter limits its own output, but its supply breaker and cabling must still carry its full rated current continuously.
Common mistakes
- Filter bought without measurement.
- No resonance check on generator supply.
- Leading power factor at light load ignored.
- No measurement after installation.
What to send us
Send harmonic recordings and the list of drives and UPS. WhatsApp 98852 01608 or use the application engineering enquiry. See load list.
Evidence note. Values are illustrative; measurements and studies govern.
Questions engineers ask
How is an active harmonic filter sized?
From the measured spectrum, adding orders as the square root of the sum of squares. Fifth, seventh, eleventh and thirteenth currents of 180, 120, 70 and 50 A total about 233 A, 29% of an 800 A load. Reaching 8%, 64 A, means cancelling about 72.5%, about 169 A, so a 200 A filter is chosen.
Why can a capacitor bank resonate on generator supply but not on grid?
Parallel resonance falls at roughly the square root of the source short-circuit capacity over the capacitor kVAr. With 300 kVAr, a 1000 kVA transformer at 5% gives about the 8.2nd harmonic, but a 1250 kVA generator with a subtransient reactance of 0.15 gives about the 5.3rd, almost on the 5th, where drives and UPS inject most current. Detune the bank or switch it out.
Passive or active?
Passive filters suit steady loads with one dominant harmonic and supply reactive power as well, but they are fixed, can resonate and give a leading power factor at light load. Active filters adapt to changing spectra and loads and cannot resonate, but cost more and need cooling. Choose from the measured spectrum and the load pattern.
Can a filter cause problems?
Yes. A passive filter can form a resonance with the source, especially on generator supply where the source is weaker, and can be overloaded by harmonics from elsewhere on the network that it was not sized for. At light load it can drive a generator into leading power factor. A study on every source avoids these.
How do I verify?
Measure the harmonic spectrum, current distortion and voltage distortion before installation and again after it, at the same point, under the same operating conditions and load, and on both grid and generator supply. Compare the results with the targets set in the study, and repeat the measurement after major changes to drives or UPS.
Does filtering reduce generator size?
It can. Harmonic currents heat the alternator and distort its voltage, so sets supplying large non-linear loads are often oversized. Reducing the harmonic current with a filter, or choosing low-harmonic drives and UPS, reduces the heating and distortion, and may allow a smaller set. The study should show the generator distortion with and without the filter.
This guide gives general principles. Filters should be designed from measurements.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.