In short. Unequal phase loading creates negative-sequence current: a set of currents that rotates against the machine. In an alternator it induces double-frequency currents in the rotor surface and heats it; in induction motors a small voltage unbalance produces a much larger current unbalance and extra heating. On generator supply the same unbalanced load causes more voltage unbalance than on the grid, because the generator’s negative-sequence impedance is much higher, and the alternator rotor has its own limit. Buildings with many single-phase boards are the usual cause. The study measures the unbalance, compares it with machine limits and sets protection to act before damage.
Who this page is for: For facility managers, electrical engineers and generator owners with single-phase loads on a three-phase generator, or motors running hot for no clear reason.
Key facts
- Voltage unbalance ≈ maximum deviation from the average ÷ average × 100.
- Strictly, unbalance is negative-sequence ÷ positive-sequence voltage (or current).
- A motor’s current unbalance is typically six to ten times its voltage unbalance.
- Many alternators allow a continuous negative-sequence current of the order of 8% of rated; check the maker’s figure.
- Unbalanced single-phase loads also drive neutral current.
- Above about 1% voltage unbalance, motors need derating: about 5% at 2% unbalance.
Definitions
Line voltages of 410, 418 and 424 V average 417.3 V; the largest deviation is 7.3 V, so the unbalance is about 1.8%.
Worked example: a 250 kVA set feeding single-phase floors (illustrative)
A building’s 250 kVA generator (rated about 348 A) feeds several single-phase floor boards. A clamp-meter survey at peak shows 180 A, 120 A and 95 A. Treating the currents as in phase with their voltages:
| Quantity | Working | Result |
|---|---|---|
| Positive-sequence current I1 | (180 + 120 + 95) ÷ 3 | About 132 A |
| Negative-sequence current I2 | |180 + 120∠120° + 95∠240°| ÷ 3 | About 25 A |
| Current unbalance | I2 ÷ I1 | About 19% |
| I2 as a share of alternator rating | 25 ÷ 348 | About 7.2%: close to a typical continuous limit |
| Neutral current | |180 + 120∠−120° + 95∠120°| | About 76 A |
The set is only about 38% loaded, yet its rotor is near its negative-sequence limit, and any further unbalance would exceed it. Moving circuits so the phases read about 135, 130 and 130 A cuts the negative-sequence current to a few amps and the neutral current to under 10 A. See independent-phase regulation.
A lightly loaded generator can still overheat its rotor if the phases are badly unbalanced. Balance single-phase loads across the phases, check them after every alteration, and fit negative-sequence or phase-unbalance protection on larger sets.
Effects by equipment
| Equipment | Effect |
|---|---|
| Alternator | Rotor surface heating; continuous and short-time negative-sequence limits |
| Induction motor | Current unbalance several times the voltage unbalance; extra heating, less torque |
| Rectifiers and drives | Extra ripple; trips on input unbalance |
| Neutral conductor | Higher current and heating |
Motor derating
| Voltage unbalance | Typical consequence |
|---|---|
| Up to about 1% | Negligible |
| About 1 to 3% | Extra heating; derate the motor |
| Above about 3 to 5% | Motor protection should act; investigate the cause |
Common causes
- Single-phase loads unevenly distributed.
- An open phase: blown fuse, failed contact or loose joint.
- Blown capacitor fuses in one phase.
- Unequal impedance in feeders or transformer taps.
Study steps
- Map single-phase loads by phase.
- Measure phase currents and voltages at peak and off-peak.
- Calculate negative-sequence current at the generator.
- Compare with the alternator’s continuous and short-time limits.
- Check motor derating at the measured voltage unbalance.
- Rebalance, then set protection. See negative-sequence protection.
Phase balance survey
One day of readings at sub-board 2 of a 2000 kVA installation with two 1250 kVA generators — a 630 A board carrying lighting and single-phase small power. The example above takes a single peak snapshot on a 250 kVA set and finds its rotor near its negative-sequence limit; this survey runs across a day on a far larger source, where the limit is never approached and the problem is somewhere else entirely.
| Time | L1 (A) | L2 (A) | L3 (A) | Neutral (A) | Voltage unbalance (%) |
|---|---|---|---|---|---|
| 06:00 | 210 | 190 | 185 | 23 | 0.4 |
| 09:00 | 295 | 240 | 225 | 64 | 0.9 |
| 12:00 | 340 | 250 | 230 | 101 | 1.3 |
| 15:00 | 355 | 245 | 225 | 121 | 1.5, the worst reading of the day |
| 18:00 | 300 | 235 | 220 | 74 | 1.0 |
| 21:00 | 230 | 195 | 190 | 38 | 0.6 |
| 15:00, after circuits were moved | 280 | 275 | 270 | 9 | 0.1 |
Take the 15:00 row through the sequence arithmetic. The positive-sequence current is the three added and divided by three: 355 plus 245 plus 225 is 825, so 275 A. The negative-sequence current is the magnitude of 355 plus 245 at 120 degrees plus 225 at 240 degrees, all divided by three, which comes to about 40 A. Current unbalance is therefore 40 divided by 275, about 15%. And the neutral carries three times the negative-sequence magnitude, 121 A — on a board whose phases are reading between 225 and 355, a neutral conductor is carrying more than a third of the lightest phase.
Now the comparison the example above makes, and the different answer this site gives. Against one 1250 kVA set, whose rated current is 1739 A, 40 A of negative sequence is 2.3% — nowhere near the 8% or so an alternator will usually carry continuously. The rotor is not the problem here, and a survey that stopped at that check would have closed the file.
What the 1.5% voltage unbalance does instead is derate every motor on that board: the derating goes with the square of the unbalance, not with the unbalance itself, so the 5% at 2% in the guidance above becomes 5 times 1.5 over 2, squared — about 3% at this board’s 1.5%. On a board full of small fan and pump motors that is a real and permanent loss nobody has budgeted for, and reading the curve as a straight line would have put it at nearly 4%.
The last row is the fix and it cost nothing but an afternoon. Moving single-phase circuits between phases to read 280, 275 and 270 takes the negative-sequence current from 40 A to about 3, the neutral from 121 A to 9, and the voltage unbalance from 1.5% to 0.1%. No equipment was bought. The total load is identical — 825 A both before and after — which is exactly why the problem is invisible to anything that measures only demand.
Two things make the survey worth doing as a survey rather than a snapshot. The spread across the day is more than threefold: 23 A of neutral at six in the morning and 121 at three in the afternoon, and a reading taken at either end alone would have been misleading in opposite directions. And the pattern itself is the diagnosis — the unbalance grows and shrinks with the working day, which points at switched single-phase load rather than at a cable fault or a loose connection, both of which would show a steady offset. The timing column does more diagnostic work here than any of the current columns.
Motor derating and extra heating
| Voltage unbalance | Approximate derating factor | Approximate extra winding heating |
|---|---|---|
| 1% | About 0.98 | About 2% |
| 2% | About 0.95 | About 8% |
| 3% | About 0.88 | About 18% |
| 4% | About 0.82 | About 32% |
| 5% | About 0.75 | About 50% |
The heating column follows a common rule of thumb that the extra temperature rise in percent is about twice the square of the voltage unbalance in percent. It shows why unbalance that looks small on a voltage reading shortens motor life: at 3%, a motor running at full load carries close to a fifth more heat than it was designed for.
Common causes and where to look
| Cause | Sign |
|---|---|
| Single-phase loads unevenly spread | Phase currents differ widely at board level |
| A failed capacitor step or blown fuse on one phase | Unbalance appears when the bank switches in |
| A high-resistance joint or worn contact on one phase | A hot spot on thermography, a voltage drop on one phase only |
| Long single-phase feeders on one phase | Unbalance grows toward the far end |
| Unequal transformer taps or an open-delta arrangement | Unbalance present even at no load |
| Unbalance already on the supply | Present at the incomer with the site load off |
Measuring unbalance properly
A power quality analyser reports the voltage unbalance factor directly from the sequence components, recorded over ten-minute intervals for at least a week. A common planning limit at low voltage is about 2% for most of the time. Measure at the incomer, at boards with heavy single-phase load and at the generator terminals during a test run, because the same load produces more unbalance on generator supply. A single spot reading with a clamp instrument shows the load pattern at that moment, not the range the motors live with.
Protection against unbalance
- Generators: negative-sequence protection, device 46, set from the alternator’s continuous and short-time limits.
- Motors: motor protection relays with current unbalance and phase-loss functions, set so that a lost phase trips quickly and moderate unbalance alarms.
- Boards: phase-loss and phase-sequence relays where motor loads would be damaged by single phasing.
Protection limits the damage; it does not remove the cause. The study pairs each protection setting with a correction of the load balance or the faulty equipment.
The regulator and unbalance on generator supply
A regulator that senses one phase holds that phase at the set voltage and lets the others drift; one that senses all three holds their average. On a generator with unbalanced load, three-phase sensing gives a better compromise for motors, and a set supplying heavily unbalanced loads may need an alternator chosen for higher negative-sequence capability. See generator sizing and transient performance studies.
Common mistakes
- Phase balance checked once at design only.
- No negative-sequence protection on larger sets.
- Judging the generator by total load, not by phase.
- Ignoring motor heating at low voltage unbalance.
What to send us
Send phase-wise current and voltage readings, the generator rating and a list of single-phase boards. WhatsApp 98852 01608 or use the enquiry form. See also neutral grounding.
Evidence note. Limits are typical values for illustration; the alternator and motor makers’ data govern.
Questions engineers ask
How much extra heating does voltage unbalance cause in a motor?
A common rule of thumb puts the extra temperature rise in percent at about twice the square of the voltage unbalance in percent. At 2% unbalance that is about 8% more heating, at 3% about 18% and at 5% about 50%, which is why motors are derated to about 0.95, 0.88 and 0.75 at those levels.
Where does voltage unbalance usually come from?
Uneven single phase loading, a failed capacitor step or blown fuse on one phase, a high resistance joint on one phase, long single phase feeders, unequal transformer taps or an open delta arrangement, or unbalance already present on the supply. Measuring at the incomer with site load off separates supply unbalance from causes inside the site.
What is negative sequence?
One of three balanced sets of components into which any unbalanced three phase set can be split. The negative sequence set rotates in the opposite direction to the normal one, so in rotating machines it induces double frequency currents in the rotor, causing heating and vibration. Its size measures how unbalanced the system is.
Why does a small voltage unbalance cause large current unbalance in motors?
Because a motor presents a low impedance to negative sequence voltage, close to its locked rotor impedance, while it presents a much higher impedance to the normal voltage at running speed. A small negative sequence voltage therefore drives a large negative sequence current, typically six to ten times the voltage unbalance in percent.
What limit applies to alternators?
The maker states a continuous negative sequence current limit, often of the order of 8% of rated current for many low voltage machines, and a short time limit expressed as the square of negative sequence current times time. Negative sequence protection is set from those figures for the actual alternator.
How can I fix unbalance?
Rebalance single phase loads across the phases, repair any faulty capacitor step, joint or contact on one phase, correct unequal transformer taps, and shorten or split long single phase feeders. Where unbalance comes from the supply, raise it with the supply authority. Protection limits damage while the cause is fixed.
This guide gives general principles. Use manufacturer limits for design.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.