In short. A generator has two limits. The engine limits real power in kW; the alternator limits apparent power in kVA. Sets are rated at 0.8 power factor, so kW = kVA × 0.8: a 500 kVA set gives 400 kW. To size a set, convert the running load to both kW and kVA, plan for the set to run at about 70 to 80%, allow for growth, and then check the largest motor start. Whichever limit is reached first, kW or kVA, decides the size.
Who this page is for: For buyers, consultants and facility managers who need a quick, correct conversion between kW and kVA and a first generator size from a known load.
Key facts
- kVA = kW ÷ power factor; kW = kVA × power factor.
- Generators are rated at 0.8 power factor: 125 kVA = 100 kW, 500 kVA = 400 kW, 1000 kVA = 800 kW.
- The engine supplies kW; the alternator supplies kVA. Check both.
- Three-phase current: I = kVA × 1000 ÷ (√3 × V); at 415 V that is about 1.39 A per kVA.
- Plan normal running at about 70 to 80% of rating, and avoid long running below about 30%.
- The largest motor start often decides the size more than the running load.
kW, kVA and power factor
| Quantity | Meaning | Sets the size of |
|---|---|---|
| kW (real power) | Power that does work: heat, light, shaft power | The engine, and the fuel it burns |
| kVA (apparent power) | Voltage × current, including reactive current | The alternator, cables, breakers and switchgear |
| Power factor | kW ÷ kVA | How the two relate for a given load |
At 0.8 power factor, 100 kW is 125 kVA. A site load of 320 kW at 0.8 is 400 kVA and draws about 400 × 1000 ÷ (1.732 × 415) ≈ 556 A at 415 V. For every rating’s current, see the full-load current chart.
Which limit is reached first
| Load on a 500 kVA set (400 kW engine) | kW | kVA | Limit reached |
|---|---|---|---|
| Typical mixed load at PF 0.8 | 400 | 500 | Both together, as designed |
| Motor-heavy load at PF 0.6 | 300 | 500 | Alternator (kVA); the engine still has 100 kW spare |
| Heaters, lighting and corrected load at PF 0.95 | 380 | 400 | Engine (kW) is near its limit while the alternator has spare kVA |
A poor power factor fills the alternator before the engine. A high power factor, for example after correction, fills the engine first. Generators cannot deliver more kW than their engine rating, even at unity power factor.
Sizing a set from a known load
- Running load. Total the kW that runs together during an outage, with realistic demand and diversity. See connected load and maximum demand.
- Convert. kVA = kW ÷ the load’s real power factor.
- Loading target. Divide the kW by about 0.75, so the set runs at about 75%, then convert to kVA at 0.8. Check the load kVA also fits.
- Growth. Add only growth that is planned, often 10 to 25%.
- Derating. Allow for high ambient and altitude. See ambient temperature derating.
- Largest motor start. Check the voltage dip. See the motor starting calculator.
- Choose the next standard rating and confirm against the maker’s data.
Worked example: a workshop (illustrative)
A workshop runs 280 kW at an average power factor of 0.85, which is 280 ÷ 0.85 ≈ 329 kVA of load. Its largest motor is a 55 kW motor on a star-delta starter.
| Step | Working | Result |
|---|---|---|
| Running at 75% | 280 ÷ 0.75 = 373 kW, ÷ 0.8 = 467 kVA | 500 kVA (400 kW) |
| Load kVA check | 329 kVA against 500 kVA | 66%: passes |
| Motor start check | A 500 kVA set typically starts about 150 kW on star-delta | 55 kW passes comfortably |
| With 20% firm growth | 336 kW ÷ 0.75 ÷ 0.8 = 560 kVA | 625 kVA, if the growth is certain |
A 400 kVA set would carry the 280 kW, but at 88% of its 320 kW engine rating, with no room for growth or a hot afternoon. The 500 kVA set is the sound choice today; 625 kVA only if the expansion is firm. For a full load list with motor starts, use the generator size calculator from a load list.
Do not size a generator from the kVA of the load alone. A low power factor can hide an engine that is already near full load, and a high power factor can hide an alternator with no spare current. Check both kW and kVA.
Not too small, not too large
| Loading | Effect |
|---|---|
| Above about 90% for long periods | No margin for starts, hot weather or growth; shorter engine life |
| About 70 to 80% | The usual target for standby and prime duty |
| Below about 30% for long periods | Wet stacking, carbon build-up, more fuel per kWh. See light-load running |
kW and kVA worksheet
| Item | Value |
|---|---|
| Running load (kW) and power factor | |
| Load kVA = kW ÷ PF | |
| Size at 75% loading = kW ÷ 0.75 ÷ 0.8 (kVA) | |
| Growth allowance (%) and derating | |
| Largest motor (kW) and starter | |
| Standard rating chosen (kVA / kW) |
Typical power factors of common loads
The kVA a set must supply depends on the power factor of the loads. The values below are typical at normal running and are illustrative; the equipment data gives the real figure.
| Load | Typical power factor |
|---|---|
| Resistive heating, incandescent lighting | About 1.0 |
| Modern LED lighting with good drivers | 0.9 to 0.95 |
| Induction motors at full load | 0.8 to 0.9 |
| Induction motors at light load | 0.5 to 0.7 |
| UPS and drives with active front ends | 0.95 or higher |
| Older rectifier loads without correction | 0.7 to 0.8 |
Worked example: combining loads with different power factors (illustrative)
A site has 60 kW of motors at 0.85 power factor, 30 kW of lighting at 0.95 and 20 kW of heating at 1.0. Adding kVA directly would overstate the total, because reactive power does not add in the same way. Instead, add kW and kVAr separately. The motors draw about 37.2 kVAr, the lighting about 9.9 kVAr and the heating none.
Total real power is 110 kW and total reactive power about 47.1 kVAr, giving about 119.7 kVA at an overall power factor of about 0.92. A 125 kVA set looks close; adding margin for growth and the largest motor start usually points to the next size up, which the starting check then confirms.
Single-phase loads on a three-phase set
Each phase of a three-phase set can carry only one third of its rating. If single-phase loads are concentrated on one phase, that phase reaches its limit while the others are lightly loaded, and the set is effectively undersized. Spreading single-phase loads evenly across the phases, and checking phase currents at full load, makes the whole rating usable.
Site conditions and derating
Catalogue ratings apply at reference conditions. High ambient temperature, altitude and restricted cooling air reduce the power a set can deliver. In a Hyderabad summer, a set installed in a hot room may need to be derated, so the derated output, not the nameplate figure, is compared with the calculated load.
Checking the result on site
Once the set is installed, log its load, power factor and phase currents during normal operation and at the busiest times. Comparing these with the sizing calculation shows whether the assumptions held, and gives early warning if growth is bringing the set close to its limit.
Keeping that log with the original calculation also gives the next engineer a clear starting point when the site plans an extension or a replacement set.
Common mistakes
- Adding the nameplate kW of every machine with no diversity.
- Checking only kVA, not kW, or only kW, not kVA.
- Ignoring the largest motor start.
- Skipping summer derating.
- Buying far too large “to be safe” and running at light load for years.
What to send us
Send the load list or electricity bills, the largest motors and their starters, and the site location. WhatsApp 98852 01608 or use the enquiry form. See also the generator size chart.
Evidence note. Figures are illustrative. Final sizing needs the site’s load data and the selected set’s data sheet.
Questions engineers ask
How do I combine loads with different power factors?
Add kW and kVAr separately, then find kVA. In the illustrative site, 60 kW of motors, 30 kW of lighting and 20 kW of heating give 110 kW and about 47.1 kVAr, which is about 119.7 kVA at an overall power factor near 0.92, before growth and motor starting are added.
What power factor do common loads have?
Typically about 1.0 for resistive heating, 0.9 to 0.95 for good LED lighting, 0.8 to 0.9 for induction motors at full load and 0.5 to 0.7 at light load, 0.95 or higher for UPS and drives with active front ends, and 0.7 to 0.8 for older rectifiers.
Why do single-phase loads matter when sizing a three-phase generator?
Each phase can carry only one third of the rating. If single-phase loads crowd one phase, it reaches its limit while others stay lightly loaded, so the set behaves as if it were smaller. Spreading loads evenly and checking phase currents makes the full rating usable.
Should site temperature change the generator size?
Yes. Ratings apply at reference conditions, and high ambient temperature, altitude or restricted cooling air reduce available output. In a hot generator room during a Hyderabad summer, the derated output, not the nameplate figure, must be compared with the calculated load, with margin left for growth on the site.
How do I convert kW to kVA?
Divide kW by the power factor. At 0.8, 100 kW is 125 kVA. The same rule works in reverse: multiply kVA by the power factor to get kW, so a 250 kVA set gives 200 kW at 0.8. Use the power factor of your actual load where it is known, because a lower power factor needs more kVA for the same kW and can make the alternator, not the engine, the limit.
Why is a generator rated at 0.8 power factor?
It is a standard rating convention that ties the alternator’s kVA to the engine’s kW. Real loads may differ. A load at a lower power factor needs more kVA for the same kW, which can overload the alternator before the engine; a load near unity power factor can load the engine fully before the alternator. Both limits are checked for the actual load.
Is it bad to oversize a generator?
Yes if it runs at very light load for long, which can cause engine problems and waste fuel. Balance margin against minimum load. Below about 30% load for long periods, diesel engines wet-stack and carbon up. Where the normal load is much smaller than the peak, two smaller sets or a regular load-bank run keep the engine healthy.
Does the generator also have to carry the starting current?
Yes. The starting kVA of the largest motor, with the base load, must stay within voltage dip and frequency limits. Starting the largest motor first, or using a soft starter or drive, often lets a smaller set carry the load. The final check uses the maker data for the set and the motor starting method.
Can I use this guide for a final purchase decision?
No. It gives a preliminary size. Final sizing needs a load study and the manufacturer’s performance data. Use the result to shortlist sets and compare quotations. Before ordering, have a service engineer confirm the size against the actual motors, their starting methods, the site ambient and the set data sheet, so the chosen set carries the load with margin.
Figures are illustrative. Final sizing requires an engineering review of your loads and site.
Looking for a specific rating? See the generator full-load current chart for every common size from 7.5 to 3000 kVA at 415 V and 11 kV.
Generators by rating
- Under 15 kVA generators
- 15–50 kVA generators
- 50–125 kVA generators
- 125–250 kVA generators
- 250–500 kVA generators
- 500–1000 kVA generators
- 1000–2000 kVA generators
- 2000 kVA and above generators
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.