Generator Full-Load Current Chart, 7.5 to 3,000 kVA

In short. A generator’s full-load current is the current it delivers at its rated kVA and rated voltage: I = kVA × 1000 ÷ (√3 × V) for three-phase sets. At 415 V that is about 1.39 A per kVA, so a 1,500 kVA set delivers about 2,087 A per phase, a 750 kVA set about 1,043 A and a 15 kVA set about 21 A. The table below lists every common rating from 7.5 kVA to 3,000 kVA with its kW at 0.8 power factor and its full-load current at 415 V, at 11 kV for medium-voltage sets, and at 230 V for small single-phase sets. Use it to size breakers, cables, busbars and changeover switches, then confirm against the nameplate of the actual set.

Quick answers: full-load current at 415 V

  • 62.5 kVA DG: about 87 A per phase at 415 V (50 kW at 0.8 PF)
  • 100 kVA DG: about 139 A per phase at 415 V (80 kW at 0.8 PF)
  • 125 kVA DG: about 174 A per phase at 415 V (100 kW at 0.8 PF)
  • 160 kVA DG: about 223 A per phase at 415 V (128 kW at 0.8 PF)
  • 200 kVA DG: about 278 A per phase at 415 V (160 kW at 0.8 PF)
  • 250 kVA DG: about 348 A per phase at 415 V (200 kW at 0.8 PF)
  • 320 kVA DG: about 445 A per phase at 415 V (256 kW at 0.8 PF)
  • 500 kVA DG: about 696 A per phase at 415 V (400 kW at 0.8 PF)
  • 750 kVA DG: about 1,043 A per phase at 415 V (600 kW at 0.8 PF)
  • 1,000 kVA (1 MVA) DG: about 1,391 A per phase at 415 V (800 kW at 0.8 PF)
  • 1,010 kVA DG: about 1,405 A per phase at 415 V (808 kW at 0.8 PF)

From the chart below: I = kVA × 1000 ÷ (√3 × 415), about 1.39 A per kVA. Confirm against the nameplate of the actual set.

Generator full-load current chart (0.8 PF, 50 Hz)

Three-phase current is per phase (line current). Single-phase current is shown only for ratings normally built as 230 V single-phase sets. Values are rounded; the generator current calculator gives exact figures for any kVA, voltage or power factor.

Rating (kVA) kW at 0.8 PF 415 V 3-phase (A) 11 kV (A) 230 V 1-phase (A)
7.5 6 10 – 33
10 8 14 – 43
15 12 21 – 65
20 16 28 – 87
25 20 35 – 109
30 24 42 – 130
40 32 56 – –
45 36 63 – –
50 40 70 – –
62.5 50 87 – –
75 60 104 – –
82.5 66 115 – –
100 80 139 – –
125 100 174 – –
140 112 195 – –
160 128 223 – –
180 144 250 – –
200 160 278 – –
250 200 348 13.1 –
275 220 383 14.4 –
320 256 445 16.8 –
380 304 529 19.9 –
400 320 556 21.0 –
450 360 626 23.6 –
500 400 696 26.2 –
600 480 835 31.5 –
625 500 870 32.8 –
650 520 904 34.1 –
750 600 1,043 39.4 –
1,000 800 1,391 52.5 –
1,010 808 1,405 53.0 –
1,250 1,000 1,739 65.6 –
1,500 1,200 2,087 78.7 –
1,750 1,400 2,435 91.9 –
2,000 1,600 2,782 105.0 –
2,250 1,800 3,130 118.1 –
2,500 2,000 3,478 131.2 –
3,000 2,400 4,174 157.5 –

Figures use nominal voltages. At 400 V the three-phase current is about 3.75% higher than the 415 V column (multiply by 1.0375); at 433 V it is about 4% lower (multiply by 0.958).

How the current is worked out

Three-phase: I = S × 1000 ÷ (√3 × VLL), where S is the rating in kVA and VLL the line-to-line voltage. Single-phase: I = S × 1000 ÷ V. The current depends on kVA, not kW, because the alternator carries the full apparent power whatever the power factor of the load. A 1,500 kVA set at 415 V: 1,500 × 1,000 ÷ (1.732 × 415) = 2,087 A. The same set generating at 11 kV: 1,500 ÷ (1.732 × 11) = 78.7 A, which is why large plants generate or step up to medium voltage when power must travel any distance.

Using the figures

Worked examples from the questions we are asked

1,500 kVA generator full-load current. 2,087 A at 415 V, 78.7 A at 11 kV. The set is 1,200 kW at 0.8 PF. Typical installation: 2,500 A ACB, 4 to 5 runs of 400 mm² aluminium or busduct per phase at 415 V.

750 kVA generator full-load current. 1,043 A at 415 V, 39.4 A at 11 kV. The set is 600 kW. Typical installation: 1,250 A ACB, 2 to 3 runs of 300 mm² copper or 400 mm² aluminium per phase.

15 kVA DG load capacity. A 15 kVA set delivers 12 kW at 0.8 PF and 21 A per phase at 415 V (65 A if it is a 230 V single-phase set). It will carry about 12 kW of mixed load continuously, with motor starting checked separately: a single 5.5 kW motor started direct-on-line can be too much for it, while the same motor on a soft starter is fine.

1 MVA and 2 MVA generators. 1 MVA = 1,000 kVA: 1,391 A at 415 V. 2 MVA = 2,000 kVA: 2,782 A at 415 V or 105 A at 11 kV. Above about 2 MVA on one bus, 11 kV generation is usually the better choice; see the 1 to 2 MVA and 2 MVA and above pages.

Common mistakes

What to send us

For a breaker, cable or changeover recommendation, send the set’s nameplate kVA and voltage, the route length to the main board, and whether the neutral is switched. Use the application engineering enquiry or call 098852 01608.

Questions engineers ask

What is the full-load current of a 1,500 kVA generator?

About 2,087 A per phase at 415 V three-phase, or 78.7 A at 11 kV. The set delivers 1,200 kW at 0.8 power factor.

What is the full-load current of a 750 kVA generator?

About 1,043 A per phase at 415 V, or 39.4 A at 11 kV. The set delivers 600 kW at 0.8 power factor.

How much load can a 15 kVA DG set carry?

12 kW at 0.8 power factor, which is 21 A per phase at 415 V or 65 A on a 230 V single-phase set. Motor starting must be checked separately because a direct-on-line start draws several times the running current.

Does the current change between 400 V and 415 V?

Yes, slightly. Current is inversely proportional to voltage, so at 400 V it is about 3.75% higher than at 415 V for the same kVA. Use the voltage on the nameplate.

Is full-load current the same as the breaker rating?

No. The breaker is chosen at or above the full-load current from the standard frame sizes, and its overload setting is adjusted to protect the alternator. The breaker must also have a short-circuit rating suited to the installation’s fault level.

Why does the chart use 0.8 power factor?

Diesel generator sets in India are rated in kVA at 0.8 lagging power factor, so the kW column is kVA × 0.8. The current column does not depend on the power factor; it depends on kVA and voltage only.

Generators by rating

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 1 November 2026.