In short. A generator’s full-load current is the current it delivers at its rated kVA and rated voltage: I = kVA × 1000 ÷ (√3 × V) for three-phase sets. At 415 V that is about 1.39 A per kVA, so a 1500 kVA set delivers about 2087 A per phase, a 750 kVA set about 1043 A and a 15 kVA set about 21 A. The table below lists every common rating from 7.5 kVA to 3000 kVA with its kW at 0.8 power factor and its full-load current at 415 V, at 11 kV for medium-voltage sets, and at 230 V for small single-phase sets. Use it to size breakers, cables, busbars and changeover switches, then confirm against the nameplate of the actual set.
Quick answers: full-load current at 415 V
- 62.5 kVA DG: about 87 A per phase at 415 V (50 kW at 0.8 PF)
- 100 kVA DG: about 139 A per phase at 415 V (80 kW at 0.8 PF)
- 125 kVA DG: about 174 A per phase at 415 V (100 kW at 0.8 PF)
- 160 kVA DG: about 223 A per phase at 415 V (128 kW at 0.8 PF)
- 200 kVA DG: about 278 A per phase at 415 V (160 kW at 0.8 PF)
- 250 kVA DG: about 348 A per phase at 415 V (200 kW at 0.8 PF)
- 320 kVA DG: about 445 A per phase at 415 V (256 kW at 0.8 PF)
- 500 kVA DG: about 696 A per phase at 415 V (400 kW at 0.8 PF)
- 750 kVA DG: about 1043 A per phase at 415 V (600 kW at 0.8 PF)
- 1000 kVA DG: about 1391 A per phase at 415 V (800 kW at 0.8 PF)
- 1010 kVA DG: about 1405 A per phase at 415 V (808 kW at 0.8 PF)
- 1250 kVA DG: about 1739 A per phase at 415 V (1000 kW at 0.8 PF)
- 1500 kVA DG: about 2087 A per phase at 415 V (1200 kW at 0.8 PF)
From the chart below: I = kVA × 1000 ÷ (√3 × 415), about 1.39 A per kVA. Confirm against the nameplate of the actual set.
Generator full-load current chart (0.8 PF, 50 Hz)
Three-phase current is per phase (line current). Single-phase current is shown only for ratings normally built as 230 V single-phase sets. Values are rounded; the generator current calculator gives exact figures for any kVA, voltage or power factor.
| Rating (kVA) | kW at 0.8 PF | 415 V 3-phase (A) | 11 kV (A) | 230 V 1-phase (A) |
|---|---|---|---|---|
| 7.5 | 6 | 10 | – | 33 |
| 10 | 8 | 14 | – | 43 |
| 15 | 12 | 21 | – | 65 |
| 20 | 16 | 28 | – | 87 |
| 25 | 20 | 35 | – | 109 |
| 30 | 24 | 42 | – | 130 |
| 40 | 32 | 56 | – | – |
| 45 | 36 | 63 | – | – |
| 50 | 40 | 70 | – | – |
| 62.5 | 50 | 87 | – | – |
| 75 | 60 | 104 | – | – |
| 82.5 | 66 | 115 | – | – |
| 100 | 80 | 139 | – | – |
| 125 | 100 | 174 | – | – |
| 140 | 112 | 195 | – | – |
| 160 | 128 | 223 | – | – |
| 180 | 144 | 250 | – | – |
| 200 | 160 | 278 | – | – |
| 250 | 200 | 348 | – | – |
| 275 | 220 | 383 | – | – |
| 320 | 256 | 445 | – | – |
| 380 | 304 | 529 | – | – |
| 400 | 320 | 556 | – | – |
| 450 | 360 | 626 | – | – |
| 500 | 400 | 696 | – | – |
| 600 | 480 | 835 | – | – |
| 625 | 500 | 870 | – | – |
| 650 | 520 | 904 | – | – |
| 750 | 600 | 1043 | – | – |
| 1000 | 800 | 1391 | – | – |
| 1010 | 808 | 1405 | – | – |
| 1250 | 1000 | 1739 | 65.6 | – |
| 1500 | 1200 | 2087 | 78.7 | – |
| 1750 | 1400 | 2435 | 91.9 | – |
| 2000 | 1600 | 2782 | 105.0 | – |
| 2250 | 1800 | 3130 | 118.1 | – |
| 2500 | 2000 | 3478 | 131.2 | – |
| 3000 | 2400 | 4174 | 157.5 | – |
Figures use nominal voltages. At 400 V the three-phase current is about 3.75% higher than the 415 V column (multiply by 1.0375); at 433 V it is about 4% lower (multiply by 0.958).
How the current is worked out
Three-phase: I = S × 1000 ÷ (√3 × VLL), where S is the rating in kVA and VLL the line-to-line voltage. Single-phase: I = S × 1000 ÷ V. The current depends on kVA, not kW, because the alternator carries the full apparent power whatever the power factor of the load. A 1500 kVA set at 415 V: 1500 × 1000 ÷ (1.732 × 415) = 2087 A. The same set generating at 11 kV: 1500 ÷ (1.732 × 11) = 78.7 A, which is why large plants generate or step up to medium voltage when power must travel any distance.
Using the figures
- Generator breaker. The outgoing ACB or MCCB is rated at or just above the full-load current: a 1500 kVA set normally has a 2500 A ACB, a 750 kVA set a 1250 A ACB, a 250 kVA set a 400 A MCCB. The protection settings, not the frame size, decide the actual trip point.
- Cables and busbars. Size for the full-load current with the installation derating applied, then check voltage drop. Above about 400 A, parallel runs or busduct are normal; the cable sizing guide and calculator cover this.
- Changeover and ATS. The transfer switch must carry the larger of the utility and generator full-load currents, with the neutral rated the same where it is switched.
- Short-circuit rating. Full-load current is not fault current. A generator’s initial fault current is roughly full-load current ÷ X′d, typically 6 to 10 times, and it decays quickly; see the fault current guide.
- Load capacity. What a set can carry is its kW, not its kVA: a 15 kVA set is a 12 kW set at 0.8 PF. For a resistive or unity-power-factor load the engine kW limit governs; for a low-power-factor load the kVA limit governs. The generator sizing guide explains both limits.
Worked examples from the questions we are asked
1500 kVA generator full-load current. 2087 A at 415 V, 78.7 A at 11 kV. The set is 1200 kW at 0.8 PF. Typical installation: 2500 A ACB, 4 to 5 runs of 400 mm² aluminium or busduct per phase at 415 V.
750 kVA generator full-load current. 1043 A at 415 V. The set is 600 kW. Typical installation: 1250 A ACB, 2 to 3 runs of 300 mm² copper or 400 mm² aluminium per phase.
15 kVA DG load capacity. A 15 kVA set delivers 12 kW at 0.8 PF and 21 A per phase at 415 V (65 A if it is a 230 V single-phase set). It will carry about 12 kW of mixed load continuously, with motor starting checked separately: a single 5.5 kW motor started direct-on-line can be too much for it, while the same motor on a soft starter is fine.
1000 kVA and 2000 kVA generators. 1000 kVA: 1391 A at 415 V. 2000 kVA: 2782 A at 415 V or 105 A at 11 kV. Above about 2000 kVA on one bus, 11 kV generation is usually the better choice; see the 1000 to 2000 kVA and 2000 kVA and above pages.
Reading the chart when the enquiry is in MW
Generator sets are ordered and quoted in kVA, and this chart is in kVA. Above about 1000 kVA a requirement sometimes arrives in megawatts instead, and converting it is arithmetic, but the direction matters: getting it the wrong way round is the most expensive mistake available on this page.
A rating in MW is real power, and it has to be divided by the 0.8 power factor before it can be looked up here at all. One megawatt is therefore 1250 kVA and 1739 A — not the 1000 kVA row, which delivers 800 kW. Quote a 1000 kVA set against a 1 MW requirement and the site is 200 kW short before it is commissioned. The same correction applies all the way up the chart: 2 MW is 2500 kVA at 3478 A, not the 2000 kVA row at 2782 A.
The occasional enquiry written in MVA is simpler, because MVA is the same quantity as kVA a thousand times larger: 1 MVA is the 1000 kVA row. Where an MVA figure appears on a single-line diagram beside a generator, it is usually the transformer or the utility supply being described, because those are the items rated in MVA. The full conversion table is on the 1000 kVA generators page.
One thing about the chart itself is worth saying here, because it is the question the column raises: the 11 kV figures start at 1250 kVA and stop being quoted below it. That is not a gap in the arithmetic but the point at which high-voltage machines begin. A smaller set generates at 415 V, and a site that needs an 11 kV board reaches it through a step-up transformer, so the 11 kV current there is the transformer’s and not the set’s.
Common mistakes
- Using the kW figure to size the breaker or cable. Current follows kVA.
- Reading a 60 Hz nameplate current for a 50 Hz site. The current formula does not change with frequency, but the set’s 50 Hz rating is usually lower than its 60 Hz rating, so use the 50 Hz kVA.
- Forgetting derating. A set derated for altitude or temperature delivers less kVA and therefore less current; the breaker and cables are still sized for the nameplate.
- Switching only three poles where the generator neutral is separately earthed. The neutral then needs its own rated path and a fourth pole.
What to send us
For a breaker, cable or changeover recommendation, send the set’s nameplate kVA and voltage, the route length to the main board, and whether the neutral is switched. Use the application engineering enquiry or call 98852 01608.
Questions engineers ask
What is the full-load current of a 1500 kVA generator?
About 2087 A per phase at 415 V three phase, worked out as 1500 times 1000 divided by 1.732 times 415. Where a set of this size generates at 11 kV it carries about 78.7 A. It delivers 1200 kW at 0.8 power factor, and at 415 V the generator breaker is usually a 2500 A air circuit breaker with busduct or several cables per phase.
What is the full-load current of a 750 kVA generator?
About 1043 A per phase at 415 V three phase, worked out as 750 times 1000 divided by 1.732 times 415. The set delivers 600 kW at 0.8 power factor. That current needs a 1250 A air circuit breaker and busbars or cables rated for it, with a short circuit rating to suit the fault level at the board.
How much load can a 15 kVA DG set carry?
12 kW at 0.8 power factor, which is 21 A per phase at 415 V or 65 A on a 230 V single phase set. For long running, keep the load to about 75% of that, around 9 kW. Motor starting must be checked separately, because a direct on line start draws several times the running current and can stall a small set.
Does the current change between 400 V and 415 V?
Yes, slightly. Current is inversely proportional to voltage, so at 400 V it is about 3.75% higher than at 415 V for the same kVA, and at 433 V about 4% lower. Use the voltage on the nameplate and the voltage the set is actually adjusted to, because the breaker and cable are chosen on that current.
Is full-load current the same as the breaker rating?
No. The breaker is chosen at or above the full load current from the standard frame sizes, and its overload setting is adjusted to protect the alternator. The breaker must also have a short circuit rating suited to the fault level of the installation, and its settings are coordinated with the downstream breakers so that the nearest one trips first.
How do I use this chart if my requirement is in MW?
Divide the megawatts by 0.8 first, because this chart is in kVA and MW is real power. A 1 MW requirement is 1250 kVA and 1739 A at 415 V; a 2 MW requirement is 2500 kVA and 3478 A. Looking up 1 MW as though it were 1000 kVA understates the set by 200 kW and the current by about 350 A.
Why does the chart use 0.8 power factor?
Diesel generator sets in India are rated in kVA at 0.8 lagging power factor, so the kW column is kVA times 0.8. The current column does not depend on the power factor; it depends on kVA and voltage only. A load with a better power factor does not let the set deliver more kW, because the engine still limits real power.
Next step: the DG breaker, changeover switch and cable size chart takes each of these ratings through to its breaker, four-pole changeover, cable runs and maximum route length.
Generators by rating
- Under 15 kVA generators
- 15–50 kVA generators
- 50–125 kVA generators
- 125–250 kVA generators
- 250–500 kVA generators
- 500–1000 kVA generators
- 1000–2000 kVA generators
- 2000 kVA and above generators
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 1 November 2026.