In short. A 20 kVA generator delivers 27.8 A per phase at 415 V, three-phase, at 0.8 power factor — which is 16 kW and 12 kVAr. At 400 V the same set delivers 28.9 A and at 433 V it delivers 26.7 A, and if the set is single-phase it delivers 87.0 A at 230 V. The figures below are the starting point for the protective device, the cables and the changeover; the page then works through what actually decides a set of this size, using published prime-rated data for CPCB-compliant sets of this rating.
Quick answers for a 20 kVA set
- Full-load current at 415 V: 27.8 A per phase
- Full-load current, single-phase 230 V set: 87.0 A
- Real power at 0.8 PF: 16 kW
- Reactive power at 0.8 PF: 12 kVAr
- Usual protective device: 40 A, MCB or MCCB, four-pole, set above 27.8 A; 125 A double-pole on a single-phase set
- Diesel at full load: about 5.1 L/h
- Per kVA at 415 V: about 1.39 A, so 20 × 1.39 ≈ 27.8 A
All figures are at the rated power factor of 0.8 on a 50 Hz set. Always confirm against the nameplate of the actual machine.
Full-load current at each supply voltage
| Supply voltage | Full-load current (A) | Against 415 V | Where it applies |
|---|---|---|---|
| 380 V 3-phase | 30.4 | +9.2% | Older and some imported equipment |
| 400 V 3-phase | 28.9 | +3.8% | Nominal European voltage; many nameplates |
| 415 V 3-phase | 27.8 | reference | Standard Indian LV supply |
| 433 V 3-phase | 26.7 | −4.2% | No-load and lightly loaded alternator setting |
| 230 V single-phase | 87.0 | 3.1 × | Single-phase sets for houses and shops |
The site’s chart rounds these figures to whole amps; this page keeps one decimal below 100 A because at this size a single amp is a noticeable share of the load.
For the same kVA, current and voltage move in opposite directions. Nothing about the machine changes between these rows — only the voltage it is connected at.
How the 27.8 A is worked out
For a three-phase set the full-load current is
I = kVA × 1000 ÷ (√3 × V)
With 20 kVA at 415 V:
- √3 × 415 = 1.732 × 415 = 718.78
- 20 × 1000 = 20,000 VA
- 20,000 ÷ 718.78 = 27.8 A
For a single-phase set there is no √3: I = kVA × 1000 ÷ V, so 20,000 ÷ 230 = 87.0 A. That is why a single-phase set needs a heavier cable and changeover than a three-phase set of the same rating.
The kW and kVAr follow from the power factor rather than from the formula: 20 × 0.8 = 16 kW of real power, and 20 × 0.6 = 12 kVAr of reactive power. Power factor does not appear in the current calculation at all: the set delivers 27.8 A at its rated kVA whatever the power factor of the load, but the kW it can deliver at that current changes completely.
What a 20 kVA set is used for
A 20 kVA set carries an independent house with several air conditioners, a small school block, a petrol pump forecourt, or a workshop with a few small machines. It is the largest size still offered with a single-phase option, and the first size where most installations are three-phase by default.
Reading the 27.8 A figure properly
At 27.8 A per phase the set sits comfortably inside a 40 A protective device, and that margin is deliberate. Sets in this range carry air-conditioning units and pumps whose starts draw several times their running current for a second or two, and a device chosen too close to 27.8 A trips on the start, not on the load.
Phase balance decides the real capacity
Almost every load at this size is single-phase: split air conditioners, lighting, computers, refrigerators. The set’s 27.8 A is per phase, so the useful capacity is set by the most heavily loaded phase, not by the total. A practical rule is to keep the heaviest phase within about 10% of the lightest.
| Phase | Balanced site (A) | Unbalanced site (A) | Verdict |
|---|---|---|---|
| R | 22 | 28 | Unbalanced: R is over full load |
| Y | 21 | 18 | |
| B | 21 | 15 | |
| Total kVA | 14.6 | 14.3 | Same load, different outcome |
Both columns carry almost the same total load. The balanced site runs at about 76% on every phase; the unbalanced site trips because R carries 28 A against the set’s 27.8 A, while B is barely half loaded. Moving two or three air conditioners from R to B fixes it without a larger set.
Prime or standby: what the 20 kVA rating means
Sets of this size in India are normally sold on a prime rating: the set may run for unlimited hours at a varying load, and may carry about 10% more for a short period, typically one hour in twelve. A standby rating, for emergency use of around 200 hours a year, is usually about 10% higher on the same machine. Ask which one a quotation means.
| Duty | What it allows | Rating | Current at 415 V |
|---|---|---|---|
| Prime (normal offer) | Unlimited hours, varying load | 20 kVA, 16 kW | 27.8 A |
| Prime, short overload | About 10% more for a limited time | about 22 kVA | about 30.6 A |
| Standby | Mains failure only, limited hours a year, no overload | about 22 kVA | about 30.6 A |
The percentages are the usual pattern for this size range; the engine maker’s rating sheet for the actual set governs.
The machine behind the figure
Published prime-rated datasheets for CPCB-compliant 20 kVA sets give the following. Where two catalogue editions differ, both figures are shown as a range; other makes differ by a few percent.
| Item | Published figure |
|---|---|
| Engine | 2 cylinders, 2.08 litres, naturally aspirated, 1500 rpm |
| Diesel at 100% load | 5.1 L/h |
| Diesel at 75% load | 3.8 L/h |
| Diesel at 50% load | 2.7 L/h |
| Diesel per kWh at full load | 0.319 L |
| Built-in fuel tank | 65 litres |
| Running time on a full tank at 75% load | about 17 hours |
The diesel-per-kWh line is the one worth reading. At this size the engine is efficient enough that loading matters more than the rating: the same set at half load burns about 53% of its full-load diesel while delivering 50% of the power.
What the site does to the 27.8 A
Published ratings are quoted at reference conditions. Plant rooms, terraces and side passages in Telangana and Andhra Pradesh are hotter than the reference, and sets of this size are often installed in tight spaces where the radiator draws back its own hot air.
A derate in the region of 5 to 10% is common in regional summer conditions, which takes this set from 20 kVA to somewhere between 18 and 19 kVA, and the usable current at 415 V from 27.8 A to between 25.0 and 26.4 A. These are illustrative figures to show the size of the effect; the engine maker’s derating curve for the actual engine is what a design should use.
The practical consequence is the margin. Keep clear space around the canopy, do not let the hot air from the radiator loop back to the air intake, and keep the radiator fins clean. On a set of this size those three things decide whether it carries its plate in May.
Worked example
An independent house plans to run four split ACs, a 1.5 HP pump, the kitchen and the lighting together on the set. The measured result is 14.6 kW at 0.82 power factor.
- Load in kVA: 14.6 ÷ 0.82 = 17.8 kVA.
- Against the set’s kW limit: the engine is rated 16 kW, so the load uses 91% of rated kW.
- Current drawn: 17.8 × 1000 ÷ (1.732 × 415) = 24.8 A, against the set’s 27.8 A.
- Largest motor: check it against the start limit in the five-line check below before signing off.
So the current is inside the set’s 27.8 A, but the engine is at 91% of its kW rating, above the 80% most owners plan to. At a power factor of 0.82 the kW limit governs, and the honest answer is a 25 kVA set rather than a 20 kVA set run flat out every afternoon.
Does a 20 kVA set fit your site? A five-line check
| Check | Figure to use | Pass if |
|---|---|---|
| 1. Running kW | Measured maximum demand in kW | 12.8 kW or less for comfortable loading |
| 2. Running kVA | kW ÷ measured power factor | 16 kVA or less |
| 3. Largest motor started direct on line | Motor kW | About 2.2 kW (3 HP) or less, or use a soft starter or drive |
| 4. Protective device | Existing device and setting | 40 A device, set above 27.8 A |
| 5. Phase arrangement | Building supply and essential loads | Set type matches the building supply |
Fail line 3 and the set is not too small for the load; it is too small for the start. That is a different fix and usually a cheaper one.
Common mistakes with a 20 kVA set
- Reading 20 kVA as 20 kW. The engine is rated 16 kW. A 17.6 kW load is outside the set even though the kVA figure looks generous.
- Putting every single-phase load on one phase. Air conditioners, lights and computers are single-phase loads. If they are not spread across the three phases, one phase carries far more than 27.8 A while the other two are lightly loaded, and the set trips on the heavy phase.
- Starting all the air conditioners at once after changeover. When the set takes over, every motor tries to start at the same moment. A start delay on the AC circuits, or a staggered restart in the AMF panel, avoids a dip the set cannot ride through.
What to send us
If you are deciding whether a 20 kVA set is the right size, these five things let us answer properly rather than guess:
- Maximum demand in kW and the power factor it was measured at. Against this set the limits are 16 kW and 20 kVA, and which one binds depends on the power factor.
- The largest motor — pump, lift or AC unit — its rating, and how it is started.
- Single-phase or three-phase: the building’s electricity connection and how the essential loads are spread across the phases.
- Where the set will stand: terrace, basement, side passage or open yard, and the distance to the changeover.
- How the set will be used: a few hours of power cuts a week, daily shifts, or continuous running. The rating and the service plan follow from it.
Buying in Hyderabad? See the 20 kVA generator page for new, used and rental options, or send an enquiry with the five items above and we will confirm the rating in writing.
Questions engineers ask
How many amps is a 20 kVA generator?
27.8 A per phase at 415 V, three-phase, at 0.8 power factor. At 400 V it is 28.9 A and at 433 V it is 26.7 A. A single-phase 20 kVA set delivers 87.0 A at 230 V. The kW rating at the same power factor is 16 kW.
What breaker size suits a 20 kVA generator?
A 40 A four-pole MCB or MCCB is usual, set above the 27.8 A full-load current with margin for motor starting; a single-phase set needs a 125 A double-pole device above its 87.0 A. The exact setting belongs to the protection coordination, because it has to protect the alternator and still ride through the largest start.
How many kW is a 20 kVA generator?
16 kW at the standard rated power factor of 0.8. The set must stay within both 16 kW and 20 kVA; whichever the load reaches first is the limit. For comfortable running, plan the load at about 12.8 kW.
How much diesel does a 20 kVA generator use per hour?
Published prime-rated figures are about 5.1 litres per hour at full load, 3.8 at 75% load and 2.7 at 50% load. Actual consumption follows the load, so a set running at half load uses close to the half-load figure.
What is the largest motor a 20 kVA set can start?
Direct on line, about 2.2 kW (3 HP) with a voltage dip the set recovers from. A larger motor needs star-delta, a soft starter or a drive, or a larger set. The motor and alternator data decide the actual case.
Full-load current at other ratings
- 5 kVA — 7.0 A at 415 V
- 7.5 kVA — 10.4 A at 415 V
- 10 kVA — 13.9 A at 415 V
- 12.5 kVA — 17.4 A at 415 V
- 15 kVA — 20.9 A at 415 V
- 25 kVA — 34.8 A at 415 V
- 30 kVA — 41.7 A at 415 V
- 40 kVA — 55.6 A at 415 V
- 45 kVA — 62.6 A at 415 V
- 50 kVA — 69.6 A at 415 V
- 62.5 kVA — 87.0 A at 415 V
- 75 kVA — 104 A at 415 V
- 82.5 kVA — 115 A at 415 V
- 100 kVA — 139 A at 415 V
- 125 kVA — 174 A at 415 V
- 250 kVA — 348 A at 415 V
- 320 kVA — 445 A at 415 V
- 750 kVA — 1043 A at 415 V
- 1010 kVA — 1405 A at 415 V
- 1250 kVA — 1739 A at 415 V
- 1500 kVA — 2087 A at 415 V
- 2000 kVA — 2782 A at 415 V
- Every rating from 7.5 to 3000 kVA — the full chart