DG Breaker, Changeover Switch and Cable Size Chart, 7.5 to 3,000 kVA

In short. Every DG set needs four things matched to its full-load current: a generator breaker, a four-pole changeover or AMF panel, power cables from the set to the panel, and an earthing system. This chart gives all of them for every common rating from 7.5 kVA to 3,000 kVA at 415 V, 50 Hz, worked out by one consistent rule: the breaker is at or above the full-load current, the changeover is at least the breaker rating, and the cable carries at least the breaker rating after derating. It then shows how far each cable can run before voltage drop reaches 3%, how to correct the cable for a hot DG room or a crowded tray, and when busduct takes over from cables. Use it for budgeting, checking a quotation or a first layout; the final selection should always be confirmed against the actual site, route and fault level.

Quick answers at 415 V

  • 62.5 kVA DG: 87 A full load, 100 A MCCB, 100 A four-pole changeover, 1 × 35 sq mm aluminium XLPE armoured cable
  • 125 kVA DG: 174 A full load, 200 A MCCB, 200 A four-pole changeover, 1 × 95 sq mm aluminium XLPE armoured cable
  • 250 kVA DG: 348 A full load, 400 A MCCB, 400 A four-pole changeover, 1 × 300 sq mm aluminium XLPE armoured cable
  • 320 kVA DG: 445 A full load, 500 A MCCB, 630 A four-pole changeover, 2 × 150 sq mm aluminium XLPE armoured cable
  • 500 kVA DG: 696 A full load, 800 A ACB, 800 A four-pole changeover, 2 × 300 sq mm aluminium XLPE armoured cable
  • 750 kVA DG: 1,043 A full load, 1,250 A ACB, 1,250 A four-pole changeover, 4 × 240 sq mm aluminium XLPE armoured cable
  • 1,010 kVA DG: 1,405 A full load, 1,600 A ACB, 1,600 A four-pole changeover, 4 × 300 sq mm aluminium XLPE armoured cable
  • 1,500 kVA DG: 2,087 A full load, 2,500 A ACB, 2,500 A four-pole changeover, 7 × 300 sq mm aluminium XLPE armoured cable (busduct is usually the better choice)

DG breaker, changeover and cable size chart (415 V, 50 Hz)

All figures are for a three-phase, four-wire DG set at 415 V. Cable sizes are 1.1 kV aluminium-conductor, XLPE-insulated, armoured cables (IS 7098 Part 1), laid in air on a perforated or ladder tray at 40 °C ambient. A single run is not derated; two or more parallel runs are spaced one cable diameter apart and given a 0.9 allowance. The last column is the longest one-way route that keeps voltage drop within 3% at full load. Tap or click any rating to get a link straight to that row.

Rating (kVA) kW at 0.8 PF Full load (A) Generator breaker (4-pole) Changeover (4-pole) Al XLPE armoured cable (runs × sq mm) Max route for 3% drop
7.5 6 10 16 A MCCB 40 A 1 × 16 281 m
10 8 14 16 A MCCB 40 A 1 × 16 211 m
15 12 21 25 A MCCB 40 A 1 × 16 141 m
20 16 28 32 A MCCB 40 A 1 × 16 106 m
25 20 35 40 A MCCB 40 A 1 × 16 84 m
30 24 42 50 A MCCB 63 A 1 × 16 70 m
40 32 56 63 A MCCB 63 A 1 × 16 53 m
45 36 63 63 A MCCB 63 A 1 × 16 47 m
50 40 70 80 A MCCB 100 A 1 × 25 67 m
62.5 50 87 100 A MCCB 100 A 1 × 35 74 m
75 60 104 125 A MCCB 125 A 1 × 50 83 m
82.5 66 115 125 A MCCB 125 A 1 × 50 76 m
100 80 139 160 A MCCB 160 A 1 × 70 90 m
125 100 174 200 A MCCB 200 A 1 × 95 99 m
140 112 195 200 A MCCB 200 A 1 × 95 89 m
160 128 223 250 A MCCB 250 A 1 × 150 117 m
180 144 250 315 A MCCB 315 A 1 × 185 127 m
200 160 278 315 A MCCB 315 A 1 × 185 115 m
250 200 348 400 A MCCB 400 A 1 × 300 138 m
275 220 383 400 A MCCB 400 A 1 × 300 125 m
320 256 445 500 A MCCB 630 A 2 × 150 117 m
380 304 529 630 A MCCB 630 A 2 × 240 152 m
400 320 556 630 A MCCB 630 A 2 × 240 144 m
450 360 626 630 A MCCB 630 A 2 × 240 128 m
500 400 696 800 A ACB 800 A 2 × 300 138 m
600 480 835 1,000 A ACB 1,000 A 3 × 240 144 m
625 500 870 1,000 A ACB 1,000 A 3 × 240 139 m
650 520 904 1,000 A ACB 1,000 A 3 × 240 133 m
750 600 1,043 1,250 A ACB 1,250 A 4 × 240 154 m
1,000 800 1,391 1,600 A ACB 1,600 A 4 × 300 138 m
1,010 808 1,405 1,600 A ACB 1,600 A 4 × 300 136 m
1,250 1,000 1,739 2,000 A ACB 2,000 A 5 × 300 138 m
1,500 1,200 2,087 2,500 A ACB 2,500 A 7 × 300 or busduct 161 m
1,750 1,400 2,435 2,500 A ACB 2,500 A 7 × 300 or busduct 138 m
2,000 1,600 2,782 3,200 A ACB 3,200 A 8 × 300 or busduct 138 m
2,250 1,800 3,130 3,200 A ACB 3,200 A 8 × 300 or busduct 122 m
2,500 2,000 3,478 4,000 A ACB 4,000 A 10 × 300 or busduct 138 m
3,000 2,400 4,174 5,000 A ACB 5,000 A 13 × 300 or busduct 149 m

Full-load current = kVA × 1000 ÷ (√3 × 415). Breaker and changeover ratings are the next standard frame at or above the current; MCCBs are shown up to 630 A and ACBs from 800 A, although MCCBs are made up to 1,600 A. Below 25 sq mm four-core cable is used, as 3.5-core cable starts at 25 sq mm; 16 sq mm is shown as the smallest practical armoured aluminium size, and small sets are often wired in copper of a smaller size. For the full-load current alone at 415 V, 11 kV and 230 V, see the generator full-load current chart.

How the chart is worked out

The chart follows the coordination rule used in IEC 60364-4-43 and the Indian wiring code: IB ≤ In ≤ IZ. The design current IB is the generator full-load current, In is the breaker rating, and IZ is what the cable can carry continuously after derating. Each column is one step of that rule.

  1. Full-load current. IB = kVA × 1000 ÷ (√3 × V). At 415 V that is 1.391 A per kVA. A 750 kVA set: 750,000 ÷ (1.732 × 415) = 1,043 A.
  2. Generator breaker. The next standard rating at or above IB: 1,043 A becomes a 1,250 A ACB. The overload release is then set close to the full-load current, so the frame size gives headroom while the setting protects the alternator.
  3. Changeover. At least the breaker rating, four-pole, and at least the mains incomer rating if that is larger: 1,250 A for the 750 kVA set.
  4. Cable. Enough parallel runs of one size so that runs × tabulated rating × derating ≥ breaker rating. For 1,250 A: four runs of 240 sq mm aluminium give 4 × 392 A × 0.9 = 1,411 A. The cable is sized to the breaker rating, not just the full-load current, so the breaker protects it whatever its setting.
  5. Voltage drop. Drop (V) = current per run × mV/A/m × length ÷ 1000. The chart gives the length at which this reaches 3% of 415 V (12.45 V) at full load. Beyond it, add a run or go up a size.

Correct the cable for your site

The chart assumes 40 °C air and cables that do not heat each other. A DG room in a Telangana summer is often 45 °C or more, and cables are frequently bunched on one tray. Multiply the cable rating by every factor that applies, then check it still carries the breaker rating.

Air temperature (XLPE, 90 °C conductor)

Ambient air Factor
30 °C 1.10
35 °C 1.05
40 °C 1.00
45 °C 0.95
50 °C 0.89
55 °C 0.84

Factor = √((90 − T) ÷ 50), relative to the 40 °C table.

Grouping on a tray, cables touching

Multicore cables in one layer Factor
1 1.00
2 0.88
3 0.82
4 0.77
6 0.73

Single layer on a perforated tray (IEC 60364-5-52, Table B.52.20). Spacing cables one diameter apart on a ladder tray recovers most of this loss.

Parallel runs of the same circuit heat each other too, so they count as grouped cables. Cables laid directly in the ground carry less than in air for the larger sizes (300 sq mm aluminium: 369 A in ground against 452 A in air), so a buried route usually needs one more run.

Aluminium cable ratings used in this chart

Size (sq mm) In ground, 30 °C (A) In air, 40 °C (A) Voltage drop (mV/A/m)
16 74 69 4.24
25 95 93 2.67
35 114 114 1.94
50 134 138 1.43
70 164 175 0.99
95 197 216 0.72
120 223 249 0.58
150 249 284 0.48
185 282 329 0.39
240 327 392 0.31
300 369 452 0.26

1.1 kV XLPE-insulated, aluminium-conductor, armoured multicore cables to IS 7098 (Part 1); conductor 90 °C, ground at 30 °C with soil thermal resistivity 1.5 K·m/W and 750 mm laying depth, air at 40 °C. Figures are typical of published Indian manufacturers’ tables and vary slightly between makes; use your chosen manufacturer’s table for the final design.

Choosing the generator breaker

Choosing the changeover: manual, ATS or AMF

Indian electrical safety regulations require a standby generator to be interlocked so that it cannot run in parallel with, or feed back into, the utility supply unless it is designed and approved to synchronise. The changeover is what guarantees this.

Arrangement How it works Where it fits
Manual changeover switch Hand-operated, three positions (mains, off, DG), mechanically prevents both sources closing together. Small and medium sets at homes, shops and sites with staff on hand to switch over.
Automatic transfer switch (ATS) Motorised four-pole switch that transfers to DG when mains fails and back when it returns, to IS/IEC 60947-6-1. Offices, hospitals, apartments and plants where the set is started automatically; 40 A to 3,200 A.
AMF panel Auto-mains-failure controller that senses mains failure, starts the engine, closes the DG breaker and returns on mains restoration; switching by two interlocked contactors, MCCBs or ACBs. Unattended standby on any size; ACB-based AMF panels are standard from about 800 A.
Synchronising panel Parallels two or more sets, or sets and mains, with load sharing. Where one set is not enough, or where redundancy (N+1) is required.

Cable practice that the chart assumes

Above 2,000 A: busduct

From about 1,500 kVA at 415 V, the breaker is 2,500 A or more and the chart needs seven to thirteen parallel runs of 300 sq mm cable. That is heavy, slow to terminate and difficult to keep balanced. A sandwich-type busduct of the same rating is the normal choice between the set and the main panel; it shares current evenly by construction, takes less space and is easier to inspect with a thermal camera. Larger installations may also generate at 11 kV, where the current falls to about one twenty-sixth (a 2,000 kVA set gives 105 A at 11 kV).

Earthing the DG set

Indian electrical safety regulations require the generator neutral to be earthed by two separate and distinct connections, and every metal body to be earthed. The usual arrangement, following IS 3043, is:

Worked examples

125 kVA set, panel 60 m away. Full-load current 174 A; breaker 200 A MCCB; changeover 200 A four-pole. One run of 95 sq mm aluminium carries 216 A in air, more than the 200 A breaker. Voltage drop: 174 A × 0.72 mV/A/m × 60 m = 7.5 V, which is 1.8% of 415 V. One run of 95 sq mm is right.

750 kVA set, 120 m route. Full-load current 1,043 A; breaker 1,250 A ACB; changeover 1,250 A. Four runs of 240 sq mm aluminium carry 4 × 392 × 0.9 = 1,411 A. Voltage drop: 1,043 ÷ 4 = 261 A per run; 261 × 0.31 × 120 ÷ 1000 = 9.7 V, which is 2.3%. Within limits.

320 kVA set in a 45 °C DG room, two runs touching on one tray. Breaker 500 A. The chart’s two runs of 150 sq mm give 2 × 284 × 0.88 (grouping) × 0.95 (air temperature) = 475 A, less than 500 A, so they are not enough here. Two runs of 185 sq mm give 2 × 329 × 0.88 × 0.95 = 550 A. Use 2 × 185 sq mm, or keep 2 × 150 sq mm and space the runs on a ladder tray.

1,010 kVA set, 200 m route. Breaker 1,600 A ACB. Four runs of 300 sq mm pass on heating (1,627 A), but voltage drop decides: 1,405 ÷ 4 = 351 A per run; 351 × 0.26 × 200 ÷ 1000 = 18.3 V, which is 4.4%. Six runs bring it down to 2.9%. On long routes, check voltage drop before ordering cable.

Common mistakes

What to send us

For a breaker, changeover and cable recommendation for your site, send the generator nameplate kVA and voltage, the mains incomer rating, the route length and how the cable is laid (tray, trench or buried), the DG room temperature in summer, the type of load (motors, UPS, drives, lighting), and the fault level of the main panel if known. Use the application engineering enquiry, call 098852 01608 or WhatsApp us on the same number.

Questions engineers ask

What size breaker does a 250 kVA DG set need?

A 250 kVA set delivers about 348 A per phase at 415 V, so the generator breaker is a 400 A four-pole MCCB with its overload release set close to 348 A. The breaking capacity (Icu) must suit the fault level of the panel it sits in, which is usually decided by the mains transformer, not by the generator.

What cable size is used for a 125 kVA DG set?

One run of 95 sq mm aluminium XLPE armoured cable (3.5-core) laid in air at 40 °C carries the 200 A breaker rating of a 125 kVA set, and keeps voltage drop within 3% up to about 99 m at full load. A hotter room, cables bunched on a tray or a longer route each push the size up; the derating tables on this page show by how much.

What changeover switch is needed for a 500 kVA generator?

A 500 kVA set delivers about 696 A at 415 V and is protected by an 800 A ACB, so the changeover is rated 800 A, four-pole. That can be an 800 A on-load changeover switch or ATS, or an AMF panel built with two mechanically and electrically interlocked 800 A ACBs. If the mains incomer is larger than the generator, the changeover is sized for the mains current instead.

Why should a DG changeover switch be four-pole?

In most Indian installations the generator neutral is earthed at the set and the transformer neutral is earthed at the substation. Switching the neutral with the phases keeps the two earthed neutrals apart, so neutral current returns to the source that is supplying it, earth fault and RCD protection see the true fault current, and the generator cannot back-feed the utility neutral.

Can 3.5-core cable be used on a generator?

Yes, where the load is mostly balanced three-phase motors and heaters, because the neutral then carries little current. Where the generator supplies UPS systems, variable-speed drives, LED lighting or IT loads, third-harmonic currents add up in the neutral and can exceed the phase current, so use four-core cable with a full-size neutral.

When should busduct be used instead of cables?

From about 2,000 to 2,500 A, which is roughly 1,500 kVA and above at 415 V. At that current a cable connection needs seven or more parallel runs of 300 sq mm, each needing its own termination and current-sharing check, whereas a single busduct run is compact, shares current by design and is quicker to install and inspect.

Is copper cable one size smaller than aluminium?

Usually, yes. A copper conductor carries roughly a quarter more current than an aluminium conductor of the same size, so the copper size is often one step smaller. Always confirm with the cable manufacturer's own copper table for the core count and laying method, and recheck voltage drop, because the smaller copper cable has a different drop per metre.

Does the chart change for a 400 V generator?

Current is about 3.75% higher at 400 V than at 415 V for the same kVA. Most rows keep the same breaker, changeover and cable because the standard sizes leave a margin, but four rows move up a size because their full-load current is within 4% of the breaker rating: 140 kVA (202 A at 400 V against a 200 A breaker), 450 kVA (650 A against 630 A), 1,750 kVA (2,526 A against 2,500 A) and 2,250 kVA (3,248 A against 3,200 A). For those, take the next breaker, changeover and cable size up.

Standards referred to

IS 7098 (Part 1), XLPE-insulated cables up to 1.1 kV. IS/IEC 60947-2, circuit-breakers. IS/IEC 60947-3, switches and switch-disconnectors. IS/IEC 60947-6-1, transfer switching equipment. IEC 60364-4-43 and IEC 60364-5-52, overcurrent protection, current-carrying capacity and grouping. IS 732, code of practice for electrical wiring installations. IS 3043, code of practice for earthing. ISO 8528 and IS/IEC 60034-1, generating set and machine ratings. Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.

Reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators, in generator service since 2001. Last reviewed 1 November 2026.