HVO / Renewable Diesel Readiness

How to prepare a diesel generator for HVO or renewable diesel: engine maker approval, fuel standards, storage and seals, filters, supply availability and what to check before switching.

In short. Hydrotreated vegetable oil (HVO) is a renewable diesel made by treating oils and fats with hydrogen. Many diesel engines can use it with little or no change, but only where the engine maker approves it. The fuel must meet a recognised specification, and the tank and filters should be cleaned before switching. HVO carries slightly less energy per litre than diesel, so a few percent more litres are used for the same output.

Who this page is for: For owners and facility managers considering renewable diesel for existing generators.

Key facts

  • Confirm engine maker approval first.
  • Buy fuel to a recognised specification.
  • Clean the tank before the change; deposits can loosen.
  • Watch filter changes closely in the first months.
  • Expect about 4–5% more litres for the same energy.
  • Confirm how local rules treat the fuel.

Worked example: a trial on one set (illustrative)

StepFinding
Maker approval checkedEngine listed as approved
Tank inspected and cleanedSludge removed before filling
First monthOne extra filter change as old deposits cleared
Load-bank testFull output; smoke visibly lower
Fuel use at the same loadabout 4% more litres than on diesel
DecisionRoll out to the other sets in stages

The small rise in litres comes from the lower energy content per litre, not from any loss of efficiency. See cleaner-fuel options and fuel consumption chart.

Do not switch fuel without the engine maker’s approval. It can affect the warranty and, on some engines, seals and fuel system parts.

Readiness checklist

CheckWhy
Maker approvalWarranty and reliability
Fuel specificationQuality
Seals, hoses and filtersMaterial compatibility
Tank conditionClean before the change
SupplyReliable local availability
Storage for standby setsFuel rotation and testing

See fuel and lifecycle decisions.

Switch-over sheet

ItemStatus
Maker approval 
Tank cleaned 
Trial set and dates 
Filter changes during trial 

What HVO is, and what it is not

Hydrotreated vegetable oil is made by reacting waste oils, fats or vegetable oils with hydrogen at high temperature and pressure. The process removes oxygen and produces straight-chain paraffinic hydrocarbons that behave very much like the paraffinic part of conventional diesel. That is why it is called renewable diesel, and why many engines can burn it without hardware changes.

It is not the same as biodiesel. Biodiesel, or FAME, is an ester made by a different chemical route. It holds oxygen, attracts water, can support microbial growth in storage and may soften some seals and hoses. Blends of biodiesel are limited by engine makers for these reasons. HVO does not carry these weaknesses in the same way, so the approvals, storage practice and blending limits for the two fuels are different and must not be confused.

PropertyConventional dieselHVOWhat it means for a generator
Chemical typeMixture of paraffins, naphthenes and aromaticsAlmost entirely paraffinicCleaner combustion, less soot
DensityAbout 0.82 to 0.845 kg per litreAbout 0.77 to 0.79 kg per litreSlightly less energy in each litre
Cetane numberTypically around 50Typically 70 or moreEasier cold starting and quieter combustion
Aromatics and sulphurPresent at controlled levelsVery lowLower particulate formation
Oxygen contentNoneNoneStorage behaviour close to diesel
LubricitySet by specification and additivesNeeds additive to meet specificationBuy only to a recognised specification

Energy content and the extra litres

Because HVO is less dense, a litre carries a little less energy than a litre of diesel, even though the energy per kilogram is slightly higher. In practice an engine burns about 4 to 5% more litres to deliver the same output. The power the engine can produce is usually unchanged within normal tolerance, because the fuel system delivers a slightly larger volume, but the maker confirms this for each engine.

A simple check shows what that means for runtime. A set that uses 40 litres per hour on diesel at its usual load would use about 41.6 to 42 litres per hour on HVO. With 800 litres usable in the tank, runtime falls from 20 hours to about 19 hours. The difference is small, but it is real, and runtime tables, fuel ordering and the reserve held for long outages are corrected before the switch, not after the first long run.

Reading an engine maker approval

Approval is the first and most important check. Engine makers publish fuel guidance that lists which fuel specifications are approved for which engine families, often with conditions. A useful approval names the engine model or family, the fuel specification, whether the fuel may be used neat or only in blends, and any change to service intervals, filters or warranty terms.

  • Engine family: confirm that the exact engine model and build fitted to the set is covered, not only a newer or older family with a similar name.
  • Fuel specification: the approval refers to a recognised paraffinic diesel specification, and the supplier must certify each delivery against it.
  • Conditions: some approvals require particular filters, more frequent filter changes in the first months, or checks of elastomer seals on older engines.
  • Warranty and insurance: confirm in writing that warranty and insurance terms remain valid on the new fuel.

Where the engine is not listed, ask the maker in writing and keep the reply. Where no approval can be obtained, the set stays on conventional diesel; a fuel change is never made on the strength of a supplier brochure alone.

Storage, tanks and filters

HVO is chemically stable and holds very little water, which makes it a good fuel for standby storage. The risk lies in the tank it goes into. Years of diesel storage leave sludge, water and microbial growth at the bottom of most tanks, and a new fuel with good solvency can loosen those deposits and carry them into the filters during the first weeks.

  1. Drain the water from the tank bottom and take a sample from the lowest point.
  2. Where sludge or microbial growth is found, clean the tank before the first HVO delivery.
  3. Change the primary and secondary fuel filters and drain the water separator.
  4. Check hoses, seals and gaskets on older engines for leaks after the first runs on HVO.
  5. Change the filters again after the first weeks of running, then return to the normal interval if they stay clean.

The fuel register records each delivery with its certificate, volume and date, so that the quality of every batch can be traced if a problem appears later.

What changes in the exhaust

Because HVO contains almost no aromatics or sulphur, engines burning it usually produce less particulate matter and less visible smoke, and often slightly less carbon monoxide and unburnt hydrocarbons. The effect on nitrogen oxides varies with the engine and its injection timing and can be small in either direction. Tailpipe carbon dioxide stays roughly the same per kilowatt-hour; the carbon benefit of HVO comes from its renewable origin across the fuel lifecycle, not from the exhaust.

A change of fuel does not by itself change the certification or the emission category of the engine. Where an emission test is needed for the set, it is carried out by the applicable method on the fuel the set actually uses, and the result is recorded with the fuel details. Claims of lower emissions are based on such measurements, not on general figures.

Planning supply and a fallback

A standby set must be able to run when it is needed, whatever happens in the fuel market. Before switching, confirm that a supplier can deliver HVO to the site at the quantities and intervals required, including during a long outage, and agree how deliveries will be certified. Keep a written fallback: if HVO is not available, the set returns to conventional diesel meeting the normal specification, which the engine accepts without any change.

Many owners start with one set on a trial, watch filter condition, starting, smoke and fuel use for a few months, and then extend the change to other sets. The trial record, the approvals and the supply arrangement together form the evidence for the decision.

Service and records after the switch

Normal service continues on HVO. Oil and filters are changed every 250 to 500 running hours or six months, whichever comes first, and coolant every year, unless the engine maker gives a different interval for the new fuel. Oil analysis at the first service after the switch shows whether fuel dilution, wear metals or soot have changed. The log book records the date of the switch, the fuel specification, every delivery and any change in fuel use per running hour, so the effect of the new fuel is visible over time.

Cold weather and long storage

HVO generally has good low-temperature behaviour, but its cloud point depends on the grade supplied, so the certificate is checked against the lowest temperature the site sees. In Telangana and Andhra Pradesh cold is rarely the limit; heat and long storage periods matter more. Tanks are kept as full as practical to limit condensation, vents and caps are checked for water entry, and a sample is drawn at each service so that the fuel in a standby tank is known to be fit before the next outage.

Common mistakes

  • Switching without approval.
  • Dirty tank at change-over.
  • No trial set.
  • Fuel quality not checked.

What to send us

Send engine details and fuel arrangements. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Values are illustrative.

Questions engineers ask

Is HVO the same as biodiesel?

No. Biodiesel is an ester that contains oxygen, attracts water and is limited to small blends by most engine makers. HVO is a paraffinic fuel made by treating oils and fats with hydrogen, with storage behaviour close to diesel. The approvals, storage practice and blending limits for the two fuels are different.

How much longer or shorter will my set run on a tank of HVO?

Slightly shorter, because each litre carries about 4 to 5% less energy. A set using 40 litres per hour on diesel uses about 42 litres per hour on HVO, so 800 litres usable gives about 19 hours instead of 20. Correct runtime tables and fuel orders before the switch.

Do I need to change the oil or service intervals on HVO?

Usually not, unless the engine maker says otherwise. Oil and filters stay at 250 to 500 running hours or six months, whichever comes first, and coolant every year. Change fuel filters again a few weeks after the switch, and use oil analysis at the first service to confirm nothing has changed.

Can I go back to diesel after using HVO?

Yes. An engine approved for HVO also runs on conventional diesel meeting the normal specification, and the two can usually be mixed in the tank during a change. Keeping diesel as a written fallback protects standby duty if HVO supply is interrupted, and the fuel register records which fuel is in use.

Is HVO a drop-in fuel?

For many engines it is, but only with the engine maker approval for that exact model and fuel system. Confirm the approval in writing, check older engines for seal compatibility, and keep the approval with the set documents. Fuel filters may need changing more often for a while after the switch.

Does it change emissions rules treatment?

Check the local rules for the specific set. A change of fuel does not by itself change the certification of the engine, and some regimes treat renewable fuels differently. Confirm in writing how the applicable rules treat the set on HVO before switching, and keep that confirmation with the set records.

Can I mix it with diesel?

Often possible, because HVO is a paraffinic fuel close to conventional diesel, but confirm the permitted blend with the engine maker guidance for your model. Record each delivery and the blend in the fuel register, and keep the tank clean, since any fuel change can loosen deposits that then block filters.

Is supply easy?

It depends on the region and the volumes needed. Check that a supplier can deliver reliably at the quantities and intervals the site requires before committing, and plan a fallback to conventional diesel for times when supply is interrupted, so the standby duty of the set is never put at risk.

General guidance only. Follow engine maker guidance.