In short. A bi-fuel set runs on one of two fuels at a time and switches between them. A dual-fuel set burns diesel and gas together. Suppliers do not always use these two terms the same way, so confirm which one is being offered. Bi-fuel gives resilience: if one fuel fails, the set carries on with the other. What decides success is how it switches (automatically or by the operator), whether power stays continuous during the switch, what output is available on each fuel, and the safety and upkeep of two fuel systems.
Who this page is for: For owners of remote or critical sites wanting a generator that can carry on when one fuel supply fails.
Key facts
- Bi-fuel: one fuel at a time. Dual fuel: two fuels together.
- Switching can be automatic on supply loss, or manual.
- Output may be lower on the alternate fuel.
- Check whether power stays continuous during a switch.
- Two fuel systems mean two sets of storage, safety and maintenance.
- Test the switch on load before relying on it.
Bi-fuel and dual fuel compared
| Item | Bi-fuel | Dual fuel |
|---|---|---|
| Fuel use | One at a time | Diesel and gas together |
| Switching | On failure or by choice | Ratio managed continuously |
| Main aim | Fuel resilience | Diesel replacement |
Worked example: a switch test (illustrative)
| Step | Result |
|---|---|
| 375 kVA set (300 kW at 0.8 power factor) on gas at 90% load (270 kW); gas supply closed | Low gas pressure detected |
| Automatic switch to the alternate fuel | Frequency dipped briefly, then recovered |
| Output on the alternate fuel | Derated by about 15% (255 kW available); 30 kW of non-essential load shed |
| Event log | Switch recorded with time and cause |
Without the test, nobody would have known that load shedding was needed on the alternate fuel. See dual-fuel engineering and cleaner-fuel options.
Do not assume the set gives full output on both fuels. Check the rating on each, and arrange load shedding if the alternate fuel gives less.
Operating modes
| Mode | Description |
|---|---|
| Primary fuel | Runs on the preferred fuel |
| Automatic fallback | Switches if primary pressure or quality fails |
| Manual selection | Operator chooses the fuel |
See renewable diesel.
Bi-fuel test sheet
| Test | Result |
|---|---|
| Switch on primary fuel loss, on load | |
| Output on alternate fuel | |
| Return to primary fuel | |
| Event logged |
Which engines can really be bi-fuel
True bi-fuel operation, where the engine runs on either fuel alone, belongs to spark-ignited gas engines. The usual pair is piped natural gas as the primary fuel with LPG vapour as the reserve, or the other way round where piped gas is not available. Both are gaseous fuels burnt with a spark, so the engine needs a second fuel train, a second set of settings for ignition timing and air-fuel ratio, and a controller that changes between them.
A diesel engine is different. It ignites fuel by compression and cannot run on gas alone, so a diesel engine that uses gas is a dual-fuel engine: it always burns some diesel as the pilot, and if the gas fails it carries on with diesel only. That arrangement also gives fuel resilience, but the reserve fuel is diesel and the gas side is the part that drops out. The difference matters when a supplier describes a converted diesel set as bi-fuel, because the switching behaviour, the rating and the emission obligations all follow from which of the two it really is.
Decision matrix for fuel resilience
| Site situation | Arrangement usually considered | Main point to check |
|---|---|---|
| Piped natural gas, outages of the gas network are rare but serious | Gas engine, bi-fuel with LPG reserve | Rating on LPG and the size of the LPG store |
| No piped gas, LPG delivered in bulk | Gas engine on LPG, natural gas not available | Vaporiser capacity at full load in cold weather |
| Existing diesel set, gas available nearby | Dual-fuel conversion with diesel fallback | Engine suitability and maker approval for the conversion |
| Critical load, any fuel interruption unacceptable | Two separate sets on different fuels, or diesel standby beside a gas set | Transfer and load sharing between the sets |
| Short occasional outages only | Single-fuel diesel set with adequate tank | Fuel quality and refill arrangements |
The matrix is a starting point, not a selection. Each row still needs the load list, the fuel supply data and the maker documentation for the actual engine.
Rating on each fuel
An engine rarely gives the same output on two fuels. Natural gas and LPG differ in heating value, in the volume of mixture the engine can draw in, and in their resistance to knock, so the maker publishes a separate rating, ignition timing and load acceptance for each. On some engines the reserve fuel gives less output because timing must be retarded to avoid knock; on others the difference is small. A derating of 5 to 20% on the reserve fuel is not unusual, and the generator nameplate rating in kVA is only valid for the fuel and conditions it was stated for.
The practical consequence is a load plan for each fuel. In the worked switch test above, the set lost 15% of its output on the alternate fuel and 30 kW of non-essential load had to be shed. That shedding must happen automatically and before the switch, or within the time the engine can carry the overload, otherwise the switch itself causes the outage it was meant to prevent.
Continuity during the fuel change
Whether power stays on during a fuel change depends on the design of the fuel trains and the controller, and it must be stated by the maker and proved on site. There are three common patterns:
- Change on load: the controller closes one fuel valve and opens the other while the engine runs, changing timing and mixture settings together. A short frequency and voltage dip is normal; its depth and recovery time are the figures to record.
- Change with a pause: the engine is unloaded, the fuel is changed at idle or rated speed, and the load is returned. The supply is interrupted unless a UPS or a second source carries it.
- Change at standstill: the engine is stopped, the fuel is selected and the engine restarted. This is a fuel option rather than resilience, and the site should be told so plainly.
Where loss of the primary fuel is detected by low supply pressure, the detection setting and delay decide how much the engine has already starved before the change begins. A setting too close to the normal pressure gives nuisance changes on every load step; a setting too low lets the engine stall first.
Controls, interlocks and protection
Two fuel systems on one engine need interlocks that make the unsafe states impossible rather than unlikely. The arrangement is set out on a drawing and tested at commissioning.
- Each gas train has two automatic shut-off valves in series, with a valve-proving check where the train design calls for it, and a manual isolating valve outside the room.
- The two fuel trains are interlocked so that only one feeds the engine, except during a transition the maker has designed for.
- Low and high gas pressure switches on each train trip or change fuel as set out in the control logic, with the action recorded in the event log.
- Gas detection, loss of room ventilation and fire detection close all fuel valves and stop the engine.
- Emergency stop removes both fuels and the ignition, not only the engine controller output.
Leak detection and ventilation
Natural gas is lighter than air and collects near the ceiling; LPG vapour is heavier than air and collects at floor level and in any pit, trench or drain. A room or enclosure that houses both needs detectors at both levels, and the LPG side needs a layout without low points where vapour can gather. Detectors are calibrated and tested at the intervals the detector maker states, with the test recorded, because a detector that has drifted gives false confidence.
Ventilation is sized for both engine combustion air and dilution of any leak, and its failure is monitored. Gas pipework is pressure tested after installation and after any modification, and joints inside the room are kept to the minimum.
Fuel storage and supply capacity
The reserve fuel only provides resilience if it is there, in condition, and able to flow at full load. For LPG, the vaporisation rate of cylinders or a bulk vessel falls in cold weather and as the vessel empties, so larger loads need a vaporiser sized for the full-load gas flow. Storage quantities, separation distances and licensing follow the rules that apply to the quantity stored, and these are confirmed with the authority before the layout is fixed.
For piped natural gas, the meter and regulator must pass the full-load flow with the pressure still above the low-pressure trip setting during a load step. Many apparent fuel failures at commissioning are a regulator or pipe size problem, not a supply failure. Where the alternate fuel is diesel in a dual-fuel set, the tank is managed like any standby diesel store, with sampling, water draining and turnover.
Commissioning acceptance
| Test | Acceptance criterion |
|---|---|
| Gas train leak and pressure test | No leak at the test pressure; result signed |
| Load steps on the primary fuel | Recovery within the limits agreed for the load |
| Load steps on the reserve fuel | Within the reserve-fuel rating from the maker |
| Change on loss of primary fuel, on load | Dip and recovery recorded; essential loads stay on |
| Return to primary fuel | Change completed as designed; event logged |
| Gas detection, ventilation failure and fire signals | All fuel valves close; engine stops |
| Emergency stop | Both fuels and ignition removed |
| Load shedding on reserve fuel | Shed loads trip before the overload |
Completed test sheet (illustrative)
| Test | Recorded result |
|---|---|
| Switch on primary fuel loss, on load | Gas closed at 270 kW; change completed; frequency dip 3.8 Hz, recovered in 4 s |
| Output on alternate fuel | 255 kW held for 1 h; exhaust temperatures within the maker limits |
| Return to primary fuel | Gas restored; change back after the set delay; dip 2.1 Hz |
| Event logged | Both changes recorded with time, cause and fuel pressures |
The figures are an illustration of what a complete record looks like. The value of the sheet is in comparing each yearly test with the commissioning result: a deeper dip or a slower recovery than last year points to a regulator, valve or setting that has changed.
Maker approval and conversions
A bi-fuel or dual-fuel arrangement is accepted only with documentation from the engine maker, or from a conversion supplier whose kit is approved for that engine model. The documents state the rating on each fuel, the settings, the emission compliance on each fuel and the effect on the engine warranty. An undocumented conversion leaves the owner without a rating to plan the load against and without a basis for any warranty or compliance claim.
Common mistakes
- Switch never tested on load.
- Full output assumed on both fuels.
- Alternate fuel left stale in storage.
- One fuel system neglected.
What to send us
Send fuel options, loads and the outage risks you want to cover. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. Values are illustrative.
Questions engineers ask
Can a diesel generator be converted to run on gas alone?
No. A diesel engine ignites its fuel by compression and needs diesel as the pilot, so a converted diesel set is dual-fuel and falls back to diesel only when gas fails. Running on gas alone needs a spark-ignited gas engine, which is a different engine rather than a conversion.
Why does an LPG installation need gas detectors near the floor?
LPG vapour is heavier than air, so a leak flows downwards and collects at floor level and in pits, trenches and drains. Natural gas is lighter than air and rises. A room with both fuels needs detectors at both levels, linked to close the fuel valves and stop the engine.
Does output drop on gas?
Often, and it can also differ between the two gaseous fuels of a bi-fuel engine. Heating value, the mixture volume the engine can draw in and knock resistance all change with the fuel, so the maker states a separate rating for each. Plan the load on the lower rating, or shed non-essential load automatically before the fuel changes.
Is switching on load possible?
It depends on the design. Some engines change fuel while running with a short frequency and voltage dip, others need the load removed for the change, and some change only at standstill. The maker states which applies, and an on-load test at commissioning proves the dip, the recovery time and whether the essential loads stay on.
Is bi-fuel the same as dual fuel?
No. A bi-fuel engine runs on one fuel at a time and can run on either fuel alone, which in practice means a spark-ignited gas engine with natural gas and LPG. A dual-fuel engine burns diesel and gas together, always needs some diesel as the pilot, and falls back to diesel only when gas fails.
Is maintenance doubled?
Not doubled, but both fuel systems need regular care. Each gas train needs its valves, regulators, pressure switches and leak detection tested, the reserve fuel must be kept in usable condition, and the fuel change itself should be tested on load at least once a year so that a fault is found before a real supply failure.
General guidance only. Use maker data.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.