Cleaner-Fuel Generator Systems

An overview of cleaner-fuel options for generator sets: natural gas, biogas and Bio-CNG, LPG, HVO and bi-fuel. Fuel properties, supply, safety, performance and how to compare them.

In short. Cleaner-fuel generator systems replace or reduce diesel with natural gas, biogas, LPG or renewable diesel. Each fuel brings its own supply, storage, safety, performance and cost questions. Choose from the site’s fuel access and the set’s duty, not from a general claim. Standby sets care most about fuel that is always there; prime sets care most about running cost.

Who this page is for: For owners and consultants comparing fuel options for new or existing generators.

Key facts

  • Pipeline gas needs no storage but depends on the network.
  • Compressed or bottled gas needs safe storage and reliable deliveries.
  • Biogas needs cleaning and drying; its quality varies.
  • Renewable diesel needs little hardware change but needs engine maker approval.
  • Gas sets usually take load steps less readily than diesel.
  • For critical standby, keep a fuel that is stored on site.

Fuel options compared

FuelStorageMain consideration
DieselTank on siteEmission control
Pipeline natural gasNoneSupply continuity
Compressed natural gasHigh-pressure cylindersDelivery and pressure safety
BiogasGas holderCleaning, drying and quality
LPGPressure vesselsStorage safety and vaporisation
Renewable dieselTank on siteMaker approval and supply

Worked example: three sites, three fuels (illustrative)

SiteDuty and accessChoice
Food plantPrime power, pipeline at the gate, heat neededGas set with heat recovery; diesel kept for critical loads
Remote hospitalStandby; gas deliveries unreliableDiesel set; renewable diesel only if the maker approves it and supply is reliable
Dairy farmLong hours; biogas from wasteBiogas set with gas cleaning; diesel backup

See gas generators, renewable diesel and bi-fuel sets.

Do not rely on a pipeline alone for critical standby power. A regional supply problem can stop the gas exactly when mains is also down.

Fuel choice sheet

QuestionAnswer
Duty: standby or prime? 
Fuels available at site 
Storage space and safety distances 
Heat use on site? 

Comparing fuels on energy, not on volume

Fuels are bought in different units: diesel and HVO by the litre, natural gas by the standard cubic metre, LPG by the kilogram and biogas by whatever the digester produces. A fair comparison converts each to the energy it delivers and then to the fuel needed per kilowatt-hour at the real load of the set. The table gives typical lower heating values for screening; actual values come from the supplier or a gas analysis.

FuelTypical energy contentUnit boughtPoints to note
DieselAbout 10 kWh per litreLitreReference fuel for most standby sets
HVOAbout 9.5 kWh per litreLitreAbout 4 to 5% more litres for the same energy
Natural gasAbout 9.5 to 10.5 kWh per standard cubic metreStandard cubic metreComposition varies by source
LPGAbout 12.8 kWh per kilogramKilogramStored as a liquid under pressure
BiogasAbout 5 to 7 kWh per cubic metreCubic metreDepends on methane content, often 50 to 70%

The engine efficiency at the operating load matters as much as the fuel. A diesel set at a healthy load turns about 35 to 40% of the fuel energy into electricity, and a gas engine may be similar or a little lower. At light load both efficiencies fall, so a fuel comparison made at full load can mislead for a set that spends most of its hours lightly loaded.

Working the numbers for one site

Consider a set that delivers 200 kW on average for 2000 hours a year, which is 400,000 kWh. At 35% efficiency the engine takes in about 1,143,000 kWh of fuel energy. On diesel at 10 kWh per litre that is about 114,000 litres a year. On natural gas at about 10 kWh per standard cubic metre, a dedicated gas engine at a similar efficiency would draw about 114,000 standard cubic metres. On HVO it would be about 120,000 litres.

These figures are then multiplied by the delivered price of each fuel at the site, with the cost of any new engine, conversion kit, gas connection, storage and the change in maintenance added over the same years. The result can differ completely from one site to the next, which is why the comparison is always made with the site load profile and local supply terms rather than general claims.

Natural gas: pipeline, compressed and liquefied

Where a city gas pipeline reaches the site with enough pressure and capacity, natural gas offers continuous supply without on-site storage, low particulate emissions and no fuel deliveries. The site needs a gas meter, pressure regulation, safety shut-off valves, gas detection and a gas train designed for the engine. Where there is no pipeline, compressed or liquefied gas delivered by road is possible but needs storage, regasification or pressure reduction, and approvals for the quantities held.

For standby duty the key question is availability during an emergency. A pipeline can be affected by the same event that cuts electricity, and delivered gas depends on road access. Many owners therefore keep a diesel set, or a dual-fuel arrangement that can return to diesel, for the most critical loads.

Biogas on farms, dairies and treatment plants

Biogas suits sites that already produce organic waste, such as dairies, food processors, poultry farms and sewage treatment plants. The gas is usually 50 to 70% methane, with carbon dioxide, moisture and hydrogen sulphide. Before it reaches the engine it is dried and cleaned, because moisture condenses in the gas train and hydrogen sulphide forms acids that attack the engine and degrade the oil.

  • A gas holder smooths the difference between production and engine demand.
  • Methane content is monitored, and the engine settings are made for the leanest gas the site expects.
  • Oil analysis at shorter intervals shows whether gas cleaning is working.
  • A backup source, often grid supply or a diesel set, covers periods of low gas production.

Dual fuel as a bridge

A dual-fuel conversion lets an existing diesel engine burn a mixture of gas and diesel, with the diesel acting as the ignition source. It keeps the ability to run on diesel alone when gas is unavailable, which suits sites with an uncertain gas supply. The share of diesel replaced depends strongly on load: it is small at light load and highest in the middle and upper load range. The conversion kit must be approved for the engine, and emissions in each load band are measured after conversion, because some pollutants fall while others, such as unburnt methane at light load, can rise.

Using less fuel of any kind

Before changing fuel, it is worth reducing how much fuel the site needs. A battery that carries light loads and short outages lets the generator stop instead of idling, and a solar array with a suitable controller can reduce daytime running. Better maintenance restores fuel efficiency that has drifted, and load management keeps sets at a healthy load. These measures cut emissions on every fuel, and they often cost less than a fuel change.

Safety and approvals for each fuel

FuelMain hazardsTypical requirements
Diesel and HVOSpills, fire in storageBunded storage, separation distances, approvals above set quantities
Natural gasLeaks, explosive mixturesGas detection, ventilation, shut-off valves, safe pipe routing
LPGHeavier-than-air leaks collecting lowStorage approvals, separation, low-level detection
BiogasToxic hydrogen sulphide, leaksGas cleaning, detection, ventilation, safe flaring of surplus

The approvals required depend on the fuel, the quantity stored and the location, and they are confirmed with the relevant authorities before equipment is ordered.

A short decision path

  1. Record the load profile, running hours and outage pattern of each set.
  2. List the fuels actually available at the site, with reliable supply terms.
  3. Compare fuel per kilowatt-hour at the real load, with equipment, conversion and maintenance costs over the same period.
  4. Check approvals, safety requirements and the effect on standby reliability.
  5. Trial the preferred option on one set and measure fuel, emissions and reliability.
  6. Decide set by set, and keep diesel capability where the standby duty depends on it.

Records that prove the result

Whatever fuel is chosen, the case for it rests on records. For each set, keep the fuel bought or metered each month, the running hours, the energy generated from the controller or an energy meter, and the average load. From these, litres or cubic metres per kilowatt-hour show efficiency, and a trend that rises points to a fault or a change in duty.

Emission measurements, taken by the applicable method after any change, sit alongside the fuel records, so that a claim of cleaner running is supported by numbers. A yearly review compares the results with the assumptions made when the fuel was chosen, and the decision is revisited if prices, supply or rules have changed in the meantime. These same records also support approvals, insurance and any future decision to replace or retrofit the set.

Where fuel comparisons usually go wrong

  • Comparing price per litre or per cubic metre instead of cost per kilowatt-hour delivered at the real load.
  • Using a full-load efficiency for a set that spends most of its hours at light load.
  • Ignoring the cost and time of gas connections, storage approvals and conversion work.
  • Assuming lower emissions without measuring them after the change.
  • Removing diesel capability from a standby set whose duty depends on fuel stored on site.

Each of these errors can turn a promising option into a disappointing one, and each is avoided by working from site data and a short trial on one set before a wider change.

Common mistakes

  • Choosing on a headline claim.
  • Pipeline gas for critical standby with no backup.
  • Biogas used uncleaned.
  • Load steps not checked on gas.

What to send us

Send your duty, fuel access and loads. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. The examples are illustrative.

Questions engineers ask

How do I compare diesel and gas fairly?

Convert each fuel to the energy it delivers, divide by the engine efficiency at the real load, and multiply by the delivered price at the site. Add equipment, conversion, connection and maintenance costs over the same years. A comparison at full load can mislead for sets that run mostly at light load.

Is LPG a practical generator fuel?

It can be where pipeline gas is not available and diesel storage is difficult. LPG carries about 12.8 kWh per kilogram and is stored as a pressurised liquid, which needs approved storage, separation distances and leak detection at low level. The engine must be designed or approved for LPG.

Should a standby set move away from diesel?

Not always. For standby duty with few running hours, availability during an emergency matters most, and diesel stored on site is independent of pipelines and road deliveries. Many owners keep diesel, or a dual-fuel set that can return to diesel, for critical loads, and change fuel only on long-running sets.

What should a fuel trial record?

Fuel used per kilowatt-hour in each load band, starting and load acceptance, smoke and measured emissions, filter condition, alarms and any returns to backup fuel. Run it long enough to cover normal duty, compare with the same set on its previous fuel, and base the fleet decision on the measured result.

Is gas always cheaper?

It depends on local fuel prices and the engine efficiency on each fuel. Compute the cost per kilowatt-hour at your real load for each option, add the conversion or equipment cost, maintenance and any change in output, and compare them over the same running hours. The answer differs from site to site.

Is biogas reliable?

Only with consistent gas quality and supply. Biogas methane content varies with the digester, and moisture and hydrogen sulphide must be removed before the engine. A reliable biogas installation monitors gas quality, has storage to smooth supply, and keeps a backup fuel or source for the times when gas production falls.

Do I need new equipment?

Often some conversion of the existing set, such as a dual-fuel kit approved for the engine, or a new set designed for the fuel. The gas train, safety systems, ventilation and controls are part of the change, and the engine maker or kit supplier confirms the rating and settings on the new fuel.

Are emissions guaranteed lower?

Not guaranteed. Verify the result for the specific engine and fuel, because some pollutants fall while others, such as carbon monoxide or unburnt methane, can rise. Measure emissions in each load band after the change by the applicable method, and compare them with the limits that apply to the set.

General guidance only. Verify fuel and engine data.